Regl. 5293, art. 250-45-200
Resolución 2535: adopta el Código Eléctrico Nacional, versión 1993. (Sustituye el Anejo A del Reglamento 4435)
Cite as Reglamento Núm. 5293, Art. 250-45-200
ARTICLE 250 - GROUNDING
70-113
250-26. Grounding Separately Derived Alternating-Current Systems. A
separately derived ac system that is required to be grounded by Section
250-5 shall be grounded as specified in (a) through (d) below.
(a) Bonding Jumper. A bonding jumper, sized in accordance with Section 250-79(d) for the derived phase conductors, shall be used to connect
the equipment grounding conductors of the derived system to the grounded
conductor. Except as permitted by Exception No. 4 or No. 5 of Section
250-23(a), this connection shall be made at any point on the separately
derived system from the source to the first system disconnecting means or
overcurrent device; or it shall be made at the source of a separately derived
system that has no disconnecting means or overcurrent devices.
Exception No. 1: The size of the bonding jumper for a system that supplies a Class 1, Class 2, or Class 3 circuit, and is derived from a transformer rated not more than 1000 volt-amperes, shall not be smaller than
the derived phase conductors and shall not be smaller than No. 14 copper
or No. 12 aluminum.
Exception No. 2: As covered in Section 250-27 and Exception No. 5 for