NDAC 33.1-24-08-40
Reporting of suspected releases
Cite as N.D. Admin. Code ยง 33.1-24-08-40
Owners and operators of underground storage tank systems must report to the department within
twenty-four hours, or another reasonable period specified by the department, and follow the procedures
in section 33.1-24-08-42 for any of the following conditions:
1.
The discovery by owners and operators or others of released regulated substances at the
underground storage tank site or in the surrounding area (such as the presence of free
product or vapors in soils, basements, sewer and utility lines, and nearby surface water);
2.
Unusual operating conditions observed by owners and operators (such as the erratic behavior
of product dispensing equipment, the sudden loss of product from the underground storage
tank system, an unexplained presence of water in the tank, or liquid in the interstitial space of
secondarily contained systems), unless:
a.
The system equipment or component is found not to be releasing regulated substances
to the environment;
b.
Any defective system equipment or component is immediately repaired or replaced; and
c.
For secondarily contained systems, except as provided for in paragraph 4 of
subdivision b of subsection 7 of section 33.1-24-08-33, any liquid in the interstitial space
not used as part of the interstitial monitoring method (for example, brine filled) is
immediately removed.
3.
Monitoring results, including investigation of an alarm, from a release detection method
required under sections 33.1-24-08-31 and 33.1-24-08-32 that indicate a release may have
occurred unless:
a.
The monitoring device is found to be defective, and is immediately repaired, recalibrated,
or replaced, and additional monitoring does not confirm the initial result;
b.
The leak is contained in the secondary containment and:
(1)
Except as provided for in paragraph 4 of subdivision b of subsection 7 of section
33.1-24-08-33, any liquid in the interstitial space not used as part of the interstitial
monitoring method (for example, brine filled) is immediately removed; and
(2)
Any defective system equipment or component is immediately repaired or replaced.
c.
In the case of inventory control, described in subsection 1 of section 33.1-24-08-33, a
second month of data does not confirm the initial result or the investigation determines
no release has occurred; or
d.
The alarm was investigated and determined to be a nonrelease event (for example, from
a power surge or caused by filling the tank during release detection testing).