Regl. 5293, art. 110-21-347
RIGID NONMETALLIC CONDUIT
Cite as Reglamento Núm. 5293, Art. 110-21-347
347-1. Description. This article shall apply to a type of conduit and fittings of suitable nonmetallic material that is resistant to moisture and
chemical atmospheres. For use aboveground, it shall also be flameretardant, resistant to impact and crushing, resistant to distortion from heat
under conditions likely to be encountered in service, and resistant to low
temperature and sunlight effects. For use underground, the material shall be
acceptably resistant to moisture and corrosive agents and shall be of sufficient strength to withstand abuse, such as by impact and crushing, in handling and during installation. Conduits listed for the purpose shall be permitted to be installed underground in continuous lengths from a reel. Where
intended for direct burial, without encasement in concrete, the material shall
also be capable of withstanding continued loading that is likely to be encountered after installation.
347-2. Uses Permitted. The use of listed rigid nonmetallic conduit and
fittings shall be permitted under the following conditions:
(FPN): Extreme cold may cause some nonmetallic conduits to become brittle
and therefore more suceptible to damage from physical contact.
(a) Concealed. In walls, floors, and ceilings.
(b) Corrosive Influences. In locations subject to severe corrosive influences as covered in Section 300-6 and where subject to chemicals for
which the materials are specifically approved.
(c) Cinders. In cinder fill.
(d) Wet Locations. In portions of dairies, laundries, canneries, or other
wet locations and in locations where walls are frequently washed, the
entire conduit system including boxes and fittings used therewith shall be
so installed and equipped as to prevent water from entering the conduit.
All supports, bolts, straps, screws, etc., shall be of corrosion-resistant
materials or be protected against corrosion by approved corrosion-resistant
materials.
(e) Dry and Damp Locations. In dry and damp locations not prohibited
by Section 347-3.
(f) Exposed. For exposed work where not subject to physical damage if
identified for such use.
(g) Underground Installations. For underground installations, see Sections 300-5 and 710-4(b).
347-3. Uses Not Permitted. Rigid nonmetallic conduit shall not be used:
(a) Hazardous (Classified) Locations. In hazardous (classified) locations, except as covered in Sections 503-3(a), 504-20, 514-8, and 515-5; and
in Class I, Division 2 locations as permitted in the exception to Section
501-4(b).
(b) Support of Fixtures. For the support of fixtures or other equipment.
Exception: Rigid nonmetallic conduit shall be permitted to support nonmetallic conduit bodies no larger than the largest trade size of an entering
raceway. The conduit bodies shall not contain devices or support fixtures.