Regl. 5293, art. 230-90-250
Resolución 2535: adopta el Código Eléctrico Nacional, versión 1993. (Sustituye el Anejo A del Reglamento 4435)
Cite as Reglamento Núm. 5293, Art. 230-90-250
Part B. Circuit and System Grounding.
Part C. Location of System Grounding Connections.
Part D. Enclosure Grounding.
Part F. Methods of Grounding.
Part G. Bonding.
Part H. Grounding Electrode System.
Part J. Grounding Conductors.
230-64. Working Space. Sufficient working space shall be provided in the
vicinity of the service equipment to permit safe operation, inspection, and
repairs. In no case shall this be less than that specified by Section 110-16.
230-65. Available Short-Circuit Current. Service equipment shall be suitable for the short-circuit current available at its supply terminals.
230-66. Marking. Service equipment shall be marked to identify it as
being suitable for use as service equipment.
F. Service Equipment - Disconnecting Means
230-70. General. Means shall be provided to disconnect all conductors in
a building or other structure from the service-entrance conductors.
(a) Location. The service disconnecting means shall be installed at a
readily accessible location either outside of a building or structure, or
inside nearest the point of entrance of the service conductors.
(b) Marking. Each service disconnecting means shall be permanently
marked to identify it as a service disconnecting means.
ARTICLE 230 - SERVICES
70-81
(c) Suitable For Use. Each service disconnecting means shall be suitable for the prevailing conditions. Service equipment installed in hazardous
(classified) locations shall comply with the requirements of Articles 500
through 517.
230-71. Maximum Number of Disconnects.
(a) General. The service disconnecting means for each service permitted by Section 230-2, or for each set of service-entrance conductors permitted by Section 230-40, Exception No. 1, shall consist of not more than
six switches or six circuit breakers mounted in a single enclosure, in a
group of separate enclosures, or in or on a switchboard. There shall be no
more than six disconnects per service grouped in any one location.
Exception: For the purpose of this section, disconnecting means used
solely for the control circuit of the ground-fault protection system, installed
as part of the listed equipment, shall not be considered a service disconnecting means.
(b) Single-Pole Units. Two or three single-pole switches or breakers,
capable of individual operation, shall be permitted on multiwire circuits,
one pole for each ungrounded conductor, as one multipole disconnect,
provided they are equipped with "handle ties" or a "master handle" to
disconnect all conductors of the service with no more than six operations
of the hand.
(FPN): See Section 384-16(a) for service equipment in panelboards.
230-72. Grouping of Disconnects.
(a) General. The two to six disconnects as permitted in Section 230-71
shall be grouped. Each disconnect shall be marked to indicate the load
served.
Exception: One of the two to six service disconnecting means permitted
in Section 230-71, where used only for a water pump also intended to provide fire protection, shall be permitted to be located remote from the other
disconnecting means.
(b) Additional Service Disconnecting Means. The one or more additional service disconnecting means for fire pumps or for emergency, legally
required standby, or optional standby services permitted by Section 230-2
shall be installed sufficiently remote from the one to six service disconnecting means for normal service to minimize the possibility of simultaneous
interruption of supply.
(FPN): See Sections 700-12(d) and (e) for emergency system services.
(c) Access to Occupants. In a multiple-occupancy building, each occupant shall have access to the occupant's service disconnecting means.
Exception: In a multiple-occupancy building where electric service and
electrical maintenance are provided by the building management and
where these are under continuous building management supervision, the
service disconnecting means supplying more than one occupancy shall be
permitted to be accessible to authorized management personnel only.
70-82
NATIONAL ELECTRICAL CODE
230-74. Simultaneous Opening of Poles. Each service disconnecting
means shall simultaneously disconnect all ungrounded service conductors
from the premises wiring system.
230-75. Disconnection of Grounded Conductor. Where the service disconnecting means does not disconnect the grounded conductor from the
premises wiring, other means shall be provided for this purpose in the service equipment. A terminal or bus to which all grounded conductors can
be attached by means of pressure connectors shall be permitted for this
purpose.
In a multisection switchboard, disconnects for the grounded conductor
shall be permitted to be in any section of the switchboard, provided any
such switchboard section is marked.
230-76. Manually or Power Operable. The service disconnecting means
for ungrounded service conductors shall consist of either (1) a manually
operable switch or circuit breaker equipped with a handle or other suitable
operating means, or (2) a power-operated switch or circuit breaker provided the switch or circuit breaker can be opened by hand in the event of
a power supply failure.
230-77. Indicating. The service disconnecting means shall plainly indicate whether it is in the open or closed position.
230-78. Externally Operable. An enclosed service disconnecting means
shall be externally operable without exposing the operator to contact with
energized parts.
Exception: A power-operated switch or circuit breaker shall not be
required to be externally operable by hand to a closed position.
230-79. Rating of Disconnect. The service disconnecting means shall
have a rating not less than the load to be carried, determined in accordance
with Article 220. In no case shall the rating be lower than specified in (a),
(b), (c), or (d) below.
(a) One-Circuit Installation. For installations to supply only limited
loads of a single branch circuit, the service disconnecting means shall have
a rating of not less than 15 amperes.
(b) Two-Circuit Installations. For installations consisting of not more
than two 2-wire branch circuits, the service disconnecting means shall
have a rating of not less than 30 amperes.
(c) One-Family Dwelling. For a one-family dwelling, the service disconnecting means shall have a rating of not less than 100 amperes, 3-wire
under either of the following conditions: (1) where the initial computed
load is 10 kVA or more, or (2) where the initial installation consists of six
or more 2-wire branch circuits.
(d) All Others. For all other installations, the service disconnecting
means shall have a rating of not less than 60 amperes.
ARTICLE 230 - SERVICES
70-83
230-80. Combined Rating of Disconnects. Where the service disconnecting means consists of more than one switch or circuit breaker, as permitted by Section 230-71, the combined ratings of all the switches or circuit breakers used shall not be less than the rating required for a single
switch or circuit breaker.
230-81. Connection to Terminals. The service conductors shall be connected to the service disconnecting means by pressure connectors, clamps,
or other approved means. Connections that depend upon solder shall not
be used.
230-82. Equipment Connected to the Supply Side of Service Disconnect.
Equipment shall not be connected to the supply side of the service disconnecting means.
(FPN): It is not the intent of this section to require individual meter socket
enclosures to be suitable for use as service equipment.
Exception No. 1: Cable limiters or other current-limiting devices.
Exception No. 2: Fuses and disconnecting means or circuit breakers
suitable for use as service equipment, in meter pedestals or otherwise provided and connected in series with the ungrounded service conductors and
located away from the building supplied.
Exception No. 3: Meters nominally rated not in excess of 600 volts,
provided all metal housings and service enclosures are grounded in accordance with Article 250.
Exception No. 4: Instrument transformers (current and voltage), highimpedance shunts, surge-protective devices identified for use on the supply arresters. side of the service disconnect, load management devices, and surge
Exception No. 5: Taps used only to supply load management devices,
circuits for emergency systems, stand-by power systems, fire pump
equipment, and fire and sprinkler alarms if provided with service equipment and installed in accordance with requirements for serviceentrance conductors.
Exception No. 6: Solar photovoltaic systems or interconnected electric
power production sources. See Articles 690 or 705 as applicable.
Exception No. 7: Where the service disconnecting means is power operable, the control circuit shall be permitted to be connected ahead of the
service disconnecting means if suitable overcurrent protection and disconnecting means are provided.
Exception No. 8: Ground-fault protection systems where installed as
part of listed equipment, if suitable overcurrent protection and disconnecting means are provided.
230-83. Transfer Equipment. Transfer equipment, including transfer
switches, shall operate such that all ungrounded conductors of one source
of supply are disconnected before any ungrounded conductors of the second source are connected.
70-84
NATIONAL ELECTRICAL CODE
Exception No. 1: Where manual equipment identified for the purpose or
suitable automatic equipment is utilized, two or more sources shall be permitted to be connected in parallel through transfer equipment.
Exception No. 2: Where parallel operation is used and suitable automatic or manual control equipment is provided.
G. Service Equipment - - Overcurrent Protection
230-90. Where Required. Each ungrounded service conductor shall have
overload protection.
(a) Ungrounded Conductor. Such protection shall be provided by an
overcurrent device in series with each ungrounded service conductor having a rating or setting not higher than the allowable ampacity of the
conductor.
Exception No. 1: For motor-starting currents, ratings in conformity
with Sections 430-52, 430-62, and 430-63 shall be permitted.
Exception No. 2: Fuses and circuit breakers with a rating or setting in
conformity with Section 240-3(b) or (c) and Section 240-6.
Exception No. 3: Not more than six circuit breakers or six sets of fuses
shall be permitted as the overcurrent device to provide the overload protection. The sum of the ratings of the circuit breakers or fuses shall be permitted to exceed the ampacity of the service conductors, provided the calculated load in accordance with Article 220 does not exceed the ampacity
of the service conductors.
Exception No. 4: Fire Pumps. Where the service to the fire pump room
is judged to be outside of buildings, these provisions shall not apply. Overcurrent protection for fire pump services shall be selected or set to carry
locked-rotor current of the motor(s) indefinitely.
(FPN): See Centrifugal Fire Pumps, NFPA 20-1990 (ANSI).
A set of fuses shall be considered all the fuses required to protect all the
ungrounded conductors of a circuit. Single-pole circuit breakers, grouped
in accordance with Section 230-71(b), shall be considered as one protective
device.
(b) Not in Grounded Conductor. No overcurrent device shall be
inserted in a grounded service conductor except a circuit breaker that
simultaneously opens all conductors of the circuit.
230-91. Location of Overcurrent Protection.
(a) General. The service overcurrent device shall be an integral part of
the service disconnecting means or shall be located immediately adjacent
thereto.
(b) Access to Occupants. In a multiple-occupancy building, each occupant shall have access to the overcurrent protective devices.
Exception: As permitted in Section 240-24(b), Exception.
230-92. Locked Service Overcurrent Devices. Where the service overcurrent devices are locked or sealed, or otherwise not readily accessible,
ARTICLE 230 - SERVICES
70-85
branch-circuit overcurrent devices shall be installed on the load side, shall
be mounted in a readily accessible location, and shall be of lower ampere
rating than the service overcurrent device.
230-93. Protection of Specific Circuits. Where necessary to prevent tampering, an automatic overcurrent device protecting service conductors supplying only a specific load, such as a water heater, shall be permitted to be
locked or sealed where located so as to be accessible.
230-94. Relative Location of Overcurrent Device and Other Service Equipment. The overcurrent device shall protect all circuits and devices.
Exception No. 1: The service switch shall be permitted on the supply
side.
Exception No. 2: High-impedance shunt circuits, lightning arresters,
surge protective capacitors, and instrument transformers (current and
voltage) shall be permitted to be connected and installed on the supply side
of the service disconnecting means as permitted in Section 230-82.
Exception No. 3: Circuits for emergency supply and load management
devices shall be permitted to be connected on the supply side of the
service overcurrent device where separately provided with overcurrent
protection.
Exception No. 4: Circuits used only for the operation of fire alarm,
other protective signaling systems, or the supply to fire pump equipment
shall be permitted to be connected on the supply side of the service overcurrent device where separately provided with overcurrent protection.
Exception No. 5: Meters nominally rated not in excess of 600 volts,
provided all metal housings and service enclosures are grounded in accordance with Article 250.
Exception No. 6: Where service equipment is power operable, the control circuit shall be permitted to be connected ahead of the service equipment if suitable overcurrent protection and disconnecting means are
provided.
230-95. Ground-Fault Protection of Equipment. Ground-fault protection
of equipment shall be provided for solidly grounded wye electrical services
of more than 150 volts to ground, but not exceeding 600 volts phaseto-phase for each service disconnecting means rated 1000 amperes or
more.
Exception No. 1: The provisions of this section shall not apply to a service disconnecting means for a continuous industrial process where a
nonorderly shutdown will introduce additional or increased hazards.
Exception No. 2: The provisions of this section shall not apply to fire
pumps.
(a) Setting. The ground-fault protection system shall operate to cause
the service disconnecting means to open all ungrounded conductors of the
faulted circuit. The maximum setting of the ground-fault protection shall be
1200 amperes, and the maximum time delay shall be one second for
ground-fault currents equal to or greater than 3000 amperes.
70-86
NATIONAL ELECTRICAL CODE
(b) Fuses. If a switch and fuse combination is used, the fuses employed
shall be capable of interrupting any current higher than the interrupting
capacity of the switch during a time when the ground-fault protective system will not cause the switch to open.
(FPN No. 1): As used in this section, the rating of the service disconnecting
means is considered to be the rating of the largest fuse that can be installed or the
highest continuous current trip setting for which the actual overcurrent device
installed in a circuit breaker is rated or can be adjusted.
(FPN No. 2): It is recognized that ground-fault protection may be desirable for
service disconnecting means rated less than 1000 amperes on solidly grounded wye
systems having more than 150 volts to ground, not exceeding 600 volts phase-tophase.
(FPN No. 3): As used in this section, solidly grounded means that the grounded conductor (neutral) is grounded without inserting any resistor or impedance
device.
(FPN No. 4): Ground-fault protection that functions to open the service disconnecting means will afford no protection from faults on the line side of the protective
element. It serves only to limit damage to conductors and equipment on the
load side in the event of an arcing ground fault on the load side of the protective
element.
(FPN No. 5): This added protective equipment at the service equipment will
make it necessary to review the overall wiring system for proper selective overcurrent protection coordination. Additional installations of ground-fault protective
equipment will be needed on feeders and branch circuits where maximum continuity of electrical service is necessary.
(FPN No. 6): Where ground-fault protection is provided for the service disconnecting means and interconnection is made with another supply system by a transfer device, means or devices may be needed to assure proper ground-fault sensing
by the ground-fault protection equipment.
(c) Performance Testing. The ground-fault protection system shall be
performance tested when first installed on site. The test shall be conducted
in accordance with instructions which shall be provided with the equipment. A written record of this test shall be made and shall be available to
the authority having jurisdiction.
H. Services Exceeding 600 Volts, Nominal
230-200. General. Service conductors and equipment used on circuits
exceeding 600 volts, nominal, shall comply with all applicable provisions of the preceding sections of this article and with the following sections, which supplement or modify the preceding sections. In no case
shall the provisions of this article apply to equipment on the supply side
of the service point.
(FPN): For clearances of conductors of over 600 volts, nominal, see National
Electrical Safety Code, ANSI C2-1990.
230-202. Service-Entrance Conductors. Service-entrance conductors to
buildings or enclosures shall be installed to conform to the following:
ARTICLE 230 - SERVICES
70-87
(a) Conductor Size. Service-entrance conductors shall not be smaller
than No. 6 unless in cable. Conductors in cable shall not be smaller than
No. 8.
(b) Wiring Methods. Service-entrance conductors shall be installed by
means of one of the following wiring methods: (1) in rigid metal conduit;
(2) in intermediate metal conduit; (3) in rigid nonmetallic conduit; (4) as
multiconductor cable identified as service cable; (5) as open conductors
where supported on insulators and where either accessible only to qualified
persons or where effectively guarded against accidental contact; (6) in
cablebus; or (7) in busways.
Underground service-entrance conductors shall conform to Section
710-4(b).
Cable tray systems shall be permitted to support cables identified as
service-entrance conductors. See Article 318.
(FPN): See Section 310-6 for shielding of solid dielectric insulated conductors.
(c) Open Work. Open wire services shall be installed in accordance with
the provisions of Article 710, Part D.
(d) Supports. Service-entrance conductors and their supports, including insulators, shall have strength and stability sufficient to ensure maintenance of adequate clearance with abnormal currents in case of short
circuits.
(e) Guarding. Open wires shall be guarded to make them accessible
only to qualified persons.
(f) Service Cable. Where cable conductors emerge from a metal sheath
or raceway, the insulation of the conductors shall be protected from moisture and physical damage by a pothead or other approved means.
(g) Draining Raceways. Unless conductors identified for use in wet
locations are used, raceways embedded in masonry or exposed to the
weather shall be arranged to drain.
(h) Over 15,000 Volts. Where the voltage exceeds 15,000 volts
between conductors, they shall enter either metal-enclosed switchgear
or a transformer vault conforming to the requirements of Sections
450-41 through 450-48.
230-203. Warning Signs. Signs with the words "Danger High Voltage-
Keep Out" shall be posted in plain view where unauthorized persons might
come in contact with energized parts.
230-204. Isolating Switches.
(a) Where Required. Where oil switches or air, oil, vacuum, or sulfur
hexafluoride circuit breakers constitute the service disconnecting means,
an air-break isolating switch shall be installed on the supply side of the disconnecting means and all associated service equipment.
Exception: Where such equipment is mounted on removable truck panels or metal-enclosed switchgear units, which cannot be opened unless the
70-88
NATIONAL ELECTRICAL CODE
circuit is disconnected, and which, when removed from the normal operating position, automatically disconnect the circuit breaker or switch from
all energized parts.
(b) Fuses as Isolating Switch. Where fuses are of the type that can be
operated as a disconnecting switch, a set of such fuses shall be permitted
as the isolating switch where: (1) the oil disconnecting means is a nonautomatic switch, and (2) the set of fuses disconnect the oil switch and all
associated service equipment from the service conductors.
(c) Accessible to Qualified Persons Only. The isolating switch shall be
accessible to qualified persons only.
(d) Grounding Connection. Isolating switches shall be provided with a
means for readily connecting the load side conductors to ground when disconnected from the source of supply.
A means for grounding the load side conductors shall not be required for
any duplicate isolating switch installed and maintained by the electric supply company.
230-205. Disconnecting Means.
(a) Location. The service disconnecting means shall be located in
accordance with Section 230-70 or Section 230-208(b).
Exception: Where under single management, the service disconnecting
means shall be permitted to be located in a separate building or structure
on the same premises. In such case, the service disconnecting means shall
be capable of being electrically opened by a readily accessible control
device located as near as practicable to where the feeder conductors enter
the building served. The control device shall be permanently marked to
identify its function and shall provide visual indication of the "on" or
"off" status of the remote service disconnect.
(b) Type. The service disconnecting means shall simultaneously disconnect all ungrounded conductors and shall have a fault-closing rating
not less than the maximum short-circuit current available at its supply
terminals.
Where fused switches or separately mounted fuses are installed, the fuse
characteristics shall be permitted to contribute to the fault-closing rating of
the disconnecting means.
230-206. Overcurrent Devices as Disconnecting Means. Where the circuit breaker or alternative for it specified in Section 230-208 for service
overcurrent devices meets the requirements specified in Section 230-205,
they shall constitute the service disconnecting means.
230-207. Equipment in Secondaries. Where the primary service equipment supplies one or more transformers whose secondary windings connect to a common bus of bars or wires, and the primary load-interrupter
switch or circuit breaker is capable of being opened and closed from a
point outside the transformer vault, the disconnecting means and overcurrent protection shall not be required in the secondary circuit if the primary
fuse or circuit breaker is rated or set to protect the secondary circuit.
ARTICLE 230 - SERVICES
70-89
230-208. Overcurrent Protection Requirements. Service-entrance conductors shall have a short-circuit protective device in each ungrounded
conductor on the load side of, or as an integral part of, the service-entrance
switch. The protective device shall be capable of detecting and interrupting all values of current in excess of its trip setting or melting point, that
can occur at its location. A fuse rated in continuous amperes not to exceed
three times the ampacity of the conductor, or a circuit breaker with a trip
setting of not more than six times the ampacity of the conductors, shall be
considered as providing the required short-circuit protection.
(FPN): See Tables 310-69 through 310-84 for ampacities of conductors rated
2001 volts and above.
Overcurrent devices shall conform to the following:
(a) In Vault or Consisting of Metal-Enclosed Switchgear. Where the
service equipment is installed in a transformer vault meeting the provisions
of Sections 450-41 through 450-48, or consists of metal-enclosed switchgear, the overcurrent protection and disconnecting means shall be one of
the following:
(1) A nonautomatic oil switch, oil fuse cutout, or air load-interrupter
switch shall be permitted with fuses. The interrupting rating of this switch
shall equal or exceed the continuous current rating of the fuse.
(2) An automatic trip circuit breaker of suitable current-carrying and
interrupting capacity.
(3) A switch capable of interrupting the no-load current of the transformer supplied through the switch and suitable fuses shall be permitted
provided the switch is interlocked with a single switch or circuit breaker on
the secondary circuit of the transformer so that the primary switch cannot
be opened when the secondary circuit is closed.
(b) Not in Vault or Not Consisting of Metal-Enclosed Switchgear.
Where the service equipment is not in a vault or metal-enclosed switchgear, the overcurrent protection and disconnecting means shall be either of
the following:
(1) An air load-interrupter switch or other switch capable of interrupting the rated circuit load shall be permitted with fuses on a pole or elevated
structure outside the building, provided the switch is operable by persons
using the building.
(2) An automatic-trip circuit breaker of suitable ampacity and interrupting capacity. The circuit breaker shall be located outside the building as near
as practicable to where the feeder conductors enter the building. The location
shall be permitted on a pole, roof, foundation, or other structure.
(c) Fuses. Fuses shall have an interrupting rating no less than the maximum available short-circuit current in the circuit at their supply terminals.
(d) Circuit Breakers. Circuit breakers shall be free to open in case. the
circuit is closed on an overload. This can be accomplished by means such
as trip-free circuit breakers. A service circuit breaker shall indicate clearly
whether it is open or closed, and shall have an interrupting rating no less
than the maximum available short-circuit current at its supply terminals.
70-90
NATIONAL ELECTRICAL CODE
Overcurrent relays shall be furnished in connection with current transformers in one of the following combinations:
(1) Three overcurrent relays operated from current transformers in
each phase.
(2) Two overcurrent relays operated by current from current transformers in any two phases and one overcurrent relay sensitive to groundfault current that is operated by the sum of the currents from current
transformers in each phase.
(3) Two overcurrent relays operated by current from current transformers in any two phases and one overcurrent relay sensitive to groundfault current that is operated from a current transformer that links all three
phase conductors and the grounded circuit conductor (neutral), if
provided.
(e) Enclosed Overcurrent Devices. The restriction to 80 percent of rating for an enclosed overcurrent device on continuous loads shall not apply
to overcurrent devices installed in services operating at over 600 volts.
230-209. Surge Arresters (Lightning Arresters). Surge arresters installed
in accordance with the requirements of Article 280 shall be permitted on
each ungrounded overhead service conductor.
230-210. Service Equipment-General Provisions. Service equipment
including instrument transformers shall conform to Article 710, Part B.
230-211. Metal-Enclosed Switchgear. Metal-enclosed switchgear shall
consist of a substantial metal structure and a sheet metal enclosure. Where
installed over a combustible floor, suitable protection thereto shall be
provided.