Regl. 5293, art. 250-5(b)
for high-impedance grounded neutral systems grounding
Cite as Reglamento Núm. 5293, Art. 250-5(b)
connection requirements.
(b) Grounding Electrode Conductor. A grounding electrode conductor,
sized in accordance with Section 250-94 for the derived phase conductors,
shall be used to connect the grounded conductor of the derived system to
the grounding electrode as specified in (c) below. Except as permitted by
Exception No. 4 of Section 250-23(a), this connection shall be made at any
point on the separately derived system from the source to the first system
disconnecting means or overcurrent device; or it shall be made at the
source of a separately derived system that has no disconnecting means or
overcurrent devices.
Exception No. 1: A grounding electrode conductor shall not be required
for a system that supplies a Class 1, Class 2, or Class 3 circuit, and is
derived from a transformer rated not more than 1000 volt-amperes, provided the system grounded conductor is bonded to the transformer frame
or enclosure by a jumper sized in accordance with Section 250-26, Exception No. 1 for (a) above, and the transformer frame or enclosure is
grounded by one of the means specified in Section 250-57.
Exception No. 2: As covered in Section 250-27 and Exception No. 5 for