Regl. 5293, art. 250-5(b) dup2
for high-impedance grounded neutral systems grounding
Cite as Reglamento Núm. 5293, Art. 250-5(b) dup2
connection requirements.
(c) Grounding Electrode. The grounding electrode shall be as near as
practicable to and preferably in the same area as the grounding conductor
connection to the system. The grounding electrode shall be (1) the nearest
available effectively grounded structural metal member of the structure; or
(2) the nearest available effectively grounded metal water pipe; or (3) other
electrodes as specified in Sections 250-81 and 250-83 where electrodes
specified by (1) or (2) above are not available.
(d) Grounding Methods. In all other respects, grounding methods shall
comply with requirements prescribed in other parts of this Code.
70-114
NATIONAL ELECTRICAL CODE
250-27. High-Impedance Grounded Neutral System Connections. Highimpedance grounded neutral systems as permitted in Exception No. 5 of