Regl. 5293, art. 240-81
Resolución 2535: adopta el Código Eléctrico Nacional, versión 1993. (Sustituye el Anejo A del Reglamento 4435)
Cite as Reglamento Núm. 5293, Art. 240-81
D. Disconnecting and Guarding
240-40. Disconnecting Means for Fuses. Disconnecting means shall be
provided on the supply side of all fuses in circuits of over 150 volts to
ground and cartridge fuses in circuits of any voltage, where accessible to
other than qualified persons, so that each individual circuit containing fuses
can be independently disconnected from the source of electric energy.
Exception No. 1: A device provided for current-limiting on the supply
side of the service disconnecting means as permitted by Section 230-82.
Exception No. 2: A single disconnecting means shall be permitted on
the supply side of more than one set of fuses as provided by Section 430-
112 for group operation of motors and in Section 424-22 for fixed electric
space heating equipment.
70-100
NATIONAL ELECTRICAL CODE
240-41. Arcing or Suddenly Moving Parts. Arcing or suddenly moving
parts shall comply with (a) and (b) below.
(a) Location. Fuses and circuit breakers shall be so located or shielded
that persons will not be burned or otherwise injured by their operation.
(b) Suddenly Moving Parts. Handles or levers of circuit breakers, and
similar parts that may move suddenly in such a way that persons in the
vicinity are likely to be injured by being struck by them, shall be guarded
or isolated.
E. Plug Fuses, Fuseholders, and Adapters
240-50. General.
(a) Maximum Voltage. Plug fuses and fuseholders shall not be used in
circuits exceeding 125 volts between conductors.
Exception: In circuits supplied by a system having a grounded neutral
and having no conductor at over 150 volts to ground.
(b) Marking. Each fuse, fuseholder, and adapter shall be marked with
its ampere rating.
(c) Hexagonal Configuration. Plug fuses of 15-ampere and lower rating
shall be identified by a hexagonal configuration of the window, cap, or other
prominent part to distinguish them from fuses of higher ampere ratings.
(d) No Energized Parts. Plug fuses, fuseholders, and adapters shall have
no exposed energized parts after fuses or fuses and adapters have been
installed.
(e) Screw Shell. The screw shell of a plug-type fuseholder shall be connected to the load side of the circuit.
240-51. Edison-Base Fuses.
(a) Classification. Plug fuses of the Edison-base type shall be classified
at not over 125 volts and 30 amperes and below.
(b) Replacement Only. Plug fuses of the Edison-base type shall be used
only for replacements in existing installations where there is no evidence
of overfusing or tampering.
240-52. Edison-Base Fuseholders. Fuseholders of the Edison-base type
shall be installed only where they are made to accept Type S fuses by the
use of adapters.
240-53. Type S Fuses. Type S fuses shall be of the plug type and shall
comply with (a) and (b) below.
(a) Classification. Type S fuses shall be classified at not over 125 volts
and 0 to 15 amperes, 16 to 20 amperes, and 21 to 30 amperes.
(b) Noninterchangeable. Type S fuses of an ampere classification as
specified in (a) above shall not be interchangeable with a lower ampere
classification. They shall be so designed that they cannot be used in any
fuseholder other than a Type S fuseholder or a fuseholder with a Type S
adapter inserted.
ARTICLE 240 - OVERCURRENT PROTECTION
70-101
240-54. Type S Fuses, Adapters, and Fuseholders.
(a) To Fit Edison-Base Fuseholders. Type S adapters shall fit Edisonbase fuseholders.
(b) To Fit Type S Fuses Only. Type S fuseholders and adapters shall be
so designed that either the fuseholder itself or the fuseholder with a Type
S adapter inserted cannot be used for any fuse other than a Type S fuse.
(c) Nonremovable. Type S adapters shall be so designed that once
inserted in a fuseholder, they cannot be removed.
(d) Nontamperable. Type S fuses, fuseholders, and adapters shall be so
designed that tampering or shunting (bridging) would be difficult.
(e) Interchangeability. Dimensions of Type S fuses, fuseholders, and
adapters shall be standardized to permit interchangeability regardless of
the manufacturer.
F. Cartridge Fuses and Fuseholders
240-60. General.
(a) Maximum Voltage-300-Volt Type. Cartridge fuses and fuseholders
of the 300-volt type shall not be used in circuits of over 300 volts between
conductors.
Exception: In single-phase line-to-neutral circuits supplied from
3-phase, 4-wire, solidly grounded neutral systems where the line-to-neutral
voltage does not exceed 300V.
(b) Noninterchangeable-0-6000 Ampere Cartridge Fuseholders. Fuseholders shall be so designed that it will be difficult to put a fuse of any
given class into a fuseholder that is designed for a current lower, or voltage higher, than that of the class to which the fuse belongs. Fuseholders for
current-limiting fuses shall not permit insertion of fuses that are not
current-limiting.
(c) Marking. Fuses shall be plainly marked, either by printing on the
fuse barrel or by a label attached to the barrel, showing the following: (1)
ampere rating; (2) voltage rating; (3) interrupting rating where other than
10,000 amperes; (4) "current-limiting" where applicable; and (5) the name
or trademark of the manufacturer.
Exception: Interrupting rating marking shall not be required on fuses
used for supplementary protection.
240-61. Classification. Cartridge fuses and fuseholders shall be classified
according to voltage and amperage ranges. Fuses rated 600 volts, nominal,
or less, shall be permitted to be used for voltages at or below their ratings.
G. Circuit Breakers
240-80. Method of Operation. Circuit breakers shall be trip free and
capable of being closed and opened by manual operation. Their normal
method of operation by other than manual means, such as electrical or
pneumatic, shall be permitted if means for manual operation is also
provided.
70-102
NATIONAL ELECTRICAL CODE
Exception: As provided in Section 230-76(2) for circuit breakers used as
service disconnecting means.
240-81. Indicating. Circuit breakers shall clearly indicate whether they
are in the open "off" or closed "on" position.
Where circuit breaker handles are operated vertically rather than rotationally or horizontally, the "up" position of the handle shall be the "on"
position.
240-82. Nontamperable. A circuit breaker shall be of such design that
any alteration of its trip point (calibration) or the time required for its operation will require dismantling of the device or breaking of a seal for other
than intended adjustments.
240-83. Marking.
(a) Durable and Visible. Circuit breakers shall be marked with their
ampere rating in a manner that will be durable and visible after installation.
Such marking shall be permitted to be made visible by removal of a trim or
cover.
(b) Location. Circuit breakers rated at 100 amperes or less and 600 volts
or less shall have the ampere rating molded, stamped, etched, or similarly
marked into their handles or escutcheon areas.
(c) Interrupting Rating. Every circuit breaker having an interrupting rating other than 5000 amperes shall have its interrupting rating shown on the
circuit breaker.
Exception: Interrupting rating marking shall not be required on circuit
breakers used for supplementary protection.
If a circuit breaker is used on a circuit having an available fault current
higher than its marked interrupting rating by being connected on the load
side of an acceptable overcurrent-protective device having the higher rating, this additional series combination interrupting rating shall be marked
on the end use equipment, such as switchboards and panelboards.
(d) Circuit Breakers Used as Switches. Where used as switches in 120-
volt and 277-volt fluorescent lighting circuits, circuit breakers shall be
listed and shall be marked "SWD."
(e) Voltage Marking. Circuit breakers shall be marked with a voltage
rating no less than the nominal system voltage that is indicative of their
capability to interrupt fault currents between phases or phase to ground.
(FPN): A circuit breaker with a straight voltage rating, e.g., 240V or 480V, may
be applied in a circuit in which the nominal voltage between any two conductors
does not exceed the circuit breaker's voltage rating; except that a two-pole circuit
breaker is not suitable for protecting a 3-phase corner-grounded delta circuit unless
it is marked 1-phase/3-phase to indicate such suitability.
A circuit breaker with a slash rating, e.g., 120/240V or 480Y/277V, may only be
applied in a circuit in which the nominal voltage to ground from any conductor does
not exceed the lower of the two values of the circuit breaker's voltage rating and the
nominal voltage between any two conductors does not exceed the higher value of
the circuit breaker's voltage rating.