Regl. 5293, art. 110-34(e)-725
REMOTE-CONTROL, SIGNALING CIRCUITS
Cite as Reglamento Núm. 5293, Art. 110-34(e)-725
70-753
720-4, Conductors. Conductors shall not be smaller than No. 12 copper
or equivalent. Conductors for appliance branch circuits supplying more
than one appliance or appliance receptacle shall not be smaller than No. 10
copper or equivalent.
720-5. Lampholders. Standard lampholders having a rating of not less
than 660 watts shall be used.
720-6. Receptacle Rating. Receptacles shall have a rating of not less than
15 amperes.
720-7. Receptacles Required. Receptacles of not less than 20-ampere
rating shall be provided in kitchens, laundries, and other locations where
portable appliances are likely to be used.
720-8. Overcurrent Protection. Overcurrent protection shall comply with