Regl. 5293, art. 110-34-110 dup3
REQUIREMENTS FOR ELECTRICAL INSTALLATIONS 70-29
Cite as Reglamento Núm. 5293, Art. 110-34-110 dup3
Table 110-34(e).
Elevation of Unguarded Live Parts above Working Space
Nominal Voltage
Between Phases
Elevation
1001-7500
8'6"
7501-35000
9'
Over 35kV
9' + 0.37" per kV above 35
For SI units: one inch = 25.4 millimeters; one foot = 0.3048 meter.
70-31
Chapter 2. Wiring and Protection