Regl. 5293, art. 250-42-374
AUXILIARY GUTTERS
Cite as Reglamento Núm. 5293, Art. 250-42-374
374-1. Use. Auxiliary gutters shall be permitted to supplement wiring
spaces at meter centers, distribution centers, switchboards, and similar
points of wiring systems and may enclose conductors or busbars but shall
not be used to enclose switches, overcurrent devices, appliances, or other
similar equipment.
374-2. Extension Beyond Equipment. An auxiliary gutter shall not
extend a greater distance than 30 feet (9.14 m) beyond the equipment that
it supplements.
Exception: As provided in Section 620-35 for elevators.
(FPN): For wireways, see Article 362. For busways, see Article 364.
374-3. Supports. Gutters shall be supported throughout their entire
length at intervals not exceeding 5 feet (1.52 m).
374-4. Covers. Covers shall be securely fastened to the gutter.
374-5. Number of Conductors. Auxiliary gutters shall not contain more
than thirty current-carrying conductors at any cross section. The sum of
the cross-sectional areas of all contained conductors at any cross section
of an auxiliary gutter shall not exceed 20 percent of the interior crosssectional area of the auxiliary gutter.
Exception No. 1: As provided in Section 620-35 for elevators.
Exception No. 2: Conductors for signaling circuits or controller conductors between a motor and its starter and used only for starting duty shall
not be considered as current-carrying conductors.
Exception No. 3: Where the correction factors specified in Article 310,
Note 8(a) of Notes to Ampacity Tables of 0 to 2000 Volts are applied, there
shall be no limit on the number of current-carrying conductors, but the
sum of the cross-sectional area of all contained conductors at any cross
section of the auxiliary gutter shall not exceed 20 percent of the interior
cross-sectional area of the auxiliary gutter.
(FPN): For conductor cross-sectional area, see Tables 5, 5A, 6, and 8 and the
applicable Notes to Tables at the beginning of Chapter 9.