OAC 310:667-41-4
Provisions for disasters
Cite as Okla. Admin. Code § 310:667-41-4
(a)
General. In locations where there is a history of tornadoes,
flooding, earthquakes, or other regional disasters, planning and design
shall consider the need to protect the life safety of all health care
facility occupants and the potential need for continuing services fol-
lowing such a disaster. When consistent with their functional program
and disaster planning, acute care facilities with emergency services can
serve as receiving, triage and initial treatment centers in the event of
nuclear, biological, or chemical (NBC) exposure. These facilities shall
designate specific area(s) for these functions.
(b)
Wind and earthquake resistant design for new buildings. Facilities
shall be designed to meet the requirements of the building codes
specified
in
OAC
310:667-41-1,
provided
these
requirements
are
substantially equivalent to American Society of Civil Engineers ASCE 7-
93. Design shall meet the requirements of ASCE 7-93.
(1)
For those facilities that must remain operational in the
aftermath of a disaster, special design shall be required to protect
systems and essential building services such as power, water, medical
gas systems, and, in certain areas, air conditioning. In addition,
consideration shall be given to the likelihood of temporary loss of
externally supplied power, gas, water, and communications.
(2)
The owner shall provide special inspection during construction
of seismic systems described in Section A.9.1.6.2 and testing in
Section A.9.1.6.3 of ASCE 7-93.
(3)
Roof coverings and mechanical equipment shall be securely
fastened or ballasted to the supporting roof construction and shall
provide weather protection for the building at the roof. Roof
covering shall be applied on clean and dry decks in accordance with
the
manufacturer's
instructions,
these
standards,
and
related
references. In addition to the wind force design and construction
requirements specified, particular attention shall be given to
roofing, entryways, glazing, and flashing design to minimize uplift,
impact damage, and other damage that could seriously impair
functioning of the building. If ballast is used it shall be designed
so as not to become a projectile.
(c)
Flood protection. Possible flood effects shall be considered when
selecting and developing the site. Insofar as possible, new facilities
shall not be located on designated flood plains. Where this is
unavoidable, the United States Corps of Engineers regional office shall
OAC 310:667
OKLAHOMA STATE DEPARTMENT OF HEALTH
108
September 13, 2019
be consulted for the latest applicable regulations pertaining to flood
insurance and protection measures that may be required.
(d)
Supplies. Should normal operations be disrupted, the facility
shall provide adequate storage capacity for, or a functional program
contingency plan to obtain, the following supplies: food, sterile
supplies, pharmacy supplies, linen, and water for sanitation. Such
storage capacity or plans shall be sufficient for at least four (4)
continuous days of operation.