Regl. 5293, art. 230-90-240
OVERCURRENT PROTECTION
Cite as Reglamento Núm. 5293, Art. 230-90-240
240-1. Scope. Parts A through G of this article provide the general
requirements for overcurrent protection and overcurrent protective
devices not more than 600 volts, nominal. Part H covers overcurrent protection over 600 volts, nominal.
(FPN): Overcurrent protection for conductors and equipment is provided to
open the circuit if the current reaches a value that will cause an excessive or dangerous temperature in conductors or conductor insulation. See also Sections 110-9
and 110-10 for requirements for interrupting capacity and protection against fault
currents.
A. General
240-2. Protection of Equipment. Equipment shall be protected against
overcurrent in accordance with the article in this Code covering the type
of equipment as specified in the following list.
ARTICLE 240 - OVERCURRENT PROTECTION
70-91
Article
Air-Conditioning and Refrigerating Equipment
440
422
Appliances
210
Branch Circuits
364
Busways
460
Capacitors
Class 1, Class 2, and Class 3 Remote-Control, Signaling, and Power-
725
Limited Circuits
Closed-Loop and Programmed Power Distribution
780
Cranes and Hoists
610
Electric Signs and Outline Lighting
600
630
Electric Welders
668
Electrolytic Cells
Elevators, Dumbwaiters, Escalators, Moving Walks, Wheelchair Lifts,
and Stairway Chair Lifts
620
700
Emergency Systems
Fire Protective Signaling Systems
760
Fixed Electric Heating Equipment for Pipelines and Vessels
427
Fixed Electric Space Heating Equipment
424
Fixed Outdoor Electric Deicing and Snow-Melting Equipment
426
445
Generators
Health Care Facilities
517
Induction and Dielectric Heating Equipment
665
670
Industrial Machinery
Lighting Fixtures, Lampholders, Lamps, and Receptacles
410
Motion Picture and Television Studios and Similar Locations
530
Motors, Motor Circuits, and Controllers
430
455
Phase Converters
650
Pipe Organs
518
Places of Assembly
230
Services
Solar Photovoltaic Systems
690
Sound-Recording and Similar Equipment
640
Switchboards and Panelboards
384
Theaters, Audience Areas of Motion Picture and Television Studios,
and Similar Locations
520
Transformers and Transformer Vaults
450
660
X-Ray Equipment
240-3. Protection of Conductors. Conductors, other than flexible cords
and fixture wires, shall be protected against overcurrent in accordance
with their ampacities as specified in Section 310-15, unless otherwise permitted in (a) through (m) below.
(a) Power Loss Hazard. Conductor overload protection shall not be
required where the interruption of the circuit would create a hazard, such
as in a material handling magnet circuit or fire pump circuit. Short-circuit
protection shall be provided.
70-92
NATIONAL ELECTRICAL CODE
(FPN): See Installation of Centrifugal Fire Pumps, NFPA 20 - 1990 (ANSI).
(b) Devices Rated 800 Amperes or Less. Conductors not part of a multioutlet branch circuit supplying receptacles for cord- and plug-connected
portable loads and where the ampacity of the conductors does not correspond with the standard ampere rating of a fuse or a circuit breaker without overload trip adjustments above its rating (but that may have other trip
or rating adjustments), the next higher standard device rating shall be permitted only if this rating does not exceed 800 amperes.
(c) Devices Rated Over 800 Amperes. Where the overcurrent device is
rated over 800 amperes, the ampacity of the conductors it protects shall be
equal to or greater than the rating of the overcurrent device as defined in