OAR 918-400-0525
OAR 918-400-0525. Plan Review Requirements
Plans and pertinent data submitted to the department under ORS 460.048 must include proof that the elevator equipment meets the Oregon Elevator Specialty Code by providing the following information:
(1) Electrical product certification by providing;
(a) The listing or certification number and identification of the approved laboratory that tested the equipment;
(b) When applicable, date and identification of the electrical special deputy who certified the equipment to the Oregon Elevator Specialty Code electrical requirement; or
(c) Proof that requests for listing or certification are pending.
(2) For the purpose of complying with plan submittal requirements of ORS 460.048, and when applicable to the type of equipment being proposed, a complete set of drawings must include:
(a) Elevation view;
(b) Plan view;
(c) Machine room layout (when applicable to the type of equipment);
(d) Cab and fixture detail;
(e) Hoistway entrance detail; and
(f) Electrical straight line wiring diagrams showing, as a minimum, safety circuits, normal and final limit circuits, and door lock circuits, which must include circuitry required by the Oregon Elevator Specialty Code.
[Publications: Publications referenced are available from the agency.]