Regl. 5293, art. 230-90-225

OUTSIDE BRANCH

Last amended: 1993Length: 104 wordsOfficial source

Cite as Reglamento Núm. 5293, Art. 230-90-225

CIRCUITS AND FEEDERS 225-1. Scope. This article covers requirements for outside branch circuits and feeders run between buildings, structures, or poles on the premises; and electric equipment and wiring for the supply of utilization equipment that is located on or attached to the outside of buildings, structures, or poles. Exception: Outside branch circuits and feeders for electrolytic cells as covered in Section 668-3(c), Exception Nos. 1 and 4. (FPN): For additional information on wiring over 600 volts, see National Electrical Safety Code, ANSI C2-1990. 225-2. Other Articles. Application of other articles, including additional requirements to specific cases of equipment and conductors, is as follows: