Regl. 5293, art. 210-5-215
FEEDERS
Cite as Reglamento Núm. 5293, Art. 210-5-215
215-1. Scope. This article covers the installation requirements and minimum size and ampacity of conductors for feeders supplying branch-circuit
loads as computed in accordance with Article 220.
Exception: Feeders for electrolytic cells as covered in Section 668-3(c),
Exception Nos. 1 and 4.
215-2. Minimum Rating and Size. Feeder conductors shall have an
ampacity not less than required to supply the load as computed in Parts B,
C, and D of Article 220. The minimum sizes shall be as specified in (a) and
(b) below under the conditions stipulated. Feeder conductors for a dwelling unit or a mobile home need not be larger than service-entrance conductors. Article 310, Note 3, Notes to Ampacity Tables of 0 to 2000 Volts shall
be permitted to be used for conductor size.
(a) For Specified Circuits. The ampacity of feeder conductors shall not
be less than 30 amperes where the load supplied consists of any of the following number and types of circuits: (1) two or more 2-wire branch circuits
supplied by a 2-wire feeder; (2) more than two 2-wire branch circuits supplied by a 3-wire feeder; (3) two or more 3-wire branch circuits supplied by
a 3-wire feeder; or (4) two or more 4-wire branch circuits supplied by a
3-phase 4-wire feeder.
(b) Ampacity Relative to Service-Entrance Conductors. The feeder
conductor ampacity shall not be less than that of the service-entrance conductors where the feeder conductors carry the total load supplied by
service-entrance conductors with an ampacity of 55 amperes or less.