Regl. 5293, art. 250-42-373 dup3
CABINETS, CUTOUT BOXES, & METER SOCKETS 70-291
Cite as Reglamento Núm. 5293, Art. 250-42-373 dup3
(b) Wire Bending Space at Terminals. Wire bending space at each terminal shall be provided in accordance with (1) or (2) below.
(1) Table 373-6(a) shall apply where the conductor does not enter or
leave the enclosure through the wall opposite its terminal.
Exception No. 1: A conductor shall be permitted to enter or leave an
enclosure through the wall opposite its terminal provided the conductor
enters or leaves the enclosure where the gutter joins an adjacent gutter
that has a width that conforms to Table 373-6(b) for that conductor.
Exception No. 2: A conductor not larger than 350 kcmil shall be permitted to enter or leave an enclosure containing only a meter socket(s)
through the wall opposite its terminal, provided the terminal is a lay-in
type where either:
a. The terminal is directly facing the enclosure wall and offset is not
greater than 50 percent of the bending space specified in Table 373-6(a),
or
b. The terminal is directed toward the opening in the enclosure and is
within a 45-degree angle of directly facing the enclosure wall.
(FPN): Offset is the distance measured along the enclosure wall from the axis
of the centerline of the terminal to a line passing through the center of the opening
in the enclosure.
(2) Table 373-6(b) shall apply where the conductor enters or leaves the
enclosure through the wall opposite its terminal.
(c) Insulated Fittings. Where ungrounded conductors of No. 4 or larger
enter a raceway in a cabinet, pull box, junction box, or auxiliary gutter, the
conductors shall be protected by a substantial fitting providing a smoothly
rounded insulating surface, unless the conductors are separated from the
raceway fitting by substantial insulating material securely fastened in place.
Exception: Where threaded hubs or bosses that are an integral part of
an enclosure provide a smoothly rounded or flared entry for conductors.
Conduit bushings constructed wholly of insulating material shall not be
used to secure a raceway. The insulating fitting or insulating material shall
have a temperature rating not less than the insulation temperature rating of
the installed conductors.
373-7. Space in Enclosures. Cabinets and cutout boxes shall have sufficient space to accommodate all conductors installed in them without
crowding.
373-8. Enclosures for Switches or Overcurrent Devices. Enclosures for
switches or overcurrent devices shall not be used as junction boxes, auxiliary gutters, or raceways for conductors feeding through or tapping off to
other switches or overcurrent devices.
Exception: Where adequate space is provided so that the conductors do
not fill the wiring space at any cross section to more than 40 percent of the
cross-sectional area of the space, and so that the conductors, splices, and
taps do not fill the wiring space at any cross section to more than 75 percent of the cross-sectional area of the space.
70-292
NATIONAL ELECTRICAL CODE
Table 373-6(b). Minimum Wire-Bending Space at Terminals for
pecified
-
-
-
8
1½
-
-
-
6
2
-
-
-
4
3
-
-
-
3
3
-
-
-
2
3½
-
-
-
1
4½
-
-
-
1/0
5½
5½
7
-
2/0
6
6
7½
-
3/0
6½
(1/2)
6½
(1/2)
8
4/0
7
(1)
7½
(1½)
8½
(1/2)
-
250
8½
(2)
8½
(2)
9
(1)
10
300
10
(3)
10
(2)
11
(1)
12
350
12
(3)
12
(3)
13
(3)
14
(2)
400
13
(3)
13
(3)
14
(3)
15
(3)
500
14
(3)
14
(3)
15
(3)
16
(3)
600
15
(3)
16
(3)
18
(3)
19
(3)
700
16
(3)
18
(3)
20
(3)
22
(3)
750
17
(3)
19
(3)
22
(3)
24
(3)
800
18
20
22
24
900
19
22
24
24
1000
20
-
-
-
1250
22
-
-
-
1500
24
-
-
-
1750
24
-
-
-
2000
24
-
-
-
For SI units: one inch = 25.4 millimeters.
Bending space at terminals shall be measured in a straight line from the end of the lug or
wire connector in a direction perpendicular to the enclosure wall.
For removable and lay-in wire terminals intended for only one wire, bending space shall
be permitted to be reduced by the number of inches shown in parentheses.
373-9. Side or Back Wiring Spaces or Gutters. Cabinets and cutout
boxes shall be provided with back wiring spaces, gutters, or wiring compartments as required by Section 373-11(c) and (d).
B. Construction Specifications
373-10. Material. Cabinets and cutout boxes shall comply with (a)
through (c) below.
(a) Metal Cabinets and Cutout Boxes. Metal cabinets and cutout boxes
shall be protected both inside and outside against corrosion.