Regl. 5293, art. 200-6
Resolución 2535: adopta el Código Eléctrico Nacional, versión 1993. (Sustituye el Anejo A del Reglamento 4435)
Cite as Reglamento Núm. 5293, Art. 200-6
(b) Equipment Grounding Conductors. Bare, covered, or insulated
grounding conductors shall be permitted. Individually covered or insulated
grounding conductors shall have a continuous outer finish that is either
green, or green with one or more yellow stripes.
ARTICLE 310 - CONDUCTORS FOR GENERAL WIRING
70-165
Exception No. 1: An insulated or covered conductor larger than No. 6
shall, at the time of installation, be permitted to be permanently identified
as a grounding conductor at each end and at every point where the conductor is accessible. Identification shall be accomplished by one of the following means:
a. Stripping the insulation or covering from the entire exposed length;
b. Coloring the exposed insulation or covering green; or
c. Marking the exposed insulation or covering with green colored
tape or green colored adhesive labels.
Exception No. 2: Where the conditions of maintenance and supervision
assure that only qualified persons will service the installation, an insulated
conductor in a multiconductor cable shall, at the time of installation, be
permitted to be permanently identified as a grounding conductor at each
end and at every point where the conductor is accessible by one of the following means:
a. Stripping the insulation from the entire exposed length;
b. Coloring the exposed insulation green; or
c. Marking the exposed insulation with green colored tape or green
colored adhesive labels.
(c) Ungrounded Conductors. Conductors that are intended for use as
ungrounded conductors, whether used as single conductors or in multiconductor cables, shall be finished to be clearly distinguishable from grounded
and grounding conductors. Ungrounded conductors shall be distinguished
by colors other than white, natural gray, or green; or by a combination of
color plus distinguishing marking. Distinguishing markings shall also be in
a color other than white, natural gray, or green, and shall consist of a stripe
or stripes or a regularly spaced series of identical marks. Distinguishing
markings shall not conflict in any manner with the surface markings
required by Section 310-11(b)(1).
Exception: As permitted by Section 200-7.
310-13. Conductor Constructions and Applications. Insulated conductors shall comply with the applicable provisions of one or more of the following: Tables 310-13, 310-61, 310-62, 310-63, and 310-64.
These conductors shall be permitted for use in any of the wiring methods recognized in Chapter 3 and as specified in their respective tables.
(FPN): Thermoplastic insulation may stiffen at temperatures colder than minus
10°C (plus 14°F), requiring that care be exercised during installation at such temperatures. Thermoplastic insulation may also be deformed at normal temperatures
where subjected to pressure, requiring care be exercised during installation and at
points of support. Thermoplastic insulation, where used on dc circuits in wet locations, may result in electroendosmosis between conductor and insulation.
310-14. Aluminum Conductor Material. Solid aluminum conductors No.
8, 10, and 12 shall be made of an AA-8000 series electrical grade aluminum
alloy conductor material. Stranded aluminum conductors No. 8 through
1000 kcmil marked as Type XHHW, THW, THHW, THWN, THHN,
service-entrance Type SE Style U and SE Style R shall be made of an
AA-8000 series electrical grade aluminum alloy conductor material.
Table 310-13. Conductor Application and Insulations
Max.
AWG
Thickness
70-166
Trade
Type
Operating
Application
or
of
Outer
Name
Letter
Temp.
Provisions
Insulation
kcmil
Insulation
Mils
Covering****
Fluorinated
FEP
90° C
Dry and damp locations.
Fluorinated
Ethylene
or
194° F
Ethylene
14-10
20
None
Propylene
FEPB
200° C
Dry locations-special applica-
Propylene
8-2
30
392° F
tions.
Fluorinated
14-8
14
Glass braid
Ethylene
Asbestos or
Propylene
6-2
14
other suitable braid
materal
18-16*****
23
Mineral Insulation
MI
90° F
Dry and wet locations.
Magnesium
16-10
36
(Metal Sheathed)
194° F
Oxide
9-4
50
Copper or
250° C
For special application.
3-500
55
Alloy Steel
482° F
Moisture-, Heat-,
60° C
Machine tool wiring in wet lo-
Flame-
(A) (B)
NATIONAL ELECTRICAL CODE
and Oil-Resistant
140° F
cations as permitted in NFPA
Retardant,
22-12
30 15
(A) None
Thermoplastic
MTW++
79. (See Article 670).
Moisture-,
10
30 20
Machine tool wiring in dry lo-
Heat-, and
8
45 30
(B) Nylon
90° C
cations as permitted in NFPA
Oil-Re-
6
60 30
jacket
194° F
79. (See Article 670.)
sistant
4-2
60 40
or
Thermo-
1-4/0
80 50
equivaplastic
213-500
95 60
lent
501-1000
110 70
Paper
85° C
For underground service con-
185° F
ductors, or by special permis-
Paper
Lead sheath
sion.
****Some insulations do not require an outer covering.
I
*****For signaling circuits permitting 300-volt insulation.
+Where environmental conditions require maximum conductor operating temperatures above 90°C.
Insulation and outer coverings that meet the requirements of flame-retardant, limited-smoke and are so listed shall be permitted to be designated
limited-smoke with the suffix /LS after the Code type designation.
Table 310-13. (Continued)
Perfluoro-
PFA
90° C
Dry and damp locations.
Perfluoro-
14-10
20
alkoxy
194° F
alkoxy
8-2
30
None
200° C
Dry locations-special applica-
1-4/0
45
392° F
tions.+
Perfluoro-
PFAH
250° C
Dry locations only. Only for
Perfluoro-
14-10
20
alkoxy
482° F
leads within apparatus or
alkoxy
8-2
30
within raceways connected to
1-4/0
45
None
apparatus. (Nickel or nickelcoated copper only.)
Heat-Resistant
RH
75° C
Dry and damp locations.
14-12**
30
Moistureor Cross-
167° F
10
45
resistant,
Linked Syn-
8-2
60
flamethetic Polymer
1-4/0
80
retardant,
213-500
95
non-
Heat-Resistant
RHH++
90° C
Dry and damp locations.
Heat-
501-1000
110
metallic
or Cross-
194° F
Resistant
1001-2000
125
covering*
Linked Synor Cross-
For 601-2000 volts,
thetic Polymer
Linked
see Table 310-62.
Synthetic
Polymer
Moisture- and
RHW+,
75° C
Dry and wet locations.
Moisture-
14-10
45
Moisture-
Heat-Resistant
+++
167° F
Where over 2000 volts insulaand Heat-
8-2
60
resistant,
or Crosston, shall be ozone-resistant
Resistant
1-4/0
80
flame-
Linked Synor Cross-
213-500
95
retardant,
ARTICLE 310 CONDUCTORS FOR GENERAL WIRING
thetic Polymer
Linked
501-1000
110
non-
Synthetic
1001-2000
125
metallic
Polymer
For 601-2000 volts,
covering*
see Table 310-62.
*Some rubber insulations do not require an outer covering.
**For size Nos. 14-12, RHH shall be 45 mils thickness insulation.
Where environmental conditions require maximum conductor operating temperatures above 90°C.
++Insulation and outer coverings that meet the requirements of flame-retardant, limited-smoke and are so listed shall be permitted to be designated
limited-smoke with the suffix /LS after the Code type designation.
ittListed wire types designated with the suffix "-2," such as RHW-2, shall be permitted to be used at a continuous 90°C-operating temperature,
70-167
I wet or dry.
Table 310-13. (Continued)
Max.
AWG
Thickness
70-168
Trade
Type
Operating
Application
or
of
Outer
Name
Letter
Temp.
Provisions
Insulation
kcmil
Insulation
Mils
Covering****
14-10
45
Moisture-
Moisture-
8-2
60
Moisture- and
resistant,
and Heat-
1-4/0
80
flame-
Heat-Resistant
90° C
Resistant or
213-500
95
or Cross-
RHW-2
retardant,
194° F
Dry and wet locations.
Cross-Linked
501-1000
110
nonmetallic
Linked Syn-
Synthetic
1001-2000
125
thetic Polymer
covering*
Polymer
For 601-2000 volts,
see Table 310-62.
Silicone-
SA
90° C
Dry and damp locations.
14-10
45
Asbestos,
Asbestos
194° F
8-2
60
glass, or
1-4/0
80
other
125° C
For special application.
Silicone Rubber
213-500
95
suitable
257° F.
501-1000
110
braid
1001-2000
125
material
Synthetic
SISTT
90° C
Switchboard wiring only.
Heat-Resistant
14-10
30
Heat-Resistant
194° F
Cross-Linked
8
45
NATIONAL ELECTRICAL CODE
None
Synthetic
6-2
60
Polymer
1-4/0
80
Thermoplastic
TA
90° C
Switchboard wiring only.
Thermoplastic
Th'pl'. Asb.
Flameand Asbestos
194° F
and Asbestos
14-8
20
20
retardant,
6-2
30
25
nonmetallic
1-4/0
40
30
covering
Thermoplastic
TBS
90° C
Switchboard wiring only.
Thermoplastic
14-10
30
Flameand Fibrous
194° F
8
45
retardant,
Outer Braid
6-2
60
nonmetallic
1-4/0
80
covering
*Some rubber insulations do not require an outer covering.
****Some insulations do not require an outer covering.
+Where environmental conditions require maximum conductor operating temperatures above 90°C.
++Insulation and outer coverings that meet the requirements of flame-retardant, limited-smoke and are so listed shall be permitted to be designated
limited-smoke with the suffix /LS after the Code type designation.
Table 310-13. (Continued)
Extended
TFE
250° C
Dry locations only. Only for
Extruded
14-10
20
Polytetra-
482° F
leads within apparatus or
Polytetra-
8-2
30
fluoroethylene
within raceways connected
fluoro-
1-4/0
45
None
to apparatus, or as open
ethylene
wiring. (Nickel or nickelcoated copper only.)
Heat-Resistant
THHN++
90° C
Dry and damp locations.
Flame-
14-12
15
Nylon
Thermoplastic
194° F
Retardant,
10
20
jacket or
Heat-
8-6
30
equivalent
Resistant
4-2
40
Thermo-
1-4/0
50
plastic
250-500
60
501-1000
70
Moisture- and
THHW
75° C
Wet location.
Flame-
14-10
45
Heat-Resistant
167° F
Retardant,
8-2
60
Thermoplastic
90° C
Dry location.
Moisture-
1-4/0
80
194° F
and Heat-
213-500
95
None
Resistant
501-1000
110
Thermoplastic
Moisture- and
THW
75° C
Dry and wet locations.
Flame-
14-10
45
ARTICLE 310 CONDUCTORS FOR GENERAL WIRING
Heat-Resistant
+++
167° F
Retardant,
8-2
60
Thermoplastic
90° C
Special applications within
Moisture-
1-4/0
80
194° F
electric discharge lighting
and Heat-
213-500
95
None
equipment. Limited to 1000
Resistant
501-1000
110
open-circuit volts or less.
Thermo-
1001-2000
125
(Size 14-8 only as permitted
plastic
in Section 410-31.)
+Insulation and outer coverings that meet the requirements of flame-retardant, limited-smoke and are so listed shall be permitted to be designated
limited-smoke with the suffix /LS after the Code type designation.
+++Listed wire types designated with the suffix "-2," such as RHW-2 shall be permitted to be used at a continuous 90°C-operating temperature,
70-169
I
wet or dry.
Table 310-13. (Continued)
Max.
AWG
Thickness
Trade
Type
Operating
Application
or
of
Outer
Name
Letter
Temp.
Provisions
Insulation
kcmil
Insulation
Mils
70-170
Covering****
Flame-
14-12
15
Retardant,
10
20
Moisture- and
Moisture-
THWN
75° C
8-6
30
Nylon
Heat-Resistant
TT, +++
167° F
Dry and wet locations.
and Heat-
4-2
40
jacket
Thermoplastic
Resistant
1-4/0
50
or equivalent
Thermo-
250-500
60
plastic
501-1000
70
Flame-
14-10
30
Retardant,
8
45
Moisture-
60° C
Moisture-
6-2
60
Resistant
TWTT
Dry and wet locations.
Resistant
140° F
1-4/0
80
None
Thermoplastic
Thermo-
213-500
95
plastic
501-1000
110
1001-2000
125
Underground
Feeder and
60° C
Moisture-
Branch-Circuit
140° F
Resistant
NATIONAL ELECTRICAL CODE
Cable-Single
Conductor.
14-10
60*
Integral
UF
See Article 339.
8-2
(For Type UF
80*
with
1-4/0
95*
cable employing
75° C
insulation
Moisturemore than one
167° F**
and Heatconductor, see
Resistant
Article 339.)
*Includes integral jacket.
**For ampacity limitation, see Section 339-5.
Some insulations do not require an outer covering.
++Insulation and outer coverings that meet the requirements of flame-retardant, limited-smoke and are so listed shall be permitted to be designated
limited-smoke with the suffix /LS after the Code type designation.
IttListed wire types designated with the suffix "-2," such as RHW-2 shall be permitted to be used at a continuous 90°C-operating temperature, wet
or dry.
Table 310-13. (Continued)
Underground
Service-
Moisture-
Entrance
12-10
45
resistant
Cable-Single
8-2
60
Heat- and
non-
Conductor.
75° C
1-4/0
80
USETTI
See Article 338.
Moisturemetallic
(For Type USE
167° F
213-500
95***
Resistant
cable employing
501-1000
110
covering
more than one
125
[See Section
1001-2000
338-1(b).]
conductor, see
Article 338.)
Heat-Resistant
XHH ++
90° C
Dry and damp locations.
Flame-
14-10
30
None
Cross-Linked
194° F
Retardant
8-2
45
Synthetic
Cross-
1-4/0
55
Polymer
Linked
213-500
65
Synthetic
501-1000
80
Polymer
1001-2000
95
Moisture- and
90° C
Dry and damp locations.
Flame-
14-10
30
Heat-Resistant
194° F
Retardant
8-2
45
Cross-Linked
XHHW
Cross-
1-4/0
55
None
Synthetic
TT, +++
75° C
Wet locations.
Linked
213-500
65
Polymer
167° F
Synthetic
501-1000
80
ARTICLE 310 - CONDUCTORS FOR GENERAL WIRING
Polymer
1001-2000
95
***Insulation thickness shall be permitted to be 80 mils for listed Type USE conductors that have been subjected to special investigations.
The nonmetallic covering over individual rubber-covered conductors of aluminum-sheathed cable and of lead-sheathed or multiconductor cable shall
not be required to be flame-retardant. For Type MC cable, see Section 334-20. For nonmetallic-sheathed cable, see Section 336-25. For Type UF
cable, see Section 339-1.
++Insulation and outer coverings that meet the requirements of flame-retardant, limited-smoke and are so listed shall be permitted to be designated
limited-smoke with the suffix /LS after the Code type designation.
+++Listed wire types designated with the suffix "-2," such as RHW-2, shall be permitted to be used at a continuous 90°C-operating temperature,
wet or dry.
70-171
70-172
Table 310-13. (Continued)
Max.
AWG
Thickness
Trade
Type
Operating
Application
or
of
Outer
Name
Letter
Temp.
Provisions
Insulation
kcmil
Insulation
Mils
Covering***
Moisture- and
90° C
Dry and wet locations.
Flame-
14-10
30
Heat-Resistant
194° F
Retardant
8-2
45
Cross-Linked
XHHW-2
Cross-Linked
1-4/0
55
Synthetic
213-500
None
Synthetic
65
Polymer
Polymer
501-1000
80
1001-2000
95
Modified
Z
90° C
Dry and damp locations.
Modified
14-12
15
Ethylene
194° F
Ethylene
10
20
Tetrafluoro-
150° C
Dry locations-special appli-
Tetrafluoro-
8-4
25
None
ethylene
302° F
cations.
ethylene
3-1
35
1/0-4/0
45
Modified
ZWITT
75° C
Wet locations.
Modified
14-10
30
NATIONAL ELECTRICAL CODE
Ethylene
167° F
Ethylene
8-2
45
Tetrafluoro-
90° C
Dry and damp locations.
Tetrafluoroethylene
194° F
None
ethylene
150° C
Dry locations-special appli-
302° F
cations.
****Some insulations do not require an outer covering.
Where environmental conditions require maximum conductor operating temperatures above 90°C.
+++Listed wire types designated with the suffix "-2," such as RHW-2 , shall be permitted to be used at a continuous 90°C-operating temperature, wet
I or dry.
ARTICLE 310 - CONDUCTORS FOR GENERAL WIRING
70-173
310-15. Ampacities. Ampacities for conductors shall be permitted to be
determined by (a) or (b) below.
(FPN): Ampacities provided by this section do not take voltage drop into consideration. Conductors of circuits as defined in Article 100, sized to prevent a voltage drop exceeding 5 percent, will provide reasonable efficiency of operation.
(a) General. Ampacities for conductors rated 0 to 2000 volts shall be as
specified in the Allowable Ampacity Tables 310-16 through 310-19 and their
accompanying notes. Ampacities for solid dielectric insulated conductors
rated 2001 through 35,000 volts shall be as specified in Tables 310-67
through 310-84 and their accompanying notes.
(FPN): Tables 310-16 through 310-19 are application tables that are for use in
determining conductor sizes on loads calculated in accordance with Article 220.
Allowable ampacities result from consideration of one or more of the following:
1. Temperature compatibility with connected equipment, especially at
the connection points.
2. Coordination with circuit and system overcurrent protection.
3. Compliance with the requirements of product listings or certifications. See Section 110-3(b).
4. Preservation of the safety benefits of established industry practices
and standardized procedures.
(b) Engineering Supervision. Under engineering supervision, conductor ampacities shall be permitted to be calculated by means of the following general formula:
I = TC - (TA + DELTA TD)
RDC (1 + YC)RCA
Where:
TC = Conductor temperature in degrees C.
TA = Ambient temperature in degrees C.
DELTA TD = Dielectric loss temperature rise.
RDC = DC resistance of conductor at temperature TC.
YC = Component ac resistance resulting from skin effect and proximity
effect.
RCA = Effective thermal resistance between conductor and surrounding ambient.
(FPN): See Appendix B for examples of formula applications.
(c) Selection of Ampacity. Where more than one calculated or tabulated
ampacity could apply for a given circuit length, the lowest value shall be
used.
Exception: Where two different ampacities apply to adjacent portions. of
a circuit, the higher ampacity shall be permitted to be used beyond the
point of transition, a distance equal to 10 feet (3.05 m) or 10 percent of the
circuit length figured at the higher ampacity, whichever is less.
(FPN): See Section 110-14(c) for conductor temperature limitations due to termination provisions.
(d) Electrical Ducts. Electrical ducts as used in Article 310 shall include
any of the electrical conduits recognized in Chapter 3 as suitable for use
underground; and other raceways round in cross section, listed for underground use; embedded in earth or concrete.
70-174
NATIONAL ELECTRICAL CODE
Table 310-16. Allowable Ampacities of Insulated Conductors
Rated 0-2000 Volts, 60° to 90°C (140° to 194°F)
Not More Than Three Conductors in Raceway or Cable or Earth
(Directly Buried), Based on Ambient Temperature of 30°C (86°F)
Size
Temperature Rating of Conductor. See Table 310-13.
Size
60°C
75°C
90°C
60°C
75°C
90°C
(140°F)
(167°F)
(194°F)
(140°F)
(167°F)
(194°F)
TYPES
TYPES
TYPES
TYPES
TYPES
TYPES
TWT,
FEPWt,
TA, TBS, SA
TWT,
RHt, RHWt,
TA, TBS,
UFt
RHt, RHWt,
SIS, FEPT,
UFt
THHWT,
SA, SIS,
THHWT,
FEPBT, MI
THWT,
THHNt,
AWG
THWT,
RHHT, RHW-2,
THWNT,
THHW+,
AWG
kcmil
THWNT,
THHNT, THHW+,
XHHWT,
THW-2, THWN-2,
kcmil
XHHW+
THW-2, THWN-2,
USET
RHHt, RHW-2
USEt, ZWT
USE-2, XHH,
USE-2
XHHWt
XHH, XHHW
XHHW-2, ZW-2
XHHW-2, ZW-2
COPPER
ALUMINUM OR COPPER-CLAD ALUMINUM
18
14
16
18
14
20t
20+
25+
12
25f
25+
30+
20t
20+
25t
12
10
30
35t
40+
25
30f
35t
10
8
40
50
55
30
40
45
8
6
55
65
75
40
50
60
6
4
70
85
95
55
65
75
4
3
85
100
110
65
75
85
3
2
95
115
130
75
90
100
2
1
110
130
150
85
100
115
1
1/0
125
150
170
100
120
135
1/0
2/0
145
175
195
115
135
150
2/0
3/0
165
200
225
130
155
175
3/0
4/0
195
230
260
150
180
205
4/0
250
215
255
290
170
205
230
250
300
240
285
320
190
230
255
300
350
260
310
350
210
250
280
350
400
280
335
380
225
270
305
400
500
320
380
430
260
310
350
500
600
355
420
475
285
340
385
600
700
385
460
520
310
375
420
700
750
400
475
535
320
385
435
750
800
410
490
555
330
395
450
800
900
435
520
585
355
425
480
900
1000
455
545
615
375
445
500
1000
1250
495
590
665
405
485
545
1250
1500
520
625
705
435
520
585
1500
1750
545
650
735
455
545
615
1750
2000
560
665
750
470
560
630
2000
CORRECTION FACTORS
Ambient
For ambient temperatures other than 30°C (86°F), multiply the allowable ampacities
Ambient
Temp. °C
shown above by the appropriate factor shown below.
Temp. °F
21-25
1.08
1.05
1.04
1.08
1.05
1.04
70-77
26-30
1.00
1.00
1.00
1.00
1.00
1.00
78-86
31-35
.91
.94
.96
.91
.94
.96
87-95
36-40
.82
.88
.91
.82
.88
.91
96-104
41-45
.71
.82
.87
.71
.82
.87
105-113
46-50
.58
.75
.82
.58
.75
.82
114-122
51-55
.41
.67
.76
.41
.67
.76
123-131
56-60
.58
.71
.58
.71
132-140
61-70
.33
.58
.33
.58
141-158
71-80
.41
.41
159-176
Unless otherwise specifically permitted elsewhere in this Code, the overcurrent protection for conductor types marked with an obelisk (f) shall not exceed 15 amperes for No. 14, 20 amperes for No. 12, and
30 amperes for No. 10 copper; or 15 amperes for No. 12 and 25 amperes for No. 10 aluminum and copperclad aluminum after any correction factors for ambient temperature and number of conductors have been
applied.
ARTICLE 310 - CONDUCTORS FOR GENERAL WIRING
70-175
Table 310-17. Allowable Ampacities of Single Insulated Conductors,
Rated 0 through 2000 Volts, In Free Air
Based on Ambient Air Temperature of 30°C (86°F)
Size
Temperature Rating of Conductor. See Table 310-13.
Size
60°C
75°C
90°C
60°C
75°C
90°C
(140°F)
(167°F)
(194°F)
(140°F)
(167°F)
(194°F)
TYPES
TYPES
TYPES
TYPES
TYPES
TYPES
TWT,
FEPWt,
TA, TBS, SA
TWt,
RHt, RHWt,
TA, TBS,
UFt
RHt, RHWt,
SIS, FEPt,
UFT
THHW+,
SA, SIS,
THHWT,
FEPBt, MI,
THWT,
THHNT,
AWG
THWT,
RHHt, RHW-2,
THWNT,
THHWT,
AWG
kcmil
THWNT,
THHNT, THHW+,
XHHW+
THW-2, THWN-2,
kcmil
XHHW+
THW-2, THWN-2,
RHHT, RHW-2,
ZWt
USE-2, XHH,
USE-2,
XHHWt,
XHH, XHHWT,
XHHW-2, ZW-2
XHHW-2, ZW-2
COPPER
ALUMINUM OR COPPER-CLAD ALUMINUM
18
18
16
24
14
25t
30+
35t
12
30+
35t
40t
25t
30t
35f
12
10
40f
50t
55f
35f
40f
40f
10
8
60
70
80
45
55
60
8
6
80
95
105
60
75
80
6
4
105
125
140
80
100
110
4
3
120
145
165
95
115
130
3
2
140
170
190
110
135
150
2
1
165
195
220
130
155
175
1
1/0
195
230
260
150
180
205
1/0
2/0
225
265
300
175
210
235
2/0
3/0
260
310
350
200
240
275
3/0
4/0
300
360
405
235
280
315
4/0
250
340
405
455
265
315
355
250
300
375
445
505
290
350
395
300
350
420
505
570
330
395
445
350
400
455
545
615
355
425
480
400
500
515
620
700
405
485
545
500
600
575
690
780
455
540
615
600
700
630
755
855
500
595
675
700
750
655
785
885
515
620
700
750
800
680
815
920
535
645
725
800
900
730
870
985
580
700
785
900
1000
780
935
1055
625
750
845
1000
1250
890
1065
1200
710
855
960
1250
1500
980
1175
1325
795
950
1075
1500
1750
1070
1280
1445
875
1050
1185
1750
2000
1155
1385
1560
960
1150
1335
2000
CORRECTION FACTORS
Ambient
For ambient temperatures other than 30°C (86°F), multiply the allowable ampacities
Ambient
Temp. °C
shown above by the appropriate factor shown below.
Temp. °F
21-25
1.08
1.05
1.04
1.08
1.05
1.04
70-77
26-30
1.00
1.00
1.00
1.00
1.00
1.00
78-86
31-35
.91
.94
.96
.91
.94
.96
87-95
36-40
.82
.88
.91
.82
.88
.91
96-104
41-45
.71
.82
.87
.71
.82
.87
105-113
46-50
.58
.75
.82
.58
.75
.82
114-122
51-55
.41
.67
.76
.41
.67
.76
123-131
56-60
.58
.71
.58
.71
132-140
61-70
.33
.58
.33
.58
141-158
71-80
.41
.41
159-176
*Unless otherwise specifically permitted elsewhere in this Code, the overcurrent protection for conductor types marked with an obelisk (f) shall not exceed 15 amperes for No. 14, 20 amperes for No. 12, and
30 amperes for No. 10 copper; or 15 amperes for No. 12 and 25 amperes for No. 10 aluminum and copperclad aluminum.
70-176
NATIONAL ELECTRICAL CODE
Table 310-18. Allowable Ampacities of Three Single Insulated Conductors
Rated 0 through 2000 Volts, 150° to 250°C (302° to 482°F), in Raceway or
Cable Based on Ambient Air Temperature of 40°C (104°F)
Size
Temperature Rating of Conductor. See Table 310-13.
Size
150°C
200°C
250°C
150°C
(302°F)
(392°F)
(482°F)
(302°F)
TYPES
FEP,
TYPES
AWG
TYPE
FEPB,
PFAH,
TYPE
AWG
kcmil
Z
PFA
TFE
Z
kcmil
NICKEL OR
ALUMINUM
NICKEL-
OR COPPER-
COATED
CLAD
COPPER
COPPER
ALUMINUM
14
34
36
39
14
12
43
45
54
30
12
10
55
60
73
44
10
8
76
83
93
57
8
6
96
110
117
75
6
4
120
125
148
94
4
3
143
152
166
109
3
2
160
171
191
124
2
1
186
197
215
145
1
1/0
215
229
244
169
1/0
2/0
251
260
273
198
2/0
3/0
288
297
308
227
3/0
4/0
332
346
361
260
4/0
250
250
300
300
350
350
400
400
500
500
600
600
700
700
750
750
800
800
1000
1000
1500
1500
2000
2000
CORRECTION FACTORS
Ambient
For ambient temperatures other than 40°C (104°F), multiply the allowable ampaci-
Ambient
Temp. °C
ties shown above by the appropriate factor shown below.
Temp. °F
41-50
.95
.97
.98
.95
105-122
51-60
.90
.94
.95
.90
123-140
61-70
.85
.90
.93
.85
141-158
71-80
.80
.87
.90
.80
159-176
81-90
.74
.83
.87
.74
177-194
91-100
.67
.79
.85
.67
195-212
101-120
.52
.71
.79
.52
213-248
121-140
.30
.61
.72
.30
249-284
141-160
.50
.65
285-320
161-180
.35
.58
321-356
181-200
.49
357-392
201-225
.35
393-437
ARTICLE 310 - CONDUCTORS FOR GENERAL WIRING
70-177
Table 310-19. Allowable Ampacities for Single Insulated Conductors
Rated 0 through 2000 Volts, 150° to 250°C (302° to 482°F),
in Free Air Based on Ambient Air Temperature of 40°C (104°F)
Size
Temperature Rating of Conductor. See Table 310-13.
Size
150°C
200°C
250°C
150°C
(302°F)
(392°F)
Bare
(482°F)
(302°F)
Bare
or
or
AWG
AWG
TYPES
covered
covered
kcmil
kcmil
FEP,
conduc-
TYPES
conduc-
TYPE
FEPB,
tors
PFAH,
TYPE
tors
Z
PFA
TFE
Z
NICKEL OR
NICKEL-
ALUMINUM
COATED
OR COPPER-
COPPER
COPPER
CLAD ALUMINUM
14
46
54
30
59
25
14
12
60
68
35
78
47
30
12
10
80
90
50
107
63
35
10
8
106
124
70
142
83
55
8
6
155
165
95
205
112
75
6
4
190
220
125
278
148
100
4
3
214
252
150
327
170
120
3
2
255
293
175
381
198
135
2
1
293
344
200
440
228
160
1
1/0
339
399
235
532
263
185
1/0
2/0
390
467
275
591
305
215
2/0
3/0
451
546
320
708
351
250
3/0
4/0
529
629
370
830
411
285
4/0
250
415
325
250
300
460
360
300
350
520
405
350
400
560
435
400
500
635
495
500
600
710
560
600
700
780
615
700
750
805
635
750
800
835
660
800
900
865
715
900
1000
895
770
1000
1500
1205
980
1500
2000
1420
1215
2000
CORRECTION FACTORS
Ambient
For ambient temperatures other than 40°C (104°F), multiply the allowable ampacities
Ambient
Temp. °C
shown above by the appropriate factor shown below.
Temp. °F
41-50
.95
.97
.98
.95
105-122
51-60
.90
.94
.95
.90
123-140
61-70
.85
.90
.93
.85
141-158
71-80
.80
.87
.90
.80
159-176
81-90
.74
.83
.87
.74
177-194
91-100
.67
.79
.85
.67
195-212
101-120
.52
.71
.79
.52
213-248
121-140
.30
.61
.72
.30
249-284
141-160
.50
.65
285-320
161-180
.35
.58
321-356
181-200
.49
357-392
201-225
.35
393-437
70-178
NATIONAL ELECTRICAL CODE
Notes to Ampacity Tables of 0 to 2000 Volts
1. Explanation of Tables. For explanation of type letters and for recognized size of conductors for the various conductor insulations, see Section
310-13. For installation requirements, see Sections 310-1 through 310-10
and the various articles of this Code. For flexible cords, see Tables 400-4,
400-5(A), and 400-5(B).
3. 120/240 Volts, 3-Wire, Single-Phase Dwelling Services and Feeders.
For dwelling units, conductors, as listed below, shall be permitted to be utilized as 120/240-volt, 3-wire, single-phase service-entrance conductors, service lateral conductors, and feeder conductors that supply the total load to a
dwelling unit and installed in raceway or cable with or without an equipment
grounding conductor. The grounded conductor shall be permitted to be not
more than two AWG sizes smaller than the ungrounded conductors for application of this note, provided the requirements of Sections 215-2, 220-22, and
230-42 are met.
Conductor Types and Sizes
RH-RHH-RHW-THHW-THW-THWN-THHN-XHHW-USE
Aluminum or
Copper
Copper-Clad AL
Rating in Amps
AWG
AWG
4
2
100
3
1
110
2
1/0
125
1
2/0
150
1/0
3/0
175
2/0
4/0
200
3/0
250 kcmil
225
4/0
300 kcmil
250
250 kcmil
350 kcmil
300
350 kcmil
500 kcmil
350
400 kcmil
600 kcmil
400
5. Bare Conductors. Where bare conductors are used with insulated
conductors, their allowable ampacities shall be limited to those permitted
for the adjacent insulated conductors.
6. Mineral-Insulated, Metal-Sheathed Cable. The temperature limitation
on which the ampacities of mineral-insulated, metal-sheathed cable are
based is determined by the insulating materials used in the end seal. Termination fittings incorporating unimpregnated, organic, insulating materials
are limited to 90°C (194°F) operation.
7. Type MTW Machine Tool Wire.
(FPN): For the allowable ampacities of Type MTW wire, see Table 13-5(a) in
the Electrical Standard for Industrial Machinery, NFPA 79-1991.
ARTICLE 310 - CONDUCTORS FOR GENERAL WIRING
70-179
8. Adjustment Factors.
(a) More than Three Current-Carrying Conductors in a Raceway or
Cable. Where the number of current-carrying conductors in a raceway or
cable exceeds three, the allowable ampacities shall be reduced as shown in
the following table:
Percent of Values in
Number of
Tables as Adjusted for
Current-Carrying
Ambient Temperature
Conductors
if Necessary
4 through 6
80
7 through 9
70
10 through 20
50
21 through 30
45
31 through 40
40
41 and above
35
Where single conductors or multiconductor cables are stacked or bundled longer than 24 inches (610 mm) without maintaining spacing and are
not installed in raceways, the allowable ampacity of each conductor shall
be reduced as shown in the above table.
Exception No. 1: Where conductors of different systems, as provided in