Regl. 5293, art. 210-50(b)-424

FIXED ELECTRIC SPACE HEATING EQUIPMENT 70-363

Last amended: 1993Length: 396 wordsOfficial source

Cite as Reglamento Núm. 5293, Art. 210-50(b)-424

(c) Unit Switch(es) as Disconnecting Means. A unit switch(es) with a marked "off" position that is part of a fixed heater and disconnects all ungrounded conductors shall be permitted as the disconnecting means required by this article where other means for disconnection are provided in the following types of occupancies. (1) Multifamily Dwellings. In multifamily dwellings, the other disconnecting means shall be within the dwelling unit, or on the same floor as the dwelling unit in which the fixed heater is installed, and shall also be permitted to control lamps and appliances. (2) Two-Family Dwellings. In two-family dwellings, the other disconnecting means shall be permitted either inside or outside of the dwelling unit in which the fixed heater is installed. In this case, an individual switch or circuit breaker for the dwelling unit shall be permitted and shall also be permitted to control lamps and appliances. (3) One-Family Dwellings. In one-family dwellings, the service disconnecting means shall be permitted to be the other disconnecting means. (4) Other Occupancies. In other occupancies, the branch-circuit switch or circuit breaker, where readily accessible for servicing of the fixed heater, shall be permitted as the other disconnecting means. 424-20. Thermostatically Controlled Switching Devices. (a) Serving as Both Controllers and Disconnecting Means. Thermostatically controlled switching devices and combination thermostats and manually controlled switches shall be permitted to serve as both controllers and disconnecting means, provided all of the following conditions are met: (1) Provided with a marked "off" position. (2) Directly open all ungrounded conductors when manually placed in the "off" position. (3) Designed so that the circuit cannot be energized automatically after the device has been manually placed in the "off" position. (4) Located as specified in Section 424-19. (b) Thermostats that Do Not Directly Interrupt All Ungrounded Conductors. Thermostats that do not directly interrupt all ungrounded conductors and thermostats that operate remote-control circuits shall not be required to meet the requirements of (a). These devices shall not be permitted as the disconnecting means. 424-21. Switch and Circuit Breaker to Be Indicating. Switches and circuit breakers used as disconnecting means shall be of the indicating type. 424-22. Overcurrent Protection. (a) Branch-Circuit Devices. Electric space heating equipment, other than such motor-operated equipment as required by Articles 430 and 440 to have additional overcurrent protection, shall be permitted to be protected against overcurrent where supplied by one of the branch circuits in
Regl. 5293, art. 210-50(b)-424: FIXED ELECTRIC SPACE HEATING EQUIPMENT 70-363 | Justis AI