Regl. 5293, art. 250-42-373 dup2
CABINETS, CUTOUT BOXES, AND
Cite as Reglamento Núm. 5293, Art. 250-42-373 dup2
METER SOCKET ENCLOSURES
373-1. Scope. This article covers the installation and construction specifications of cabinets, cutout boxes, and meter socket enclosures.
A. Installation
373-2. Damp, Wet, or Hazardous (Classified) Locations.
(a) Damp and Wet Locations. In damp or wet locations, cabinets and
cutout boxes of the surface type shall be so placed or equipped as to prevent moisture or water from entering and accumulating within the cabinet
or cutout box, and shall be mounted so there is at least ¹/₄-inch (6.35-mm)
air space between the enclosure and the wall or other supporting surface.
Cabinets or cutout boxes installed in wet locations shall be weatherproof.
(FPN): For protection against corrosion, see Section 300-6.
(b) Hazardous (Classified) Locations. Installations in hazardous (classified) locations shall conform to Articles 500 through 517.
373-3. Position in Wall. In walls of concrete, tile, or other noncombustible material, cabinets shall be so installed that the front edge of the cabinet
will not set back of the finished surface more than ¼ inch (6.35 mm). In
walls constructed of wood or other combustible material, cabinets shall be
flush with the finished surface or project therefrom.
373-4. Unused Openings. Unused openings in cabinet or cutout boxes
shall be effectively closed to afford protection substantially equivalent to
that of the wall of the cabinet or cutout box. Where metal plugs or plates
are used with nonmetallic cabinets or cutout boxes, they shall be recessed
at least ¼ inch (6.35 mm) from the outer surface.
70-290
NATIONAL ELECTRICAL CODE
373-5. Conductors Entering Cabinets or Cutout Boxes. Conductors
entering cabinets or cutout boxes shall be protected from abrasion and
shall comply with (a) through (c) below.
(a) Openings to Be Closed. Openings through which conductors enter
shall be adequately closed.
(b) Metal Cabinets and Cutout Boxes. Where metal cabinets or cutout
boxes are installed with open wiring or concealed knob-and-tube wiring,
conductors shall enter through insulating bushings or, in dry locations,
through flexible tubing extending from the last insulating support and
firmly secured to the cabinet or cutout box.
(c) Cables. Where cable is used, each cable shall be secured to the cabinet or cutout box.
373-6. Deflection of Conductors. Conductors at terminals or conductors
entering or leaving cabinets or cutout boxes and the like shall comply with
(a) through (c) below.
(a) Width of Wiring Gutters. Conductors shall not be deflected within
a cabinet or cutout box unless a gutter having a width in accordance
with Table 373-6(a) is provided. Conductors in parallel in accordance
with Section 310-4 shall be judged on the basis of the number of conductors in parallel.
Table 373-6(a). Minimum Wire-Bending Space at Terminals and Minimum
Width of Wiring Gutters in Inches
Wires per Terminal
AWG or
Circular-Mil
Size of Wire
1
2
3
4
5
14-10
Not Specified
-
-
-
-
8-6
1½
I
-
-
-
4-3
2
-
-
-
-
2
2½
-
-
-
-
1
3
-
-
|
-
1/0-2/0
3½
5
7
-
-
3/0-4/0
4
6
8
-
-
250 kcmil
4½
6
8
10
-
300-350 kcmil
5
8
10
12
----
400-500 kcmil
6
8
10
12
14
600-700 kcmil
8
10
12
14
16
750-900 kcmil
8
12
14
16
18
1000-1250 kcmil
10
—
-
|
I
1500-2000 kcmil
12
-
-
-
-
For SI units: one inch = 25.4 millimeters.
Bending space at terminals shall be measured in a straight line from the end of the lug or
wire connector (in the direction that the wire leaves the terminal) to the wall, barrier, or
obstruction.