Regl. 5293, art. 250-42-373 dup4
CABINETS, CUTOUT BOXES, & METER SOCKETS 70-293
Cite as Reglamento Núm. 5293, Art. 250-42-373 dup4
(FPN): For protection against corrosion, see Section 300-6.
(b) Strength. The design and construction of cabinets and cutout boxes
shall be such as to secure ample strength and rigidity. If constructed of
sheet steel, the metal thickness shall not be less than 0.053 inch (1.35 mm)
uncoated.
(c) Nonmetallic Cabinets. Nonmetallic cabinets shall be listed or they
shall be submitted for approval prior to installation.
373-11. Spacing. The spacing within cabinets and cutout boxes shall
comply with (a) through (d) below.
(a) General. Spacing within cabinets and cutout boxes shall be sufficient
to provide ample room for the distribution of wires and cables placed in
them, and for a separation between metal parts of devices and apparatus
mounted within them as follows:
(1) Base. Other than at points of support, there shall be an air space
of at least ¹/₁₆ inch (1.59 mm) between the base of the device and the wall
of any metal cabinet or cutout box in which the device is mounted.
(2) Doors. There shall be an air space of at least 1 inch (25.4 mm)
between any live metal part, including live metal parts of enclosed fuses,
and the door.
Exception: Where the door is lined with an approved insulating material
or is of a thickness of metal not less than 0.093 inches (2.36 mm) uncoated,
the air space shall not be less than ¹/₂ inch (12.7 mm).
(3) Live Parts. There shall be an air space of at least ½ inch (12.7 mm)
between the walls, back, gutter partition, if of metal, or door of any cabinet or cutout box and the nearest exposed current-carrying part of devices
mounted within the cabinet where the voltage does not exceed 250. This
spacing shall be increased to at least 1 inch (25.4 mm) for voltages 251 to
600, nominal.
Exception: As permitted in (2) above.
(b) Switch Clearance. Cabinets and cutout boxes shall be deep enough
to allow the closing of the doors when 30-ampere branch-circuit panelboard switches are in any position; when combination cutout switches are
in any position; or when other single-throw switches are opened as far as
their construction will permit.
(c) Wiring Space. Cabinets and cutout boxes that contain devices or
apparatus connected within the cabinet or box to more than eight conductors, including those of branch circuits, meter loops, feeder circuits, power
I
circuits, and similar circuits, but not including the supply circuit or a continuation thereof, shall have back-wiring spaces or one or more side-wiring
spaces, side gutters, or wiring compartments.
(d) Wiring Space - Enclosure. Side-wiring spaces, side gutters, or
side-wiring compartments of cabinets and cutout boxes shall be made tight
enclosures by means of covers, barriers, or partitions extending from the
bases of the devices, contained in the cabinet to the door, frame, or sides
of the cabinet.
70-294
NATIONAL ELECTRICAL CODE
Exception: Where the enclosure contains only those conductors that are
led from the cabinet at points directly opposite their terminal connections
to devices within the cabinet.
Partially enclosed back-wiring spaces shall be provided with covers to
complete the enclosure. Wiring spaces that are required by (c) above, and
that are exposed when doors are open, shall be provided with covers to
complete the enclosure. Where adequate space is provided for feedthrough conductors and for splices as required in Section 373-8, Exception,
additional barriers shall not be required.