Regl. 5293, art. 110-21-349
FLEXIBLE METALLIC TUBING
Cite as Reglamento Núm. 5293, Art. 110-21-349
A. General
349-1. Scope. The provisions of this article apply to a raceway for electric conductors that is circular in cross section, flexible, metallic, and liquidtight without a nonmetallic jacket.
349-2. Other Articles. Installations of flexible metallic tubing shall comply with the provisions of the applicable sections of Article 300 and Section 110-21.
349-3. Uses Permitted. Flexible metallic tubing shall be permitted to be
used (1) in dry locations; (2) in accessible locations where protected from
physical damage or concealed, such as above suspended ceilings; (3) for
1000 volts maximum; and (4) in branch circuits.
349-4. Uses Not Permitted. Flexible metallic tubing shall not be used (1)
in hoistways; (2) in storage battery rooms; (3) in hazardous (classified)
locations unless otherwise permitted under other articles in this Code; (4)
underground for direct earth burial, or embedded in poured concrete or
aggregate; (5) where subject to physical damage; and (6) in lengths over
6 feet (1.83 m).
B. Construction and Installation
349-10. Size.
(a) Minimum. Flexible metallic tubing smaller than 1/2-inch electrical
trade size shall not be used.
Exception No. 1: ³/₈-inch trade size shall be permitted to be installed in
accordance with Sections 300-22(b) and (c).
Exception No. 2: ³/₈-inch trade size shall be permitted in lengths not in
excess of 6 feet (1.83 m) as part of an approved assembly or for lighting
fixtures. See Section 410-67(c).
(b) Maximum. The maximum size of flexible metallic tubing shall be the
³/₄-inch trade size.
349-12. Number of Conductors.
(a) 1/2-Inch and 3/4-Inch Flexible Metallic Tubing. The number of conductors permitted in 1/2-inch and ³/₄-inch trade sizes of flexible metallic tubing shall not exceed the percentage of fill specified in Table 1, Chapter 9.
(b) 3/8-Inch Flexible Metallic Tubing. The number of conductors permitted in ³/₈-inch trade size flexible metallic tubing shall not exceed that permitted in Table 350-3.
(FPN): For conductor cross-sectional area, see Tables 5, 5A, 6, and 8 and the
applicable Notes to Tables at the beginning of Chapter 9.
70-254
NATIONAL ELECTRICAL CODE
349-16. Grounding. See Section 250-91(b), Exception No. 1.
349-17. Splices and Taps. Splices and taps shall be made only in junction boxes, outlet boxes, device boxes, or conduit bodies. See Article 370.
349-18. Fittings. Flexible metallic tubing shall be used only with
approved terminal fittings. Fittings shall effectively close any openings in
the connection.
(FPN): See Sections 300-22(b) and (c) for use in ducts, plenums, and other
spaces used for environmental air.
349-20. Bends.
(a) Infrequent Flexing Use. Where the flexible metallic tubing shall be
infrequently flexed in service after installation, the radii of bends measured
to the inside of the bend shall not be less than specified in Table 349-20(a).
Table 349-20(a). Minimum Radii for Flexing Use
Trade
Size
Minimum Radii
3/8 inch
10 inches
½ inch
12½ inches
3/4 inch
17½ inches
For SI units: (Radii) one inch = 25.4 millimeters.
(b) Fixed Bends. Where the flexible metallic tubing is bent for installation purposes and is not flexed or bent as required by use after installation,
the radii of bends measured to the inside of the bend shall not be less than
specified in Table 349-20(b).
Table 349-20(b). Minimum Radii for Fixed Bends
Trade
Size
Minimum Radii
3/8 inch
3½ inches
½ inch
4 inches
3/4 inch
5 inches
For SI units: (Radii) one inch = 25.4 millimeters.