Regl. 5293, art. 210-50(b)-210
Resolución 2535: adopta el Código Eléctrico Nacional, versión 1993. (Sustituye el Anejo A del Reglamento 4435)
Cite as Reglamento Núm. 5293, Art. 210-50(b)-210
70-364
NATIONAL ELECTRICAL CODE
(b) Resistance Elements. Resistance-type heating elements in electric
space heating equipment shall be protected at not more than 60 amperes.
Equipment rated more than 48 amperes and employing such elements shall
have the heating elements subdivided, and each subdivided load shall not
exceed 48 amperes. Where a subdivided load is less than 48 amperes, the
rating of the supplementary overcurrent protective device shall comply
with Section 424-3(b).
Exception: As provided in Section 424-72(a).
(c) Overcurrent Protective Devices. The supplementary overcurrent
protective devices for the subdivided loads specified in (b) above shall be
(1) factory-installed within or on the heater enclosure or supplied for use
with the heater as a separate assembly by the heater manufacturer; (2)
accessible, but shall not be required to be readily accessible; and (3) suitable for branch-circuit protection.
(FPN): See Section 240-10.
Where cartridge fuses are used to provide this overcurrent protection, a
single disconnecting means shall be permitted to be used for the several
subdivided loads.
(FPN No. 1): For supplementary overcurrent protection, see Section 240-10.
(FPN No. 2): For disconnecting means for cartridge fuses in circuits of any
voltage, see Section 240-40.
(d) Branch-Circuit Conductors. The conductors supplying the supplementary overcurrent protective devices shall be considered branch-circuit
conductors.
Exception: For heaters rated 50 kW or more, the conductors supplying
the supplementary overcurrent protective devices specified in (c) above
shall be permitted to be sized at not less than 100 percent of the nameplate
rating of the heater, provided all of the following conditions are met:
a. The heater is marked with a minimum conductor size; and
b. The conductors are not smaller than the marked minimum size; and
c. A temperature-actuated device controls the cyclic operation of the
equipment.
(e) Conductors for Subdivided Loads. Field-wired conductors between
the heater and the supplementary overcurrent protective devices shall be
sized at not less than 125 percent of the load served. The supplementary
overcurrent protective devices specified in (c) shall protect these conductors in accordance with Section 240-3.
Exception: For heaters rated 50 kW or more, the ampacity of field-wired
conductors between the heater and the supplementary overcurrent protective devices shall be permitted to be not less than 100 percent of the load
of their respective subdivided circuits, provided all of the following conditions are met:
a. The heater is marked with a minimum conductor size; and
b. The conductors are not smaller than the marked minimum size; and
c. A temperature-activated device controls the cyclic operation of the
equipment.