OAC 310:667-41-2
Renovation
Cite as Okla. Admin. Code § 310:667-41-2
(a)
Where renovation or replacement work is done within an existing
facility, all new work or additions, or both, shall comply, insofar as
practical, with applicable sections of these standards and with
appropriate parts of NFPA 101, 2000 edition, covering New Health Care
Occupancies. Where major structural elements make total compliance
impractical or impossible, exceptions may be considered by the
Department. This does not guarantee that an exception shall be granted,
OAC 310:667
OKLAHOMA STATE DEPARTMENT OF HEALTH
106
September 13, 2019
but does attempt to minimize restrictions on those improvements where
total compliance would not substantially improve safety, but would
create an unreasonable hardship. These standards shall not be construed
as prohibiting a single phase of improvement. For example, a facility
may plan to replace a flammable ceiling with noncombustible material but
lacks funds to do other corrective work. However, they are not intended
as an encouragement to ignore deficiencies when resources are available
to correct life-threatening problems.
(b)
When
construction
is
complete,
the
facility
shall
satisfy
functional requirements for the appropriate classification (general
medical surgical hospital, psychiatric hospital, etc.) in an environment
that shall provide acceptable care and safety to all occupants.
(c)
In renovation projects and those making additions to existing
facilities, only that portion of the total facility affected by the
project shall comply with applicable sections of these standards and
with appropriate parts of NFPA 101, 2000 edition, covering New Health
Care Occupancies.
(d)
Those existing portions of the facility which are not included in
the renovation but which are essential to the functioning of the
complete facility, as well as existing building areas that receive less
than substantial amounts of new work shall, at a minimum, comply with
that section of NFPA 101, 2000 edition, for Existing Health Care
Occupancies.
(e)
Conversion to other appropriate use or replacement shall be
considered when cost prohibits compliance with acceptable standards.
(f)
When a building is converted from one occupancy to another, it
shall comply with the new occupancy requirements. For purpose of life
safety, a conversion from a hospital to a nursing home or vice versa is
not considered a change in occupancy.
(g)
When parts of an existing facility essential to continued overall
facility operation cannot comply with particular standards, those
standards may be waived by the Commissioner of Health if patient care
and safety are not jeopardized.
(h)
Renovations, including new additions, shall not diminish the
safety level that existed prior to the start of the work; however,
safety in excess of that required for new facilities is not required.
(i)
Nothing in this Chapter shall be construed as restrictive to a
facility that chooses to do work or alterations as part of a phased
long-range safety improvement plan. It is emphasized that all hazards
to life and safety and all areas of noncompliance with applicable codes
and regulations, shall be corrected as soon as possible in accordance
with a plan of correction.