Regl. 5293, art. 240-81-250
GROUNDING
Cite as Reglamento Núm. 5293, Art. 240-81-250
70-103
H. Overcurrent Protection Over 600 Volts, Nominal
240-100. Feeders. Feeders shall have a short-circuit protective device in
each ungrounded conductor or comply with Section 230-208(d)(2) or (d)(3).
The protective device(s) shall be capable of detecting and interrupting all
values of current that can occur at their location in excess of their trip setting or melting point. In no case shall the fuse rating in continuous amperes
exceed three times, or the long-time trip element setting of a breaker, six
times, the ampacity of the conductor.
Conductors tapped to a feeder shall be permitted to be protected by the
feeder overcurrent device where that overcurrent device also protects the
tap conductors.
(FPN): The operating time of the protective device, the available short-circuit
current, and the conductor used will need to be coordinated to prevent damaging or
dangerous temperatures in conductors or conductor insulation under short-circuit
conditions.
240-101. Branch Circuits. Branch circuits shall have a short-circuit protective device in each ungrounded conductor or comply with Section 230-
208(d)(2) or (d)(3). The protective device(s) shall be capable of detecting
and interrupting all values of current that can occur at their location in
excess of their trip setting or melting point.
ARTICLE 250 - GROUNDING
NOTICE
Following the issuance of this edition an appeal was filed with respect to
Section 250-45 of this article - refer to page 70-iii.
A. General
250-1. Scope. This article covers general requirements for grounding and
bonding of electrical installations, and specific requirements in (a) through
(f) below.
(a) Systems, circuits, and equipment required, permitted, or not permitted to be grounded.
(b) Circuit conductor to be grounded on grounded systems.
(c) Location of grounding connections.
(d) Types and sizes of grounding and bonding conductors and electrodes.
(e) Methods of grounding and bonding.
(f) Conditions under which guards, isolation, or insulation may be substituted for grounding.
(FPN No. 1): Systems and circuit conductors are grounded to limit voltages due
to lightning, line surges, or unintentional contact with higher voltage lines, and to
stabilize the voltage to ground during normal operation. Equipment grounding conductors are bonded to the system grounded conductor to provide a low impedance
path for fault current that will facilitate the operation of overcurrent devices under
ground-fault conditions.
(FPN No. 2): Conductive materials enclosing electrical conductors or equipment, or forming part of such equipment, are grounded to limit the voltage to ground
70-104
NATIONAL ELECTRICAL CODE
on these materials and bonded to facilitate the operation of overcurrent devices
under ground-fault conditions. See Section 110-10.
250-2. Application of Other Articles. In other articles applying to particular cases of installation of conductors and equipment, there are requirements that are in addition to those of this article or are modifications of
them:
Article
Section
Agricultural Buildings
547-8
Appliances
422-16
Branch Circuits
210-5
210-6
210-7
Cablebus
365-9
Circuits and Equipment Operating at
Less Than 50 Volts
720
Class 1, Class 2, and Class 3 Remote-Control, Signaling,
and Power-Limited Circuits
725-20
725-43
Closed-Loop and Programmed Power Distribution
780-3
Communications Circuits
800
Community Antenna Television and Radio Distribution
Systems
820-33
820-40
820-41
Conductors for General Wiring
310
Cranes and Hoists
610
Electronic Computer/Data Processing Equipment
645-15
Electrically Driven or Controlled Irrigation Machines
675-11(c)
675-12
675-13
675-14
675-15
Electric Signs and Outline Lighting
600
Electrolytic Cells
668
Elevators, Dumbwaiters, Escalators, Moving Walks,
Wheelchair Lifts, and Stairway Chair Lifts
620
Fire Protective Signaling Systems
760-6
Fixed Electric Heating Equipment for Pipelines
and Vessels
427-21
427-29
427-48
Fixed Electric Space Heating Equipment
424-14
Fixed Equipment Outdoor Electric Deicing and Snow-Melting
426-27
Fixtures and Lighting Equipment
410-17
410-18
410-19
410-21
410-105(b)
Flexible Cords and Cables
400-22
400-23
ARTICLE 250 - GROUNDING
70-105
Floating Buildings
553-8
553-10
553-11
Grounding-type Receptacles, Adapters, Cord Connectors,
and Attachment Plugs
410-58
Hazardous (Classified) Locations
500-517
Health Care Facilities
517
Induction and Dielectric Heating Equipment
665
Industrial Machinery
670
Intrinsically Safe Systems
504-50
I
Lighting Fixtures, Lampholders, Lamps,
and Receptacles
410
Marinas and Boatyards
555-7
Mobile Homes and Mobile Home Parks
550
Motion Picture and Television Studios and Similar
Locations
530-20
530-66
Motors, Motor Circuits, and Controllers
430
Outlet, Device, Pull and Junction Boxes, Conduit Bodies
and Fittings
370-4
370-25
Over 600 Volts, Nominal-General
710-4(b)(1)
Panelboards
384-20
Pipe Organs
650
Radio and Television Equipment
810
Receptacles and Cord Connectors
210-7
Recreational Vehicles and Recreational Vehicle Parks
551
Services
230
Service Equipment
230-63
Solar Photovoltaic Systems
690-41
690-42
690-43
690-44
Sound-Recording and Similar Equipment
640-4
Swimming Pools, Fountains, and Similar Installations
680
Switchboards and Panelboards
384-3(d)
384-11
Switches
380-12
Theaters, Audience Areas of Motion Picture and
Television Studios, and Similar Locations
520-81
Transformers and Transformer Vaults
450-10
Use and Identification of Grounded Conductors
200
X-Ray Equipment
660
517-77
B. Circuit and System Grounding
250-3. Direct-Current Systems.
(a) Two-Wire Direct-Current Systems. Two-wire dc systems supplying
premises wiring shall be grounded.
70-106
NATIONAL ELECTRICAL CODE
Exception No. 1: A system equipped with a ground detector and supplying only industrial equipment in limited areas.
Exception No. 2: A system operating at 50 volts or less between conductors.
Exception No. 3: A system operating at over 300 volts between conductors.
Exception No. 4: A rectifier-derived dc system supplied from an ac system complying with Section 250-5.
Exception No. 5: DC fire protective signaling circuits having a maximum current of 0.030 amperes as specified in Article 760, Part C.
(b) Three-Wire Direct-Current Systems. The neutral conductor of all
3-wire dc systems supplying premises wiring shall be grounded.
250-5. Alternating-Current Circuits and Systems to Be Grounded. AC
circuits and systems shall be grounded as provided for in (a), (b), (c), or (d)
below. Other circuits and systems shall be permitted to be grounded.
(FPN): An example of a system permitted to be grounded is a corner-grounded
delta transformer connection. See Section 250-25(4) for conductor to be grounded.
(a) Alternating-Current Circuits of Less than 50 Volts. AC circuits of
less than 50 volts shall be grounded under any of the following conditions:
(1) Where supplied by transformers if the transformer supply system
exceeds 150 volts to ground.
(2) Where supplied by transformers if the transformer supply system is
ungrounded.
(3) Where installed as overhead conductors outside of buildings.
(b) Alternating-Current Systems of 50 Volts to 1000 Volts. AC systems
of 50 volts to 1000 volts supplying premises wiring and premises wiring
systems shall be grounded under any of the following conditions:
(1) Where the system can be so grounded that the maximum voltage to
ground on the ungrounded conductors does not exceed 150 volts.
(2) Where the system is 3-phase, 4-wire wye connected in which the
neutral is used as a circuit conductor.
(3) Where the system is 3-phase, 4-wire delta connected in which the
midpoint of one phase winding is used as a circuit conductor.
(4) Where a grounded service conductor is uninsulated in accordance
with the exceptions to Sections 230-22, 230-30, and 230-41.
Exception No. 1: Electric systems used exclusively to supply industrial
electric furnaces for melting, refining, tempering, and the like.
Exception No. 2: Separately derived systems used exclusively for rectifiers supplying only adjustable speed industrial drives.
Exception No. 3: Separately derived systems supplied by transformers
that have a primary voltage rating less than 1000 volts, provided that all of
the following conditions are met:
a. The system is used exclusively for control circuits.
b. The conditions of maintenance and supervision assure that only
qualified persons will service the installation.
ARTICLE 250 - GROUNDING
70-107
c. Continuity of control power is required.
d. Ground detectors are installed on the control system.
Exception No. 4: Isolated systems as permitted or required in Articles
517 and 668.
(FPN): The proper use of suitable ground detectors on ungrounded systems can
provide additional protection.
Exception No. 5: High-impedance grounded neutral systems in which a
grounding impedance, usually a resistor, limits the ground-fault current to
a low value. High-impedance grounded neutral systems shall be permitted
for 3-phase ac systems of 480 volts to 1000 volts where all of the following
conditions are met:
a. The conditions of maintenance and supervision assure that only
qualified persons will service the installation.
b. Continuity of power is required.
c. Ground detectors are installed on the system.
d. Line-to-neutral loads are not served.
(c) Alternating-Current Systems of 1 kV and Over. AC systems supplying mobile or portable equipment shall be grounded as specified in Section
250-154. Where supplying other than portable equipment, such systems
shall be permitted to be grounded. Where such systems are grounded, they
shall comply with the applicable provisions of this article.
(d) Separately Derived Systems. A premises wiring system whose
power is derived from generator, transformer, or converter windings and
has no direct electrical connection, including a solidly connected grounded
circuit conductor, to supply conductors originating in another system, if
required to be grounded as in (a) or (b) above, shall be grounded as specified in Section 250-26.
(FPN No. 1): An alternate alternating-current power source such as an on-site
generator is not a separately derived system if the neutral is solidly interconnected
to a service-supplied system neutral.
(FPN No. 2): For systems that are not separately derived and are not required
to be grounded as specified in Section 250-26, see Section 445-5 for minimum size of
conductors that must carry fault current.
250-6. Portable and Vehicle-Mounted Generators.
(a) Portable Generators. Under the following conditions, the frame of a
portable generator shall not be required to be grounded and shall be permitted to serve as the grounding electrode for a system supplied by the
generator:
(1) The generator supplies only equipment mounted on the generator
or cord- and plug-connected equipment through receptacles mounted on
the generator, or both, and
(2) The noncurrent-carrying metal parts of equipment and the equipment grounding conductor terminals of the receptacles are bonded to the
generator frame.
(b) Vehicle-Mounted Generators. Under the following conditions, the
frame of a vehicle shall be permitted to serve as the grounding electrode for
a system supplied by a generator located on the vehicle:
70-108
NATIONAL ELECTRICAL CODE
(1) The frame of the generator is bonded to the vehicle frame, and
(2) The generator supplies only equipment located on the vehicle or
cord- and plug-connected equipment through receptacles mounted on the
vehicle or both equipment located on the vehicle and cord- and plugconnected equipment through receptacles mounted on the vehicle or on
the generator, and
(3) The noncurrent-carrying metal parts of equipment and the equipment grounding conductor terminals of the receptacles are bonded to the
generator frame, and
(4) The system complies with all other provisions of this article.
(c) Neutral Conductor Bonding. A neutral conductor shall be bonded to
the generator frame where the generator is a component of a separately
derived system. The bonding of any conductor other than a neutral within
the generator to its frame shall not be required.
(FPN): For grounding of portable generators supplying fixed wiring systems,
see Section 250-5(d).
250-7. Circuits Not to Be Grounded. The following circuits shall not be
grounded:
(a) Cranes. Circuits for electric cranes operating over combustible
fibers in Class III locations, as provided in Section 503-13.
(b) Health Care Facilities. Circuits as provided in Article 517.
(c) Electrolytic Cells. Circuits as provided in Article 668.
C. Location of System Grounding Connections
250-21. Objectionable Current over Grounding Conductors.
(a) Arrangement to Prevent Objectionable Current. The grounding of
electric systems, circuit conductors, surge arresters, and conductive
noncurrent-carrying materials and equipment shall be installed and
arranged in a manner that will prevent an objectionable flow of current
over the grounding conductors or grounding paths.
(b) Alterations to Stop Objectionable Current. If the use of multiple
grounding connections results in an objectionable flow of current, one or
more of the following alterations shall be permitted to be made, provided
that the requirements of Section 250-51 are met:
(1) Discontinue one or more but not all of such grounding connections.
(2) Change the locations of the grounding connections.
(3) Interrupt the continuity of the conductor or conductive path interconnecting the grounding connections.
(4) Take other suitable remedial action satisfactory to the authority
having jurisdiction.
ARTICLE 250 - GROUNDING
70-109
(c) Temporary Currents Not Classified as Objectionable Currents.
Temporary currents resulting from accidental conditions, such as groundfault currents, that occur only while the grounding conductors are performing their intended protective functions shall not be classified as objectionable current for the purposes specified in (a) and (b) above.
(d) Limitations to Permissible Alterations. The provisions of this section shall not be considered as permitting electronic equipment being operated on ac systems or branch circuits that are not grounded as required by
this article. Currents that introduce noise or data errors in electronic equipment shall not be considered the objectionable currents addressed in this
section.
250-22. Point of Connection for Direct-Current Systems. DC systems to
be grounded shall have the grounding connection made at one or more
supply stations. A grounding connection shall not be made at individual
services nor at any point on premises wiring.
Exception: Where the dc system source is located on the premises, a
grounding connection shall be made either (1) at the source or the first
system disconnecting means or overcurrent device, or (2) by another
means that accomplishes equivalent system protection and that utilizes
equipment listed and identified for the use.
250-23. Grounding Service-Supplied Alternating-Current Systems.
(a) System Grounding Connections. A premises wiring system that is
supplied by an ac service and is required to be grounded by Section 250-5
shall have at each service a grounding electrode conductor connected to a
grounding electrode that complies with Part H of Article 250. The grounding electrode conductor shall be connected to the grounded service conductor at any accessible point from the load end of the service drop or service lateral to and including the terminal or bus to which the grounded
service conductor is connected at the service disconnecting means. Where
the transformer supplying the service is located outside the building, at
least one additional grounding connection shall be made from the grounded
service conductor to a grounding electrode, either at the transformer or
elsewhere outside the building. A grounding connection shall not be made
to any grounded circuit conductor on the load side of the service disconnecting means.
(FPN): See definition of "Service Drop" and "Service Lateral"; also Section
230-21.
Exception No. 1: A grounding electrode conductor shall be connected
to the grounded conductor of a separately derived system in accordance
with the provisions of Section 250-26(b).
Exception No. 2: A grounding conductor connection shall be made at
each separate building where required by Section 250-24.
Exception No. 3: For ranges, counter-mounted cooking units, wallmounted ovens, clothes dryers, and meter enclosures as permitted by Section 250-61.
70-110
NATIONAL ELECTRICAL CODE
Exception No. 4: For services that are dual fed (double ended) in a
common enclosure or grouped together in separate enclosures and
employing a secondary tie, a single grounding electrode connection to the
tie point of the grounded circuit conductors from each power source shall
be permitted.
Exception No. 5: Where the main bonding jumper specified in Sections
250-53(b) and 250-79 is a wire or busbar, and is installed from the neutral
bar or bus to the equipment grounding terminal bar or bus in the service
equipment, the grounding electrode conductor shall be permitted to be
connected to the equipment grounding terminal bar or bus to which the
main bonding jumper is connected.
Exception No. 6: As covered in Section 250-27 for high-impedance
grounded neutral systems grounding connection requirements.
(b) Grounded Conductor Brought to Service Equipment. Where an ac
system operating at less than 1000 volts is grounded at any point, the
grounded conductor shall be run to each service disconnecting means and
shall be bonded to each disconnecting means enclosure. This conductor
shall be routed with the phase conductors and shall not be smaller than the
required grounding electrode conductor specified in Table 250-94, and, in
addition, for service-entrance phase conductors larger than 1100 kcmil
copper or 1750 kcmil aluminum, the grounded conductor shall not be
smaller than 12½ percent of the area of the largest service-entrance phase
conductor. Where the service-entrance phase conductors are paralleled,
the size of the grounded conductor shall be based on the equivalent area
for parallel conductors as indicated in this section.
(FPN): See Section 310-4 for grounded conductors connected in parallel.
Exception No. 1: The grounded conductor shall not be required to be
larger than the largest ungrounded service-entrance phase conductor.
Exception No. 2: As covered in Section 250-27 for high-impedance
grounded neutral systems grounding connection requirements.
Exception No. 3: Where more than one service disconnecting means
are located in an assembly listed for use as service equipment, one
grounded conductor shall be required to be run to the assembly, and it
shall be bonded to the assembly enclosure.
250-24. Two or More Buildings or Structures Supplied from a Common
Service.
(a) Grounded Systems. Where two or more buildings or structures are
supplied from a common service, the grounded system in each building or
structure shall have a grounding electrode as described in Part H connected to the metal enclosure of the building disconnecting means and to
the ac system grounded circuit conductor on the supply side of the building or structure disconnecting means.
Exception No. 1: A grounding electrode at separate buildings or structures shall not be required where only one branch circuit is supplied and
there is no equipment in the building or structure that requires grounding.
ARTICLE 250 - GROUNDING
70-111
Exception No. 2: A grounded circuit conductor connection to the
grounding electrode shall not be required at a separate building or structure if an equipment grounding conductor is run with the circuit conductors for grounding any noncurrent-carrying equipment, interior metal piping systems, and building or structural metal frames, and the equipment
grounding conductor is bonded at a separate building or structure disconnecting means to existing grounding electrodes described in Part H.
Where there are no existing electrodes, a grounding electrode meeting the
requirements of Part H shall be installed where the building or structure
supplies more than one branch circuit. Where livestock is housed, that
portion of the equipment grounding conductor run underground to the disconnecting means shall be insulated or covered copper.
(FPN): See Section 547-8(a), Exception for special grounding requirements for
agricultural buildings.
(b) Ungrounded Systems. Where two or more buildings or structures
are supplied by a common service from an ungrounded system, each building or structure shall have a grounding electrode as described in Part H
connected to the metal enclosure of the building or structure disconnecting
means.
Exception No. 1: A grounding electrode at separate buildings or
structures shall not be required where only one branch circuit is supplied and there is no equipment in the building or structure that requires
grounding.
Exception No. 2: A grounding electrode and grounding electrode conductor connection to the metal enclosure of the building or structure disconnecting means shall not be required, provided all of the following conditions are met:
a. An equipment grounding conductor is run with the circuit conductors to the building or structure disconnecting means for grounding
any noncurrent-carrying equipment, interior metal piping systems, and
building or structural metal frames.
b. There are no existing grounding electrodes as described in Part H.
c. The building or structure supplies only one branch circuit.
d. Where livestock is housed, that portion of the equipment
grounding conductor run underground to the disconnecting means shall
be insulated or covered copper.
(FPN): See Section 547-8(a), Exception for special grounding requirements for
agricultural buildings.
(c) Disconnecting Means Located in Separate Building or Structure on
the Same Premises. Where one or more disconnecting means supply one
or more additional buildings or structures under single management, and
where these disconnecting means are located remote from those buildings
or structures in accordance with the provisions of Section 225-8(b), Exception Nos. 1 and 2 or Section 230-205(a), Exception, all of the following
conditions shall be met:
70-112
NATIONAL ELECTRICAL CODE
(1) The connection of the grounded circuit conductor to the grounding
electrode at a separate building or structure shall not be made;
(2) An equipment grounding conductor for grounding any noncurrentcarrying equipment, interior metal piping systems, and building or structural metal frames is run with the circuit conductors to a separate building
or structure and bonded to existing grounding electrodes described in Part
H, or, where there are no existing electrodes, a grounding electrode meeting the requirements of Part H shall be installed where a separate building
or structure supplies more than one branch circuit;
(3) Bonding the equipment grounding conductor to the grounding electrode at a separate building or structure shall be made in a junction box,
panelboard, or similar enclosure located immediately inside or outside the
separate building or structure.
Exception No. 1: A grounding electrode at a separate building or structure shall not be required where only one branch circuit is supplied and
there is no equipment in the building or structure that requires grounding.
Exception No. 2: Where livestock is housed, that portion of the equipment grounding conductor run underground to the disconnecting means
shall be insulated or covered copper.
(d) Grounding Conductor. The size of the grounding conductor to the
grounding electrode(s) shall not be less than given in Table 250-95, and the
I
installation shall be in accordance with Sections 250-92(a) and (b).
Exception No. 1: The grounding conductor shall not be required to be
larger than the largest ungrounded supply conductor.
Exception No. 2: Where connected to made electrodes as in Section
250-83(c) or (d), that portion of the grounding conductor that is the sole
connection between the electrode(s) and the grounded or grounding conductor or the metal enclosure of the building disconnecting means shall
not be required to be larger than No. 6 copper or No. 4 aluminum.
250-25. Conductor to Be Grounded - Alternating-Current Systems. For
ac premises wiring systems, the conductor to be grounded shall be as
specified in (1) through (5) below.
(1) Single-phase, 2-wire: one conductor.
(2) Single-phase, 3-wire: the neutral conductor.
(3) Multiphase systems having one wire common to all phases: the common conductor.
(4) Multiphase systems requiring one grounded phase: one phase
conductor.
(5) Multiphase systems in which one phase is used as in (2) above: the
neutral conductor.
Grounded conductors shall be identified by the means specified in