SURGE ARRESTERS
Cite as Reglamento Núm. 5293, Art. 250-8-280
70-139
(b) Exposed Noncurrent-Carrying Metal Parts. Exposed noncurrentcarrying metal parts of portable or mobile equipment shall be connected by
an equipment grounding conductor to the point at which the system neutral impedance is grounded.
(c) Ground-Fault Current. The voltage developed between the portable
or mobile equipment frame and ground by the flow of maximum groundfault current shall not exceed 100 volts.
(d) Ground-Fault Detection and Relaying. Ground-fault detection and
relaying shall be provided to automatically deenergize any high-voltage
system component that has developed a ground fault. The continuity of the
equipment grounding conductor shall be continuously monitored so as to
deenergize automatically the high-voltage feeder to the portable or mobile
equipment upon loss of continuity of the equipment grounding conductor.
(e) Isolation. The grounding electrode to which the portable or mobile
equipment system neutral impedance is connected shall be isolated from
and separated in the ground by at least 20 feet (6.1 m) from any other system or equipment grounding electrode, and there shall be no direct connection between the grounding electrodes, such as buried pipe, fence, etc.
(f) Trailing Cable and Couplers. High-voltage trailing cable and couplers for interconnection of portable or mobile equipment shall meet the
requirements of Part C of Article 400 for cables and Section 710-45 for
couplers.
250-155. Grounding of Equipment. All noncurrent-carrying metal parts
of fixed, portable, and mobile equipment and associated fences, housings,
enclosures, and supporting structures shall be grounded.
Exception No. 1: Where isolated from ground and located so as to prevent any person who can make contact with ground from contacting such
metal parts when the equipment is energized.
Exception No. 2: Pole-mounted distribution apparatus as provided in