Regl. 5293, art. 110-21-346
RIGID METAL CONDUIT
Cite as Reglamento Núm. 5293, Art. 110-21-346
346-1. Use. The use of rigid metal conduit shall be permitted under all
atmospheric conditions and occupancies subject to the following:
(a) Protected by Enamel. Ferrous raceways and fittings protected from
corrosion solely by enamel shall be permitted only indoors and in occupancies not subject to severe corrosive influences.
(b) Dissimilar Metals. Where practicable, dissimilar metals in contact
anywhere in the system shall be avoided to eliminate the possibility of galvanic action.
Exception: Aluminum fittings and enclosures shall be permitted to be
used with steel rigid metal conduit, and steel fittings and enclosures shall
be permitted to be used with aluminum rigid metal conduit.
(c) Corrosion Protection. Ferrous or nonferrous metal conduit, elbows,
couplings, and fittings shall be permitted to be installed in concrete, in
direct contact with the earth, or in areas subject to severe corrosive influences where protected by corrosion protection and judged suitable for the
condition.
(FPN): See Section 300-6 for protection against corrosion.
346-2. Other Articles. Installations of rigid metal conduit shall comply
with the applicable provisions of Article 300.
A. Installation
346-3. Cinder Fill. Conduit shall not be used in or under cinder fill where
subject to permanent moisture.
Exception No. 1: Where of corrosion-resistant material suitable for the
purpose.
Exception No. 2: Where protected on all sides by a layer of noncinder
concrete at least 2 inches (50.8 mm) thick.
Exception No. 3: Where the conduit is at least 18 inches (457 mm) under
the fill.
ARTICLE 346 - RIGID METAL CONDUIT
70-245
346-4. Wet Locations. All supports, bolts, straps, screws, etc., shall be
of corrosion-resistant materials or protected against corrosion by
corrosion-resistant materials.
(FPN): See Section 300-6 for protection against corrosion.
346-5. Minimum Size. Conduit smaller than 1/2-inch electrical trade size
shall not be used.
Exception: For enclosing the leads of motors as permitted in Section
430-145(b).
346-6. Number of Conductors in Conduit. The number of conductors
permitted in a single conduit shall not exceed the percentage fill specified
in Table 1, Chapter 9.
(FPN): For conductor cross-sectional area, see Tables 5, 5A, 6, and 8 and the
applicable Notes to Tables at the beginning of Chapter 9.
346-7. Reaming and Threading.
(a) Reamed. All cut ends of conduits shall be reamed or otherwise finished to remove rough edges.
(b) Threaded. Where conduit is threaded in the field, a standard conduit
cutting die with a ³/₄-inch taper per foot (1 in 16) shall be used.
(FPN): See Standards for Pipe Threads, General Purpose (Inch), ANSI/ASME,
B.1.20.1-1983.
346-8. Bushings. Where a conduit enters a box, fitting, or other enclosure, a bushing shall be provided to protect the wire from abrasion unless
the box, fitting, or enclosure design provides equivalent protection.
(FPN): See Section 373-6(c) for the protection of conductors at bushings.
346-9. Couplings and Connectors.
(a) Threadless. Threadless couplings and connectors used with conduit
shall be made tight. Where buried in masonry or concrete, they shall be of
the concrete-tight type. Where installed in wet locations, they shall be of
the raintight type.
(b) Running Threads. Running threads shall not be used on conduit for
connection at couplings.
346-10. Bends - How Made. Bends of rigid metal conduit shall be so
made that the conduit will not be damaged, and that the internal diameter of
the conduit will not be effectively reduced. The radius of the curve of the
inner edge of any field bend shall not be less than shown in Table 346-10.
Exception: For field bends for conductors without lead sheath and
made with a single operation (one shot) bending machine designed for
the purpose, the minimum radius shall not be less than indicated in
Table 346-10, Exception.
346-11. Bends - Number in One Run. There shall not be more than the
equivalent of four quarter bends (360 degrees total) between pull points,
e.g., conduit bodies and boxes.
70-246
NATIONAL ELECTRICAL CODE
Table 346-10. Radius of Conduit Bends (Inches)
Conductors
Conductors
Size of
without
with
Conduit (In.)
Lead Sheath (In.)
Lead Sheath (In.)
½
4
6
3/4
5
8
1
6
11
1½
8
14
1½
10
16
2
12
21
2½
15
25
3
18
31
3½
21
36
4
24
40
5
30
50
6
36
61
For SI units: (Radius) one inch = 25.4 millimeters.
Table 346-10, Exception.
Radius of Conduit Bends (Inches)
Size of
Radius to
Conduit (In.)
Center of Conduit (In.)
½
4
3/4
4½
1
53/4
1½
7½
1½
8½
2
9½
2½
101/2
3
13
3½
15
4
16
5
24
6
30
For SI units: (Radius) one inch = 25.4 millimeters.
346-12. Supports. Rigid metal conduit shall be installed as a complete
system as provided in Article 300 and shall be securely fastened in place.
Conduit shall be supported at least every 10 feet (3.05 m). In addition, conduit shall be securely fastened within 3 feet (914 mm) of each outlet box,
junction box, device box, cabinet, conduit body, or other conduit termination. Fastening shall be permitted to be increased to a distance of 5 feet
(1.52 m) where structural members do not readily permit fastening within
3 feet (914 mm).
(FPN): Support provided by a bored or punched hole in a framing member is
intended to meet the support requirements of this section.
ARTICLE 346 - RIGID METAL CONDUIT
70-247
Exception No. 1: If made up with threaded couplings, it shall be permissible to support straight runs of rigid metal conduit in accordance with
Table 346-12, provided such supports prevent transmission of stresses to
termination where conduit is deflected between supports.
Exception No. 2: The distance between supports shall be permitted to
be increased to 20 feet (6.1 m) for exposed vertical risers from industrial
machinery, provided that the conduit is made up with threaded couplings,
is firmly supported at the top and bottom of the riser, and no other means
of intermediate support is readily available.
Table 346-12. Supports for Rigid Metal Conduit
Maximum Distance
Between Rigid Metal
Conduit Size
Conduit Supports
(Inches)
(Feet)
1/2-3/4
10
1
12
11/4-11/2
14
2-2½₂
16
3 and larger
20
For SI units: (Supports) one foot = 0.3048 meter.
346-13. Boxes and Fittings. Boxes and fittings shall comply with the
applicable provisions of Article 370.
346-14. Splices and Taps. Splices and taps shall be made only in junction
boxes, outlet boxes, device boxes, or conduit bodies. See Article 370.
B. Construction Specifications
346-15. General. Rigid metal conduit shall comply with (a) through (c)
below.
(a) Standard Lengths. Rigid metal conduit as shipped shall be in standard lengths of 10 feet (3.05 m), including coupling, one coupling to be furnished with each length. Each length shall be reamed and threaded on each
end. For specific applications or uses, it shall be permissible to ship standard lengths or lengths shorter or longer than 10 feet (3.05 m) with or without couplings and with or without threads.
(b) Corrosion-Resistant Material. Nonferrous conduit of corrosionresistant material shall have suitable markings.
(c) Durably Identified. Each length shall be clearly and durably identified in every 10 feet (3.05 m) as required in the first sentence of Section 110-21.
70-248
NATIONAL ELECTRICAL CODE