Regl. 5293, art. 110-21
The type of conduit material shall also be included in the
Cite as Reglamento Núm. 5293, Art. 110-21
marking.
Identification of conductors or cables used in the assembly shall be provided on a tag attached to each end of the assembly or to the side of a reel.
ARTICLE 345 - INTERMEDIATE METAL CONDUIT
A. General
345-1. Definition. Intermediate metal conduit is a metal raceway of circular cross section with integral or associated couplings, connectors, and fittings approved for the installation of electrical conductors.
345-2. Other Articles. Installations for intermediate metal conduit shall
comply with the provisions of the applicable sections of Article 300.
345-3. Uses Permitted.
(a) All Atmospheric Conditions and Occupancies. Use of intermediate
metal conduit shall be permitted under all atmospheric conditions and
occupancies. Where practicable, dissimilar metals in contact anywhere in
the system shall be avoided to eliminate the possibility of galvanic action.
conductor. Intermediate metal conduit shall be permitted as an equipment grounding
70-242
NATIONAL ELECTRICAL CODE
(FPN): See Section 250-91(b) for types of equipment grounding conductors.
Exception: Aluminum fittings and enclosures shall be permitted to be
used with steel intermediate metal conduit.
(b) Corrosion Protection. Intermediate metal conduit, elbows, couplings,
and fittings shall be permitted to be installed in concrete, in direct contact
with the earth, or in areas subject to severe corrosive influences where protected by corrosion protection and judged suitable for the condition.
(FPN): See Section 300-6 for protection against corrosion.
(c) Cinder Fill. Intermediate metal conduit shall be permitted to be
installed in or under cinder fill where subject to permanent moisture where
protected on all sides by a layer of noncinder concrete not less than
2 inches (50.8 mm) thick; where the conduit is not less than 18 inches
(457 mm) under the fill; or where protected by corrosion protection and
judged suitable for the condition.
(FPN): See Section 300-6 for protection against corrosion.
B. Installation
345-5. Wet Locations. All supports, bolts, straps, screws, etc., shall be
of corrosion-resistant materials or protected against corrosion by
corrosion-resistant materials.
(FPN): See Section 300-6 for protection against corrosion.
345-6. Size.
(a) Minimum. Conduit smaller than 1/2-inch electrical trade size shall not
be used.
(b) Maximum. Conduit larger than 4-inch electrical trade size shall not
be used.
345-7. Number of Conductors in Conduit. The number of conductors in
a single conduit shall not exceed that permitted by the percentage fill
specified in Table 1, Chapter 9, using the conduit dimensions of Table
4, Chapter 9.
345-8. Reaming and Threading. All cut ends of conduits shall be reamed
or otherwise finished to remove rough edges. Where conduit is threaded in
I the field, a standard cutting die with a 3/4-inch taper per foot (1 in 16) shall
be used.
(FPN): See Standards for Pipe Threads, General Purpose (Inch), ANSI/ASME
B.1.20.1-1983.
345-9. Couplings and Connectors.
(a) Threadless. Threadless couplings and connectors used with conduit
shall be made tight. Where buried in masonry or concrete, they shall be the
concrete-tight type. Where installed in wet locations, they shall be the
raintight type.
ARTICLE 345 - INTERMEDIATE METAL CONDUIT
70-243
(b) Running Threads. Running threads shall not be used on conduit for
connection at couplings.
345-10. Bends - How Made. Bends of intermediate metal conduit shall
be so made that the conduit will not be damaged and that the internal
diameter of the conduit will not be effectively reduced. The radius of the
curve of the inner edge of any field bend shall not be less than indicated in
Table 346-10.
Exception: For field bends for conductors without lead sheath and
made with a single operation (one shot) bending machine designed for the
purpose, the minimum radius shall not be less than that indicated in Table
346-10, Exception.
345-11. Bends - Number in One Run. There shall not be more than the
equivalent of four quarter bends (360 degrees total) between pull points,
e.g., conduit bodies and boxes.
345-12. Supports. Intermediate metal conduit shall be installed as a complete system as provided in Article 300 and shall be securely fastened in
place. Conduit shall be supported at least every 10 feet (3.05 m). In addition, conduit shall be securely fastened within 3 feet (914 mm) of each outlet box, junction box, device box, cabinet, conduit body, or other conduit
termination. Fastening shall be permitted to be increased to a distance of
5 feet (1.52 m) where structural members do not readily permit fastening
within 3 feet (914 mm).
(FPN): Support provided by a bored or punched hole in a framing member is
intended to meet the support requirements of this section.
Exception No. 1: If made up with threaded couplings, it shall be permissible to support straight runs of intermediate metal conduit in accordance
with Table 346-12, provided such supports prevent transmission of stresses
to termination where conduit is deflected between supports.
Exception No. 2: The distance between supports shall be permitted to
be increased to 20 feet (6.1 m) for exposed vertical risers from industrial
machinery, provided that the conduit is made up with threaded couplings,
is firmly supported at the top and bottom of the riser, and no other means
of intermediate support is readily available.
345-13. Boxes and Fittings. See Article 370.
345-14. Splices and Taps. Splices and taps shall be made only in junction boxes, outlet boxes, device boxes, or conduit bodies. See Article 370.
I
345-15. Bushings. Where a conduit enters a box, fitting, or other enclosure, a bushing shall be provided to protect the wire from abrasion unless
the design of the box, fitting, or enclosure is such as to afford equivalent
protection.
(FPN): See Section 373-6(c) for the protection of conductors Nos. 4 and larger
at bushings.
70-244
NATIONAL ELECTRICAL CODE
C. Construction Specifications
345-16. General. Intermediate metal conduit shall comply with (a)
through (c) below.
(a) Standard Lengths. Intermediate metal conduit as shipped shall be in
standard lengths of 10 feet (3.05 m), including coupling, one coupling to be
furnished with each length. For specific applications or use, it shall be permissible to ship lengths shorter or longer than 10 feet (3.05 m), with or
without couplings.
(b) Corrosion-Resistant Material. Nonferrous conduit of corrosionresistant material shall have suitable markings.
(c) Marking. Each length shall be clearly and durably identified at
2½2-foot (762-mm) intervals with the letters IMC. Each length shall be
marked as required in the first sentence of Section 110-21.