OAC 252:641-5-2
Installation
Cite as Okla. Admin. Code § 252:641-5-2
(a) Minimum fall. The following minimum fall requirements shall be met:
(1) Three-inch and four-inch pipe. Pipe having a diameter of three inches (3") or four
inches (4") that delivers sewage to a septic tank or a trash tank shall be installed with a
minimum fall of one-eighth inch (1/8") per foot.
(2) Six-inch pipe. Pipe having a diameter of six inches (6") that delivers sewage to a septic
tank or a trash tank shall be installed with a minimum fall of one-sixteenth inch (1/16") per
foot.
(b) Cleanouts. For all pipe located upstream of a septic tank, a two-way cleanout or two-way
cleanout assembly shall be installed:
(1) Within five feet (5') from where the plumbing stubs out of the building or appurtenance
to the building;
(2) Within five feet (5') after each of a change in direction of more than forty-five degrees
(45). Where more than one change of direction greater than forty-five degrees (45)
occurs within forty (40) feet of pipe, the cleanout for the first change of direction shall serve
as the cleanout for all changes in direction within that forty (40) feet of piping;
(3) For each one-hundred-foot interval of straight pipe.
Nothing in this paragraph shall require the installation of more than one (1) two-way cleanout
or two-way cleanout assembly per one-hundred-foot (100') section of straight pipe. For purposes
of this paragraph, straight pipe is pipe that does not have any change of direction of more than
forty-five degrees (45).
SUBCHAPTER 7. SEPTIC TANKS