Regl. 5293, art. 210-5-220 dup3
BRANCH-CIRCUIT, FEEDER, AND SERVICE CALCS 70-53
Cite as Reglamento Núm. 5293, Art. 210-5-220 dup3
220-4. Branch Circuits Required. Branch circuits for lighting and for
appliances, including motor-operated appliances, shall be provided to supply the loads computed in accordance with Section 220-3. In addition,
branch circuits shall be provided for specific loads not covered by Section
220-3 where required elsewhere in this Code; for small appliance loads as
specified in (b) below; and for laundry loads as specified in (c) below.
(a) Number of Branch Circuits. The minimum number of branch circuits shall be determined from the total computed load and the size or rating of the circuits used. In all installations, the number of circuits shall be
sufficient to supply the load served. In no case shall the load on any circuit
exceed the maximum specified by Section 210-22.
(b) Small Appliance Branch Circuits - Dwelling Unit. In addition to the
number of branch circuits determined in accordance with (a) above, two or
more 20-ampere small appliance branch circuits shall be provided for all
receptacle outlets specified by Section 210-52 for the small appliance loads.
(c) Laundry Branch Circuits - Dwelling Unit. In addition to the number
of branch circuits determined in accordance with (a) and (b) above, at least
one additional 20-ampere branch circuit shall be provided to supply the
laundry receptacle outlet(s) required by Section 210-52(f). This circuit shall
have no other outlets.
(d) Load Evenly Proportioned Among Branch Circuits. Where the load
is computed on a volt-amperes-per-square-foot (0.093-sq m) basis, the wiring system up to and including the branch-circuit panelboard(s) shall be
provided to serve not less than the calculated load. This load shall be
evenly proportioned among multioutlet branch circuits within the panelboard(s). Branch-circuit overcurrent devices and circuits need only be
installed to serve the connected load.
(FPN): See Examples 1(a), 1(b), 2(b), and 4(a), Chapter 9.
B. Feeders
220-10. General.
(a) Ampacity and Computed Loads. Feeder conductors shall have sufficient ampacity to supply the load served. In no case shall the computed
load of a feeder be less than the sum of the loads on the branch circuits
supplied as determined by Part A of this article after any applicable
demand factors permitted by Parts B, C, or D have been applied.
(FPN): See Examples 1 through 10, Chapter 9. See Section 210-22(b) for maximum load in amperes permitted for lighting units operating at less than 100 percent
power factor.
(b) Continuous and Noncontinuous Loads. Where a feeder supplies
continuous loads or any combination of continuous and noncontinuous
loads, the rating of the overcurrent device shall not be less than the noncontinuous load plus 125 percent of the continuous load.
70-54
NATIONAL ELECTRICAL CODE
Exception: Where the assembly including the overcurrent devices protecting the feeder(s) are listed for operation at 100 percent of their rating,
neither the ampere rating of the overcurrent device nor the ampacity of the
feeder conductors shall be less than the sum of the continuous load plus
the noncontinuous load.
220-11. General Lighting. The demand factors listed in Table 220-11 shall
apply to that portion of the total branch-circuit load computed for general
illumination. They shall not be applied in determining the number of
branch circuits for general illumination.
(FPN): See Section 220-16 for application of demand factors to small appliance
and laundry loads in dwellings.
Table 220-11. Lighting Load Feeder Demand Factors
Portion of Lighting Load
Demand
to which Demand
Factor
Type of Occupancy
Factor Applies (volt-amperes)
Percent
Dwelling Units
First 3000 or less at
100
From 3001 to 120,000 at
35
Remainder over 120,000 at
25
Hospitals*
First 50,000 or less at
40
Remainder over 50,000 at
20
Hotels and Motels - Including
Apartment Houses without
First 20,000 or less at
50
Provision for Cooking by
From 20,001 to 100,000 at
40
Tenants*
Remainder over 100,000 at
30
Warehouses
First 12,500 or less at
100
(Storage)
Remainder over 12,500 at
50
All Others
Total volt-amperes
100
*The demand factors of this table shall not apply to the computed load of feeders to areas
in hospitals, hotels, and motels where the entire lighting is likely to be used at one time, as
in operating rooms, ballrooms, or dining rooms.
220-12. Show-Window Lighting. For show-window lighting, a load of not
less than 200 volt-amperes shall be included for each linear foot (305 mm)
of show window, measured horizontally along its base.
(FPN): See Section 220-3(c), Exception No. 3, for branch circuits supplying
show windows.
220-13. Receptacle Loads - Nondwelling Units. In other than dwelling
units, receptacle loads computed at not more than 180 volt-amperes per
outlet in accordance with Section 220-3(c)(6) shall be permitted to be added
to the lighting loads and made subject to the demand factors given in Table
220-11, or they shall be permitted to be made subject to the demand factors given in Table 220-13.