Regl. 5293, art. 210-5-220 dup4
BRANCH-CIRCUIT, FEEDER, AND SERVICE CALCS 70-55
Cite as Reglamento Núm. 5293, Art. 210-5-220 dup4
Table 220-13.
Demand Factors for Nondwelling Receptacle Loads
Portion of Receptacle Load
Demand
to which Demand Factor
Factor
Applies (volt-amperes)
Percent
First 10 kVA or less
100
Remainder over 10 kVA at
50
220-14. Motors. Motor loads shall be computed in accordance with Sections 430-24, 430-25, and 430-26.
220-15. Fixed Electric Space Heating. Fixed electric space heating loads
shall be computed at 100 percent of the total connected load; however, in
no case shall a feeder load current rating be less than the rating of the largest branch circuit supplied.
Exception No. 1: Where reduced loading of the conductors results from
units operating on duty-cycle, intermittently, or from all units not operating at one time, the authority having jurisdiction may grant permission for
feeder conductors to have an ampacity less than 100 percent, provided the
conductors have an ampacity for the load so determined.
Exception No. 2: The use of the optional calculations in Sections 220-30
and 220-31 shall be permitted for fixed electric space heating loads in a
dwelling unit. In a multifamily dwelling, the use of the optional calculation
in Section 220-32 shall be permitted.
220-16. Small Appliance and Laundry Loads - Dwelling Unit.
(a) Small Appliance Circuit Load. In each dwelling unit, the feeder load
shall be computed at 1500 volt-amperes for each 2-wire small appliance
branch circuit required by Section 220-4(b) for small appliances supplied by
15- or 20-ampere receptacles on 20-ampere branch circuits in the kitchen,
pantry, dining room, and breakfast room. Where the load is subdivided
through two or more feeders, the computed load for each shall include not
less than 1500 volt-amperes for each 2-wire branch circuit for small appliances. These loads shall be permitted to be included with the general lighting
load and subjected to the demand factors permitted in Table 220-11 for the
general lighting load.
(b) Laundry Circuit Load. A feeder load of not less than 1500 voltamperes shall be included for each 2-wire laundry branch circuit installed
as required by Section 220-4(c). It shall be permissible to include this load
with the general lighting load and subject it to the demand factors provided
in Section 220-11.
220-17. Appliance Load - Dwelling Unit(s). It shall be permissible to
apply a demand factor of 75 percent to the nameplate-rating load of four or
more appliances fastened in place that are served by the same feeder in a
one-family, two-family, or multifamily dwelling.
70-56
NATIONAL ELECTRICAL CODE
Exception: This demand factor shall not be applied to electric ranges,
clothes dryers, space heating equipment, or air-conditioning equipment.
220-18. Electric Clothes Dryers - Dwelling Unit(s). The load for household electric clothes dryers in a dwelling unit(s) shall be 5000 watts (voltamperes) or the nameplate rating, whichever is larger, for each dryer
served. The use of the demand factors in Table 220-18 shall be permitted.
Table 220-18.
Demand Factors for Household Electric Clothes Dryers
Number of
Demand Factor
Dryers
Percent
1
100
2
100
3
100
4
100
5
80
6
70
7
65
8
60
9
55
10
50
11-13
45
14-19
40
20-24
35
25-29
32.5
30-34
30
35-39
27.5
40 and over
25
220-19. Electric Ranges and Other Cooking Appliances - Dwelling
Unit(s). The feeder demand load for household electric ranges, wallmounted ovens, counter-mounted cooking units, and other household
cooking appliances individually rated in excess of 13/4 kW shall be permitted to be computed in accordance with Table 220-19. Where two or more
single-phase ranges are supplied by a 3-phase, 4-wire feeder, the total load
shall be computed on the basis of twice the maximum number connected
between any two phases. kVA shall be considered equivalent to kW for
loads computed under this section.
(FPN): See Example 5(a), Chapter 9.
220-20. Kitchen Equipment - Other than Dwelling Unit(s). It shall be
permissible to compute the load for commercial electric cooking equipment, dishwasher booster heaters, water heaters, and other kitchen equipment in accordance with Table 220-20. These demand factors shall be
applied to all equipment that has either thermostatic control or intermittent
use as kitchen equipment. They shall not apply to space heating, ventilating, or air-conditioning equipment.
However, in no case shall the feeder demand be less than the sum of the
largest two kitchen equipment loads.