Regl. 5293, art. 2
2,
Cite as Reglamento Núm. 5293, Art. 2
Facilities, NFPA 99-1990
Hazardous
Area in
Flammable
Anesthetizing
Location
A-517-61(a)(1)
Standard for Health Care
Paragraph
Facilities, NFPA 99-1990
12-4.1.3.2
A-517-61(a)(3)
Standard for Health Care
Paragraphs
Facilities, NFPA 99-1990
3-4.1.2.1(e)(2)
7-5.1.2.4,
7-5.1.2.5
A-517-64
Standard for Health Care
Paragraph
Facilities, NFPA 99-1990
7-5.1.2.3
A-517-160(a)(2)
Standard for Health Care
Paragraph
Facilities, NFPA 99-1990
3-4.3.1.2
A-517-160(b)
Standard for Health Care
Paragraph
Facilities, NFPA 99-1990
3-4.3.3
70-855
Appendix B
This appendix is not part of the requirements of this Code, but is
included for information purposes only.
B-310-15(b)(1). Formula Application Information. This appendix provides application information for ampacities calculated under engineering
supervision.
B-310-15(b)(2). Typical Applications Covered by Tables. Typical ampacities for conductors rated 0 through 2000 volts are shown in Tables B-310-1
through B-310-10. Underground electrical duct bank configurations, as
detailed in Figures B-310-3, B-310-4, and B-310-5, are utilized for conductors rated 0 through 5000 volts. In Figures B-310-2 through B-310-5, where
adjacent duct banks are used, a separation of 5 feet (1.52 m) between the
centerlines of the closest ducts in each bank or 4 feet (1.22 m) between the
extremities of the concrete envelopes is sufficient to prevent derating of the
conductors due to mutual heating. These ampacities were calculated as
detailed in the basic ampacity paper, "The Calculation of the Temperature
Rise and Load Capability of Cable Systems," by J. H. Neher and M. H.
McGrath, AIEE Paper 57-660. For additional information concerning the
application of these ampacities, see Power Cable Ampacities, IEEE/ICEA
Standard S-135/P-46-426.
Typical values of thermal resistivity (Rho) are as follows:
Polyethylene (PE) = 450
Concrete = 55
Polyvinyl Chloride PVC = 650
Very Dry Soil (rocky or sandy) = 120
Rubber and Rubber-like = 500
Damp Soil
Paper Insulation = 550
(coastal areas, high water table) = 60
Average Soil (90 percent of USA) = 90
Thermal resistivity, as used in this appendix, refers to the heat transfer
capability through a substance by conduction. It is the reciprocal of thermal conductivity and is normally expressed in the units °C-cm/watt. For
additional information on determining soil thermal resistivity (Rho), see
IEEE Guide for Soil Thermal Resistivity Measurements, ANSI/IEEE
Standard 442-1981.
B-310-15(b)(3). Criteria Modifications.
Where values of load factor and Rho are known for a particular electrical
duct bank installation and they are different from those shown in a specific
table or figure, the ampacities shown in the table or figure can be modified by
the application of factors derived from the use of Figure B-310-1.
Where two different ampacities apply to adjacent portions of a circuit,
the higher ampacity can be used beyond the point of transition, a distance
equal to 10 feet (3.05 m) or 10 percent of the circuit length figured at the
higher ampacity, whichever is less.
Where the burial depth of direct burial or electrical duct bank circuits are
modified from the values shown in a figure or table, ampacities can be modified as shown in (1) and (2), which follow.
(1) Where burial depths are increased in part(s) of an electrical duct run
to avoid underground obstructions, no decrease in ampacity of the conduc-
70-856
NATIONAL ELECTRICAL CODE
tors is needed, provided the total length of parts of the duct run increased
in depth to avoid obstructions is less than 25 percent of the total run length.
(2) Where burial depths are deeper than shown in a specific underground ampacity table or figure, an ampacity derating factor of 6 percent
per increased foot (305 mm) of depth for all values of Rho can be utilized.
No rating change is needed where the burial depth is decreased.
B-310-15(b)(4). Electrical Ducts. The term electrical duct(s) is defined in