Regl. 5293, art. 250-24
Resolución 2535: adopta el Código Eléctrico Nacional, versión 1993. (Sustituye el Anejo A del Reglamento 4435)
Cite as Reglamento Núm. 5293, Art. 250-24
Exception No. 2: Service equipment shall be permitted to be installed in
or on a manufactured home, provided that all of the following conditions
are met:
a. The service equipment is completely installed by the manufacturer
of the structure.
b. The installation of the service equipment complies with Article 230.
C. Means are provided for the connection of a grounding electrode
conductor to the service equipment and routing it outside the structure.
(b) Rating. Mobile home service equipment shall be rated at not less
than 100 amperes, and provision shall be made for connecting a mobile
home feeder assembly by a permanent wiring method. Power outlets used
ARTICLE 550 - MOBILE HOMES AND MOBILE HOME PARKS
70-603
as mobile home service equipment shall also be permitted to contain receptacles rated up to 50 amperes with appropriate overcurrent protection.
Fifty-ampere receptacles shall conform to the configuration shown in Figure 550-5(c).
(FPN): Complete details on the 50-ampere attachment plug cap configuration
can be found in American National Standard Dimensions of Caps, Plugs and Receptacles, ANSI C73.17-1972.
(c) Additional Outside Electrical Equipment. Mobile home service
equipment shall also contain a means for connecting a mobile home accessory building or structure or additional electrical equipment located outside
a mobile home by a fixed wiring method.
(d) Additional Receptacles. Additional receptacles shall be permitted
for connection of electrical equipment located outside the mobile home,
and all such 125-volt, single-phase, 15- and 20-ampere receptacles shall be
protected by a listed ground-fault circuit-interrupter protection.
(e) Mounting Height. Outdoor mobile home disconnecting means shall
be installed so the bottom of the enclosure containing the disconnecting
means is not less than 2 feet (610 mm) above finished grade or working
platform. The disconnecting means shall be so installed that the center of
the grip of the operating handle, when in its highest position, will not be
more than 6½ feet (1.98 m) above the finished grade or working platform.
(f) Grounded. Each mobile home service equipment shall be grounded
in accordance with Article 250 for service equipment.
(g) Marking. Where a 125/250-volt receptacle is used in mobile home
service equipment, the service equipment shall be marked as follows:
"Turn disconnecting switch or circuit breaker off before inserting or
removing plug. Plug must be fully inserted or removed."
The marking shall be located on the service equipment adjacent to the
receptacle outlet.
550-24. Feeder.
(a) Feeder Conductors. Mobile home feeder conductors shall consist of
either a listed cord, factory-installed in accordance with Section 550-5(b),
or a permanently installed feeder consisting of four, insulated, color-coded
conductors that shall be identified by the factory or field marking of the
conductors in compliance with Section 310-12. Equipment grounding conductors shall not be identified by stripping the insulation.
Exception: A mobile home feeder located between service equipment
and a mobile home disconnecting means as covered in Section 550-23(a),
Exception No. 1 shall be permitted to omit the equipment grounding conductor where the grounded circuit conductor is grounded at the disconnecting means as permitted in Section 250-24(a).
(b) Adequate Feeder Capacity. Mobile home lot feeder circuit conductors shall have adequate capacity for the loads supplied and shall be rated
at not less than 100 amperes at 120/240 volts.
70-604
NATIONAL ELECTRICAL CODE