NDAC 45-18-01-04
Fire prevention rules
Cite as N.D. Admin. Code ยง 45-18-01-04
The fire prevention rules for this state include the following:
Fire code. The State Fire Code includes:
1.
The provisions of the State Building Code, effective January 1, 2023, providing for fire-safe
construction and operation, as provided for in North Dakota Century Code section 54-21.3-03.
2.
The provisions of the International Fire Code (IFC), 2021 edition International Code Council
(ICC), with the following exceptions and modifications:
a.
Chapter 1. Scope and administration.
101.1 Title. The words "[NAME OF JURISDICTION]" are replaced with "North Dakota".
102.4 Application of building code. Insert "as amended by the State of North Dakota"
after the words "International Building Code" in both instances.
103.1 Creation of agency. The words "[INSERT NAME OF DEPARTMENT]" is replaced
with "North Dakota fire marshals division".
105.1.1 Permits required. The words "obtain the required permit" are replaced with
"may be required to obtain a permit".
106.4 Retention of construction documents. Remove the words "One set of approved
construction documents shall be returned to the applicant, and said set shall be kept on
the site of the building or work at all times during which the work authorized thereby is in
progress."
112.4 Violation penalties. Does not apply.
b.
Chapter 2. Definitions.
Commercial motor vehicle. Commercial motor vehicle is amended to read as follows:
"Refer to North Dakota Century Code section 39-06.2-02 for commercial motor vehicle
definition."
Fireworks. Fireworks is amended to read as follows: "Refer to North Dakota Century
Code chapter 23-15 for the fireworks definition."
Residential child care building. For the purposes of child care fire safety inspections, a
residential child care building is defined as a maximum of 30 children in a building
designed for residential purposes (i.e. single family dwelling, single apartment, etc.).
Commercial child care or preschool building. For the purposes of child care fire
safety inspections, a commercial child care or preschool building is defined as any
building licensed for over 30 children, or any building designed for commercial purpose
regardless of the number of occupants.
c.
Chapter 3. General requirements.
308.1.4 Open-flame cooking devices. Insert "or decks" after the word "balconies".
Exception 3. The words "2 ยฝ pounds [nominal 1 pound (0.454 kg)" is replaced with
"47.8 pounds [nominal 20 pounds (9 kg)".
308.1.6.3 Sky lanterns. Does not apply.
308.3 Group A occupancies. Exception 1. The following is added: "1.4 Open-flame
devices for food warming."
314.4 Vehicles. Insert "Batteries may remain connected if keys are not in ignition
system." immediately after subsection 1's "safety features." as a subsection a. Delete
"Fuel in fuel tanks does not exceed one-quarter tank or 5 gallons (19 L) (whichever is
least)" and renumber accordingly.
d.
Chapter 5. Fire service features.
510.1 Emergency responder radio coverage in new buildings. In the first sentence,
replace "New" with "Where required by the fire code official, new".
e.
Chapter 8. Interior finishes.
806.1.1 Restricted occupancies. Insert the following exception:
"3. For purposes of this provision, churches shall not be deemed public buildings and
may utilize natural or resin-bearing cut trees in the alter area of the church. No electric
lighting is allowed on the tree."
f.
Chapter 9. Fire protection and life safety systems.
903.2.8 Group R. The following exception is added: after "fire area." add "Exception:
Sprinklers are not required in single family dwellings or residential buildings that contain
no more than two dwelling units and no higher risk occupancy within the same building."
903.3.1.1.1 Exempt locations is amended by adding the following exception:
"7. Elevator machine room and machinery spaces. Where sprinklers are not installed in
elevator machine rooms, shunt trip required in accordance with IBC 3005.5 shall not be
installed."
903.3.5 Water supplies. After the words "fire code official." add "Underground water
supply piping shall be constructed of a material allowed by the North Dakota State
Plumbing Code and shall be allowed to extend into the building through the slab or wall
not more than 24 inches."
905.1.1 Standpipe hose. Add the following "The installation of the fire hose on
standpipes may be omitted when approved by the fire code official. Approved standpipe
hose valves and connections shall be provided where required."
907.8.3 Fire alarm system interface. Delete this paragraph in its entirety.
g.
Chapter 10. Means of egress.
1009.8.1 System requirements. After the words "monitoring location" delete the words
"or 9-1-1".
1103.5.1 Group A-2. After the word "Where" remove the words "alcoholic beverages are
consumed" and immediately add the words "a state liquor license is applied for or,
renewed or in-place".
h.
Chapter 23. Wood.
2301.1 Scope. After the words "in accordance with this chapter and" insert the words
"/or". After the words "International Mechanical Code" insert the words "NFPA 30 and
NFPA 30A."
i.
Chapter 61. Liquefied petroleum gases.
6101.3 Construction documents. After the word "Where" delete "a single LP gas
container is more than 2,000 gallons (750 L) in water capacity or".
6108.1 General. After the words "(15,140 L)" insert "at the request of the AHJ".