NDAC 33-33-05-02
Passageway devices - General alarm
Cite as N.D. Admin. Code ยง 33-33-05-02
Lodging establishments or assisted living facilities without direct access from sleeping rooms to the
outside shall have hallways or exit corridors equipped with listed smoke detection devices. Hallway or
exit corridor smoke detection devices shall be wired into an approved fire alarm system so as to sound
an alarm when any of the smoke detection devices are activated. Audible signaling appliances shall be
located so as to be clearly heard throughout the facility regardless of the maximum noise level under
normal conditions of occupancy. In all cases one appliance must be installed at manufacturer's
recommendations or for each thirty feet [9.15 meters] of hallway or exit corridor or fraction thereof.