230-1. Scope. This article covers service conductors and equipment for
control and protection of services and their installation requirements.
(FPN): See Diagram 230-1.
A. General.
230-2. Number of Services. A building or other structure served shall be
supplied by only one service.
Where more than one service is permitted by any of the following exceptions, a permanent plaque or directory shall be installed at each service
drop or lateral or at each service-equipment location denoting all other services on or in that building or structure and the area served by each.
Exception No. 1: For fire pumps where a separate service is required.
Exception No. 2: For emergency, legally required standby, optional
standby, or parallel power production systems where a separate service is
required.
ARTICLE 230 - SERVICES
70-71
General
Part A
Overhead Service Drop Conductors
Part B
Underground Service-Lateral Conductors
Part C
Service-Entrance Conductors
Part D
Service Equipment - General
Part E
Service Equipment - Disconnecting Means
Part F
Service Equipment - Overcurrent Protection
Part G
Services over 600 Volts, Nominal
Part H
SOURCE
Overhead
Underground
Last pole
Street main
Part B
Service drop
Service lateral
Part C
230-24
Clearances
Depth of burial 230-49
and protection
Service head
Terminal box,
meter, or other
enclosure
Service-entrance
Part D
conductors
Service equipment
General
Part E
grounding
230-63
Disconnecting means
Part F
Overcurrent protection
Part G
Branch circuits
Articles 210, 225
Feeders
Articles 215, 225
Diagram 230-1. Services.
70-72
NATIONAL ELECTRICAL CODE
Exception No. 3: Multiple-Occupancy Buildings. By special permission,
in multiple-occupancy buildings where there is no available space for service equipment accessible to all the occupants.
Exception No. 4: Capacity Requirements. Two or more services shall be
permitted:
a. Where the capacity requirements are in excess of 2000 amperes at
a supply voltage of 600 volts or less; or
b. Where the load requirements of a single-phase installation are
greater than the serving agency normally supplies through one service; or
C. By special permission.
Exception No. 5: Buildings of Large Area. By special permission, for a
single building or other structure sufficiently large to make two or more
services necessary.
Exception No. 6: For different characteristics, such as for different voltages, frequencies, or phases, or for different uses, such as for different
rate schedules.
Exception No. 7: For the purpose of Section 230-40, Exception No. 2
only, underground sets of conductors, size ¹/₀ and larger, running to
the same location and connected together at their supply end but not
connected together at their load end shall be considered to be one service lateral.
230-3. One Building or Other Structure Not to Be Supplied Through
Another. Service conductors supplying a building or other structure shall
not pass through the interior of another building or other structure.
(FPN): See Section 230-6 for concrete or masonry-encased conductors considered outside of a building.
230-6. Conductors Considered Outside of Building. Conductors shall be
considered outside of a building or other structure under any of the following conditions: (1) where installed under not less than 2 inches (50.8 mm)
of concrete beneath a building or other structure; (2) where installed within
a building or other structure in a raceway that is encased in concrete or
brick not less than 2 inches (50.8 mm) thick; or (3) where installed in a
transformer vault conforming to the requirements of Article 450, Part C.
230-7. Other Conductors in Raceway or Cable. Conductors other than
service conductors shall not be installed in the same service raceway or
service cable.
Exception No. 1: Grounding conductors.
Exception No. 2: Load management control conductors having overcurrent protection.
230-8. Raceway Seal. Where a service raceway enters from an underground distribution system, it shall be sealed in accordance with Section
300-5. Spare or unused raceways shall also be sealed. Sealants shall be
identified for use with the cable insulation, shield, or other components.
ARTICLE 230 - SERVICES
70-73
230-9. Clearance from Building Openings. Service conductors installed
as open conductors or multiconductor cable without an overall outer jacket
shall have a clearance of not less than 3 feet (914 mm) from windows
that are designed to be opened, doors, porches, fire escapes, or similar
locations.
Exception: Conductors run above the top level of a window shall be
permitted to be less than the 3 feet (914 mm) requirement above.
Overhead service conductors shall not be installed beneath openings
through which materials may be moved, such as openings in farm and
commercial buildings, and shall not be installed where they will obstruct
entrance to these building openings.
230-10. Service Conductors. The conductors from the service point to
the service disconnecting means shall be considered service conductors.
B. Overhead Service-Drop Conductors
230-21. Overhead Supply. Overhead conductors to a building or other
structure (such as a pole) on which a meter or disconnecting means is
installed shall be considered as a service drop and installed accordingly.
(FPN): Example: Farm loads in Part D of Article 220.
230-22. Insulation or Covering. Service conductors shall normally withstand exposure to atmospheric and other conditions of use without detrimental leakage of current. Individual conductors shall be insulated or covered with an extruded thermoplastic or thermosetting insulating material.
Exception: The grounded conductor of a multiconductor cable shall be
permitted to be bare.
230-23. Size and Rating.
(a) General. Conductors shall have sufficient ampacity to carry the load
without a temperature rise detrimental to the covering or insulation of the
conductors and shall have adequate mechanical strength.
(b) Minimum Size. The conductors shall not be smaller than No. 8 copper or No. 6 aluminum or copper-clad aluminum.
Exception: For installations to supply only limited loads of a single
branch circuit such as small polyphase power, controlled water heaters.
and the like, they shall not be smaller than No. 12 hard-drawn copper or
equivalent.
(c) Grounded Conductors. The grounded conductor shall not be less
than the minimum size as required by Section 250-23(b).
230-24. Clearances. The vertical clearances of all service-drop conductors shall be based on conductor temperature of 60°F (15°C), no wind, with
final unloaded sag in the wire, conductor, or cable.
70-74
NATIONAL ELECTRICAL CODE
Service-drop conductors shall not be readily accessible and shall comply
with (a) through (d) below for services not over 600 volts, nominal.
(a) Above Roofs. Conductors shall have a vertical clearance of not less
than 8 feet (2.44 m) above the roof surface. The vertical clearance above
the roof level shall be maintained for a distance not less than 3 feet (914
mm) in all directions from the edge of the roof.
Exception No. 1: The area above a roof surface subject to pedestrian or
vehicular traffic shall have a vertical clearance from the roof surface in
accordance with the clearance requirements of Section 230-24(b).
Exception No. 2: Where the voltage between conductors does not
exceed 300 and the roof has a slope of not less than 4 inches (102 mm) in
12 inches (305 mm), a reduction in clearance to 3 feet (914 mm) shall be
permitted.
Exception No. 3: Where the voltage between conductors does not
exceed 300, a reduction in clearance above only the overhanging portion
of the roof to not less than 18 inches (457 mm) shall be permitted if (1) not
more than 6 feet (1.83 m) of service-drop conductors, 4 feet (1.22 m) horizontally, pass above the roof overhang, and (2) they are terminated at a
through-the-roof raceway or approved support.
(FPN): See Section 230-28 for mast supports.
Exception No. 4: The requirement for maintaining the vertical clearance
3 feet (914 mm) from the edge of the roof shall not apply to the final conductor span where the service drop is attached to the side of a building.
(b) Vertical Clearance from Ground. Service-drop conductors where
not in excess of 600 volts, nominal, shall have the following minimum
clearance from final grade.
10 feet (3.05 m) - at the electric service entrance to buildings, or at the
drip loop of the building electric entrance, or above areas or sidewalks
accessible only to pedestrians, measured from final grade or other accessible surface only for service-drop cables supported on and cabled together
with a grounded bare messenger and limited to 150 volts to ground.
12 feet (3.66 m) - over residential property and driveways, and those
commercial areas not subject to truck traffic where the voltage is limited to
300 volts to ground.
15 feet (4.57 m) - for those areas listed in the 12-foot (3.66-m) classification where the voltage exceeds 300 volts to ground.
18 feet (5.49m) - over public streets, alleys, roads, parking areas subject to truck traffic, driveways on other than residential property, and other
land traversed by vehicles such as cultivated, grazing, forest, and orchard.
(c) Clearance from Building Openings. See Section 230-9.
(d) Clearance from Swimming Pools. See Section 680-8.
230-26. Point of Attachment. The point of attachment of the service-drop
conductors to a building or other structure shall provide the minimum
clearances as specified in Section 230-24. In no case shall this point of
attachment be less than 10 feet (3.05 m) above finished grade.
ARTICLE 230 - SERVICES
70-75
230-27. Means of Attachment. Multiconductor cables used for service
drops shall be attached to buildings or other structures by fittings identified
for use with service conductors. Open conductors shall be attached to fittings identified for use with service conductors or to noncombustible, nonabsorbent insulators securely attached to the building or other structure.
230-28. Service Masts as Supports. Where a service mast is used for the
support of service-drop conductors, it shall be of adequate strength or be
supported by braces or guys to withstand safely the strain imposed by the
service drop. Where raceway-type service masts are used, all raceway fittings shall be identified for use with service masts.
(FPN): It is the intent of this section to allow only power service-drop conductors to be attached to a service mast.
230-29. Supports Over Buildings. Service-drop conductors passing over
a roof shall be securely supported by substantial structures. Where practicable, such supports shall be independent of the building.
C. Underground Service-Lateral Conductors
230-30. Insulation. Service-lateral conductors shall withstand exposure to
atmospheric and other conditions of use without detrimental leakage of current. Service-lateral conductors shall be insulated for the applied voltage.
Exception: A grounded conductor shall be permitted to be uninsulated
as follows:
a. Bare copper used in a raceway.
b. Bare copper for direct burial where bare copper is judged to be
suitable for the soil conditions.
C. Bare copper for direct burial without regard to soil conditions
where part of a cable assembly identified for underground use.
d. Aluminum or copper-clad aluminum without individual insulation or covering where part of a cable assembly identified for underground use in a raceway or for direct burial.
230-31. Size and Rating.
(a) General. Service-lateral conductors shall have sufficient ampacity to
carry the current for the load as computed in accordance with Article 220
and shall have adequate mechanical strength.
(b) Minimum Size. The conductors shall not be smaller than No. 8 copper or No. 6 aluminum or copper-clad aluminum.
Exception: For installations to supply only limited loads of a single
branch circuit such as small polyphase power, controlled water heaters
and the like, they shall not be smaller than No. 12 copper or No. 10 aluminum or copper-clad aluminum.
(c) Grounded Conductors. The grounded conductor shall not be less
than the minimum size required by Section 250-23(b).
(FPN): Reasonable efficiency of operation can be provided when voltage drop
is taken into consideration in sizing the service-lateral conductors.
70-76
NATIONAL ELECTRICAL CODE
230-32. Protection Against Damage. Underground service-lateral conductors shall be protected against damage in accordance with Section
300-5. Service-lateral conductors entering a building shall be installed in
accordance with Section 230-6 or protected by a raceway wiring method
identified in Section 230-43.
D. Service-Entrance Conductors
230-40. Number of Service-Entrance Conductor Sets. Each service drop
or lateral shall supply only one set of service-entrance conductors.
Exception No. 1: Buildings with more than one occupancy shall be permitted to have one set of service-entrance conductors run to each occupancy or to a group of occupancies.
Exception No. 2: Where two to six service disconnecting means in
separate enclosures are grouped at one location and supply separate loads
from one service drop or lateral, one set of service-entrance conductors
shall be permitted to supply each or several such service equipment
enclosures.
230-41. Insulation of Service-Entrance Conductors. Service-entrance
conductors shall normally withstand exposure to atmospheric and other
conditions of use without detrimental leakage of current. Service-entrance
conductors entering or on the exterior of buildings or other structures shall
be insulated.
Exception: A grounded conductor shall be permitted to be uninsulated
as follows:
a. Bare copper used in a raceway or part of a service cable assembly.
b. Bare copper for direct burial where bare copper is judged to be
suitable for the soil conditions.
C. Bare copper for direct burial without regard to soil conditions
where part of a cable assembly identified for underground use.
d. Aluminum or copper-clad aluminum without individual insulation or covering where part of a cable assembly or identified for underground use in a raceway or for direct burial.
230-42. Size and Rating.
(a) General. Service-entrance conductors shall be of sufficient size to
carry the loads as computed in Article 220. Ampacity shall be determined
from Section 310-15.
Exception: The maximum allowable current of approved busways shall
be that value for which the busway has been listed or labeled.
(b) Ungrounded Conductors. Ungrounded conductors shall have an
ampacity of not less than:
(1) 100 amperes, 3-wire for a service to a one-family dwelling with six
or more 2-wire branch circuits.
(2) 100 amperes, 3-wire for a service to a one-family dwelling with an
initial net computed load of 10 kVA or more.
ARTICLE 230 - SERVICES
70-77
(3) 60 amperes for other loads.
Exception No. 1: For loads consisting of not more than two 2-wire branch
circuits, No. 8 copper or No. 6 aluminum or copper-clad aluminum.
Exception No. 2: By special permission, for loads limited by demand or
by the source of supply, No. 8 copper or No. 6 aluminum or copper-clad
aluminum.
Exception No. 3: For limited loads of a single branch circuit, No. 12
copper or No. 10 aluminum or copper-clad aluminum, but in no case
smaller than the branch-circuit conductors.
(c) Grounded Conductors. The grounded conductor shall not be less
than the minimum size as required by Section 250-23(b).
230-43. Wiring Methods for 600 Volts, Nominal, or Less. Serviceentrance conductors shall be installed in accordance with the applicable
requirements of this Code covering the type of wiring method used and
limited to the following methods: (1) open wiring on insulators; (2) rigid
metal conduit; (3) intermediate metal conduit; (4) electrical metallic tubing; (5) service-entrance cables; (6) wireways; (7) busways; (8) auxiliary
gutters; (9) rigid nonmetallic conduit; (10) cablebus; (11) Type MC
cable; (12) mineral-insulated, metal-sheathed cable; (13) flexible metal
conduit or liquidtight flexible metal conduit not over 6 feet (1.83 m) long
between raceways, or between raceway and service equipment, with
equipment bonding jumper routed with the flexible metal conduit
according to provisions of Section 250-79(a), (c), (d), and (f); or (14) liquidtight flexible nonmetallic conduit.
Approved cable tray systems shall be permitted to support cables
approved for use as service-entrance conductors.
230-46. Unspliced Conductors. Service-entrance conductors shall not be
spliced.
Exception No. 1: Clamped or bolted connections in metering equipment
enclosures shall be permitted.
Exception No. 2: Where service-entrance conductors are tapped to supply two to six disconnecting means grouped at a common location.
Exception No. 3: At a properly enclosed junction point where an underground wiring method is changed to another type of wiring method.
Exception No. 4: A connection shall be permitted where service conductors are extended from a service drop to an outside meter location and
returned to connect to the service-entrance conductors of an existing
installation.
Exception No. 5: Where the service-entrance conductors consist of
busway, connections shall be permitted as required to assemble the various sections and fittings.
230-49. Protection Against Physical Damage - Underground. Underground service-entrance conductors shall be protected against physical
damage in accordance with Section 300-5.
70-78
NATIONAL ELECTRICAL CODE
230-50. Protection of Open Conductors and Cables Against Damage -
Aboveground. Service-entrance conductors installed aboveground shall
be protected against physical damage as specified in (a) or (b) below.
(a) Service-Entrance Cables. Service-entrance cables, where subject
to physical damage, such as where installed in exposed places near
sidewalks, walkways, driveways, or coal chutes, or where subject to
contact with awnings, shutters, swinging signs, or similar objects, shall
be protected in any of the following ways: (1) by rigid metal conduit; (2)
by intermediate metal conduit; (3) by rigid nonmetallic conduit suitable
for the location; (4) by electrical metallic tubing; or (5) by other
approved means.
(b) Other than Service-Entrance Cable. Individual open conductors and
cables other than service-entrance cables shall not be installed within
10 feet (3.05 m) of grade level or where exposed to physical damage.
Exception: Type MI and Type MC cable shall be permitted within
10 feet (3.05 m) of grade level where not exposed to physical damage or
where protected in accordance with Section 300-5(d).
230-51. Mounting Supports. Cables or individual open service conductors shall be supported as specified in (a), (b), or (c) below.
(a) Service-Entrance Cables. Service-entrance cables shall be supported by straps or other approved means within 12 inches (305 mm) of
every service head, gooseneck, or connection to a raceway or enclosure
and at intervals not exceeding 30 inches (762 mm).
(b) Other Cables. Cables that are not approved for mounting in contact
with a building or other structure shall be mounted on insulating supports
installed at intervals not exceeding 15 feet (4.57 m) and in a manner that
will maintain a clearance of not less than 2 inches (50.8 mm) from the surface over which they pass.
(c) Individual Open Conductors. Individual open conductors shall be
installed in accordance with Table 230-51(c). Where exposed to the
weather, the conductors shall be mounted on insulators or on insulating
supports attached to racks, brackets, or other approved means. Where not
exposed to the weather, the conductors shall be mounted on glass or porcelain knobs.
230-52. Individual Conductors Entering Buildings or Other Structures.
Where individual open conductors enter a building or other structure, they
shall enter through roof bushings or through the wall in an upward slant
through individual, noncombustible, nonabsorbent insulating tubes. Drip
loops shall be formed on the conductors before they enter the tubes.
230-53. Raceways to Drain. Where exposed to the weather, raceways
enclosing service-entrance conductors shall be raintight and arranged to
drain. Where embedded in masonry, raceways shall be arranged to
drain.
Exception: As permitted in Section 350-2.
ARTICLE 230 - SERVICES
70-79
Table 230-51(c). Supports and Clearances for
Individual Open Service Conductors
Minimum Clearances
In Inches
Maximum Distance
Maximum
in Feet
Between
From
Volts
Between Supports
Conductors
Surface
600
9
6
2
600
15
12
2
300
4½
3
2
600*
41/2*
2½*
1*
For SI units: one inch = 25.4 millimeters; one foot = 0.3048 meter.
*Where not exposed to weather.
230-54. Connections at Service Head.
(a) Raintight Service Head. Service raceways shall be equipped with a
raintight service head at the point of connection to service-drop conductors.
(b) Service Cable Equipped with Raintight Service Head or Gooseneck.
Service cables, either (1) unless continuous from pole to service equipment
or meter, shall be equipped with a raintight service head, or (2) shall be
formed in a gooseneck and taped and painted or taped with a self-sealing,
weather-resistant thermoplastic.
(c) Service Heads Above Service-Drop Attachment. Service heads, and
goosenecks in service-entrance cables, shall be located above the point of
attachment of the service-drop conductors to the building or other
structure.
Exception: Where it is impracticable to locate the service head above
the point of attachment, the service head location shall be permitted not
farther than 24 inches (610 mm) from the point of attachment.
(d) Secured. Service cables shall be held securely in place.
(e) Separately Bushed Openings. Service heads shall have conductors
of different potential brought out through separately bushed openings.
(f) Drip Loops. Drip loops shall be formed on individual conductors. To
prevent the entrance of moisture, service-entrance conductors shall be
connected to the service-drop conductors either (1) below the level of the
service head, or (2) below the level of the termination of the serviceentrance cable sheath.
(g) Arranged that Water Will Not Enter Service Raceway or Equipment.
Service-drop conductors and service-entrance conductors shall be
arranged so that water will not enter service raceway or equipment.
230-55. Termination at Service Equipment. Any service raceway or
cable shall terminate at the inner end in a box, cabinet, or equivalent fitting that effectively encloses all energized metal parts.
Exception: Where the service disconnecting means is mounted on a
switchboard having exposed busbars on the back, a raceway shall be permitted to terminate at a bushing.
70-80
NATIONAL ELECTRICAL CODE
230-56. Service-Entrance Conductor with the Higher Voltage-to-Ground.
On a 4-wire delta-connected service where the midpoint of one phase is
grounded, the service-entrance conductor having the higher phase voltage
to ground shall be durably and permanently marked by an outer finish that
is orange in color or by other effective means.
E. Service Equipment - General
230-62. Service Equipment - Enclosed or Guarded. Energized parts of
service equipment shall be enclosed as specified in (a) below, or guarded
as specified in (b) below.
(a) Enclosed. Energized parts shall be enclosed so that they will not be
exposed to accidental contact or guarded as in (b) below.
(b) Guarded. Energized parts that are not enclosed shall be installed on
a switchboard, panelboard, or control board and guarded in accordance
with Sections 110-17 and 110-18. Such an enclosure shall be provided with
means for locking or sealing doors providing access to energized parts.
230-63. Grounding and Bonding. Service equipment, raceways, cable
armor, cable sheaths, etc., and any service conductor that is to be
grounded shall be grounded in accordance with the following parts of