OAR 918-261-0039
OAR 918-261-0039. Board Exemption for Products Located on the Load Side of a Listed Class 2 Transformer
(1) An exemption from product certification is granted under ORS 479.540 for installation of Class 2 products, other than wiring, located on the load side of a listed Class 2 transformer. The exemption applies only to products that are not:
(a) In a damp or wet location;
(b) Located in a plenum, duct or other air-handling space;
(c) Located in any area from chapter 5 of the adopted Oregon Electrical Specialty Code; or
(d) Part of a protective signaling system.
(2) An exemption from permitting is created for installation of Class 2 wiring located on the load side of a listed garage door controller. The exemption applies only to one- and two-family dwellings when the wiring is not part of the original wiring of the dwelling.