Regl. 5293, art. 110-16-640 dup2
SOUND-RECORDING AND SIMILAR EQUIPMENT 70-669
Cite as Reglamento Núm. 5293, Art. 110-16-640 dup2
Exception No. 1: Special permission may be granted for the installation
of two 2-conductor lead-covered cables in ³/₄-inch conduit or tubing, provided the cross-sectional area of each cable does not exceed 11 square
inch (70.97 mm 2 ).
Exception No. 2: Special permission may be granted for the installation of two 2-conductor No. 19 lead-covered cables in ¹/₂-inch conduit
or tubing, provided the sum of the cross-sectional areas of the cables
does not exceed 32 percent of the internal cross-sectional area of the
conduit or tubing.
640-4. Wireways and Auxiliary Gutters. Wireways shall comply with the
requirements of Article 362, and auxiliary gutters shall comply with the
requirements of Article 374.
Exception: Where used for sound-recording and reproduction, the following shall be complied with:
a. Conductors in wireways or gutters shall not fill the raceway to
more than 75 percent of its depth.
b. Where the cover of auxiliary gutters is flush with the flooring and
is subject to the moving of heavy objects, it shall be of steel at least ¹/₄ inch
(6.35 mm) in thickness; where not subject to moving of heavy objects, as
in the rear of patch or other equipment panels, the cover shall be at least
No. 10 MSG.
c. Wireways shall be permitted in concealed places, provided they
are run in a straight line between outlets or junction boxes. Covers of
boxes shall be accessible. Edges of metal shall be rounded at outlet or
junction boxes and all rough projections smoothed to prevent abrasion of
insulation or conductors.
d. Wireways and auxiliary gutters shall be grounded and bonded in
accordance with the requirements of Article 250. Where the wireway or
auxiliary gutter does not contain power-supply wires, the equipment
grounding conductor shall not be required to be larger than No. 14 copper
or its equivalent. Where the wireway or auxiliary gutter contains powersupply wires, the equipment grounding conductor shall not be smaller than
specified in Section 250-95.
640-5. Conductors. Amplifier output circuits carrying audio-program signals of 70 volts or less and whose open-circuit voltage will not exceed 100
volts shall be permitted to employ Class 2 or Class 3 wiring as covered in