Regl. 5293, art. 210-5-220 dup2
BRANCH-CIRCUIT, FEEDER, AND SERVICE CALCS 70-51
Cite as Reglamento Núm. 5293, Art. 210-5-220 dup2
Table 220-3(b). General Lighting Loads By Occupancies
Unit Load per
Square Foot
Type of Occupancy
(Volt-Amperes)
Armories and Auditoriums
1
Banks
31/2**
Barber Shops and Beauty Parlors
3
Churches
1
Clubs
2
Court Rooms
2
Dwelling Units*
3
Garages - Commercial (storage)
½
Hospitals
2
Hotels and Motels, including apartment houses
without provision for cooking by tenants*
2
Industrial Commercial (Loft) Buildings
2
Lodge Rooms
1½
Office Buildings
3½***
Restaurants
2
Schools
3
Stores
3
Warehouses (storage)
¼
In any of the above occupancies except onefamily dwellings and individual dwelling units
of two-family and multifamily dwellings:
Assembly Halls and Auditoriums
1
Halls, Corridors, Closets, Stairways
½
Storage Spaces
¼
For SI units: one square foot = 0.093 square meter.
*All general-use receptacle outlets of 20-ampere or less rating in one-family, two-family, and
multifamily dwellings and in guest rooms of hotels and motels [except those connected to the
receptacle circuits specified in Sections 220-4(b) and (c)] shall be considered as outlets for general illumination, and no additional load calculations shall be required for such outlets.
**In addition, a unit load of 1 volt-ampere per square foot shall be included for generalpurpose receptacle outlets where the actual number of general-purpose receptacle outlets is
unknown.
(c) Other Loads - All Occupancies. In all occupancies, the minimum
load for each outlet for general-use receptacles and outlets not used for
general illumination shall be not less than the following, the loads shown
being based on nominal branch-circuit voltages.
70-52
NATIONAL ELECTRICAL CODE
(1) Outlet for a specific appliance or other load except for a motor
load
ampere rating of appliance or load served.
(2) Outlet for motor load
See Sections 430-22 and 430-24 and