Rule 3701:1-52-10. Fire protection

Last amended: 2002Year: 2026Length: 112 wordsOfficial source
119.03 (A) The radiation room at a panoramic irradiator must have heat and smoke detectors. The detectors must activate an audible alarm. The alarm must be capable of alerting a person who is prepared to summon assistance promptly. The sources must automatically become fully shielded if a fire is detected. (B) The radiation room at a panoramic irradiator must be equipped with a fire extinguishing system capable of extinguishing a fire without the entry of personnel into the room. The system for the radiation room must have a shut-off valve to control flooding into unrestricted areas. Last updated August 1, 2023 at 2:39 PM Supplemental Information Authorized By: 3748.04 Amplifies: 3748.04 4/19/2027