Regl. 5293, art. 250-8-2.58
NATIONAL ELECTRICAL CODE
Cite as Reglamento Núm. 5293, Art. 250-8-2.58
3½
3.548
9.90
3.07
3.96
5.25
5.44
2.97
3.96
3.76
3.47
4
4.026
12.72
3.94
5.09
6.74
7.00
3.82
5.09
4.83
4.45
5
5.047
20.00
6.20
8.00
10.60
11.00
6.00
8.00
7.60
7.00
6
6.065
28.89
8.96
11.56
15.31
15.89
8.67
11.56
10.98
10.11
Table 5. Dimensions of Rubber-Covered and Thermoplastic-Covered Conductors
Types****
Types
FEP, FEPB, FEPW,
RFH-2, RH,
Types
Types
TFE, PF, PFA,
Types
Types
RHH,***, RHW-2,
TF, THW+,
TFN, THHN,
PFAH, PGF, PTF,
XHHW, ZWH,
KF-1, KF-2,
RHW,* SF-2
TW, THHW
THWN
Z, ZF, ZFF
XHHW-2
KFF-1, KFF-2
Size
Approx.
Approx.
Approx.
Approx.
Approx.
Approx.
Approx.
Approx.
Approx.
Approx.
Approx.
Approx.
AWG
Diam.
Area
Diam.
Area
Diam.
Area
Diam.
Area
Diam.
Area
Diam.
Area
kcmil
Inches
Sq. In.
Inches
Sq. In.
Inches
Sq. In.
Inches
Sq. In.
Inches
Sq. In.
Inches
Sq. In.
Col.1
Col.2
Col. 3
Col. 4
Col. 5
Col. 6
Col. 7
Col. 8
Col. 9
Col. 10
Col. 11
Col. 12
Col. 13
18
.146
.0167
.106
.0088
.089
.0062
.081
.0052
.065
.0033
16
.158
.0196
.118
.0109
.100
.0079
.092
.0066
.070
.0038
14
30 mils
.171
.0230
.131
.0135
.105
.0087
.105
.105
.0087
.0087
.083
.0054
14
45 mils
.204*
.0327*
14
.162+
.0206+
129
.0131
12
30 mils
.188
.0278
.148
.0172
.122
.0117
121
.121
.0115
.0115
.102
.0082
12
45 mils
.221*
.0384*
12
.179+
.0252+
146
.0167
10
.242
.0460
.168
.0222
.153
.0184
.142
.142
.0158
.0158
.124
.0121
CHAPTER 9 AND EXAMPLES
10
.199+
.0311+
166
.0216
8
.328
.0845
.245
.0471
.218
.0373
.206
.186
.0333
.0272
8
.276+
.0598+
241
.0456
6
.397
.1238
.323
.0819
.257
.0519
.244
.302
.0468
.0716
.282
.0625
4
.452
.1605
.372
.1087
.328
.0845
.292
.350
.0670
.0962
.328
.0845
3
.481
1817
.401
.1263
.356
.0995
.320
.378
.0804
.1122
.356
.0995
2
.513
.2067
.433
.1473
.388
.1182
.352
.410
.0973
.1320
.388
.1182
1
.588
.2715
.508
.2027
.450
.1590
.420
.1385
.450
.1590
1/0
.629
.3107
.549
.2367
.491
.1893
.462
.1676
.491
.1893
2/0
.675
.3578
.595
.2781
.537
.2265
.498
.1948
.537
.2265
3/0
.727
.4151
.647
.3288
.588
.2715
.560
.2463
.588
.2715
70-825
4/0
.785
.4840
.705
.3904
.646
.3278
.618
.3000
.646
.3278
Table 5. (Continued)
Types****
Types
FEP, FEPB, FEPW,
70-826
RFH-2, RH,
Types
Types
TFE, PF, PFA,
Types
RHH, RHW-2,
TF, THW+,
TFN,
PFAH, PGF, PTF,
XHHW, ZWH,
RHW,* SF-2
TW, THHW
THHN, THWN
Z, ZF, ZFF
XHHW-2
Size
Approx.
Approx.
Approx.
Approx.
Approx.
Approx.
Approx.
Approx.
Approx.
Approx.
AWG
Diam.
Area
Diam.
Area
Diam.
Area
Diam.
Area
Diam.
Area
kcmil
Inches
Sq. In.
Inches
Sq. In.
Inches
Sq. In.
Inches
Sq. In.
Inches
Sq. In.
Col.1
Col.2
Col. 3
Col. 4
Col. 5
Col. 6
Col. 7
Col. 8
Col. 9
Col. 10
Col. 11
250
.868
.5917
.788
.4877
.716
.4026
.716
.4026
300
.933
.6837
.843
.5581
.771
.4669
.771
.4669
350
.985
.7620
.895
.6291
.822
.5307
.822
.5307
400
1.032
.8365
.942
.6969
.869
.5931
.869
.5931
500
1.119
.9834
1.029
.8316
.955
.7163
.955
.7163
600
1.233
1.1940
1.143
1.0261
1.058
.8791
1.073
.9043
700
1.304
1.3355
1.214
1.1575
1.129
1.0011
1.145
1.0297
750
1.339
1.4082
1.249
1.2252
1.163
1.0623
1.180
1.0936
800
1.372
1.4784
1.282
1.2908
1.196
1.1234
1.210
1.1499
NATIONAL ELECTRICAL CODE
900
1.435
1.6173
1.345
1.4208
1.259
1.2449
1.270
1.2668
1000
1.494
1.7530
1.404
1.5482
1.317
1.3623
1.330
1.3893
1250
1.676
2.2062
1.577
1.9532
1.500
1.7671
1500
1.801
2.5475
1.702
2.2751
1.620
2.0612
1750
1.916
2.8832
1.817
2.5930
1.740
2.3779
2000
2.021
3.2079
1.922
2.9013
1.840
2.6590
* The dimensions of Types RHH and RHW with outer covering.
+ Dimensions of THW in sizes No. 14 through No. 8. Nos. 6 THW and larger are the same dimension as TW.
Dimensions of RHH and RHW without outer coverings are the same as THW No. 18 through No. 10, solid; Nos. 8 and larger, stranded.
****
In Columns 8 and 9, the values shown for size Nos. 1 through 4/0 are for TFE and Z only. The right-hand values in Columns 8 and 9 are for
FEPB, Z, ZF, and ZFF only.
++ No. 14 through No. 2.
Table 5A. Compact Aluminum Building Wire Nominal Dimensions* and Areas
Bare Conductor
Types THW and THHW
Type THHN
Type XHHW
Size
Number
Approx.
Approx.
Approx.
Approx.
Approx.
Approx.
Size
AWG or
of
Diam.
Diam.
Area
Diam.
Area
Diam.
Area
AWG or
kcmil
Strands
Inches
Inches
Sq. In.
Inches
Sq. In.
Inches
Sq. Inches
kcmil
8
7
.134
.255
.0510
-
-
.224
.0394
8
6
7
.169
.290
.0660
.240
.0452
.260
.0530
6
4
7
.213
.335
.0881
.305
.0730
.305
.0730
4
2
7
.268
.390
.1194
.360
.1017
.360
.1017
2
1
19
.299
.465
.1698
.415
.1352
.415
.1352
1
1/0
19
.336
.500
.1963
.450
.1590
.450
.1590
1/0
2/0
19
.376
.545
.2332
.495
.1924
.490
.1885
2/0
3/0
19
.423
.590
.2733
.540
.2290
.540
.2290
3/0
4/0
19
.475
.645
.3267
.595
.2780
.590
.2733
4/0
250
37
.520
.725
.4128
.670
.3525
.660
.3421
250
300
37
.570
.775
.4717
.720
.4071
.715
.4015
300
350
37
.616
.820
.5281
.770
.4656
.760
.4536
350
400
37
.659
.865
.5876
.815
.5216
.800
.5026
400
CHAPTER 9 - TABLES AND EXAMPLES
500
37
.736
.940
.6939
.885
.6151
.880
.6082
500
600
61
.813
1.050
.8659
.985
.7620
.980
.7542
600
700
61
.877
1.110
.9676
1.050
.8659
1.050
.8659
700
750
61
.908
1.150
1.0386
1.075
.9076
1.090
.9331
750
1000
61
1.060
1.285
1.2968
1.255
1.2370
1.230
1.1882
1000
* Dimensions are from industry sources.
70-827
Table 5B. Maximum Number of Compact Conductors in Trade Sizes of Conduit or Tubing
Insulation Type
70-828
Conductor T T T X T T T X T T T X T T T X T T TXTTTXTTTXTTTX Conductor
Size
HHHH HHHH HHHH
Size
AWG or
WHHH
WHHHWHHH
WHHH
WHHH
WHHH
WHHHWHHH
AWG or
kcmil
WNW
WNW
WNW
WNW
WNW
WNW
WNW
WNW
kcmil
I
Conduit or Tubing Trade Size
1 in.
1½ in.
1½ in.
2 in.
2½ in.
3 in.
3½ in.
4 in.
6
5 7 6
9 13 11
12 18 15
6
4
4 4 4
7 8 8
9 11 11
15 18 18
4
2
3 3 3
5 6 6
7 8 8
11 13 13
2
1
3 4 4
5 6 6
8 10 10
11 14 14
1
1/0
3 3 3
4 5 5
7 8 8
9 12 12
1/0
2/0
3 3
3 4 4
5 7 7
8 10 10
12 15 15
2/0
3/0
3 3 3
5 6 6
7 8 8
10 13 13
3/0
4/0
3 3
4 5 5
6 7 7
9 10 10
12 14 14
4/0
250
3 4 4
4 5 5
7 8 8
9 11 11
250
NATIONAL ELECTRICAL CODE
300
3 3 3
4 4 4
6 7 7
8 9 10
10 12 12
300
350
3 3
3 4 4
5 6 6
7 8 8
9 11 11
350
400
3 3 4
5 5 6
6 7 8
8 9 10
400
500
3 3
4 4 5
5 6 6
7 8 8
500
600
3 4 4
4 5 5
6 6 7
600
700
3 3 3
4 4 4
5 6 6
700
750
3 3 3
4 4 4
5 5 5
750
1000
3 3 3
4 4 4
1000
Definition: Compact stranding is the result of a manufacturing process where the standard conductor is compressed to the extent that the interstices (voids between strand wires) are virtually eliminated.
CHAPTER 9 - TABLES AND EXAMPLES
70-829
Table 6. Dimensions of Lead-Covered Conductors
Types RL, RHL, and THHW
Single
Two
Three
Conductor
Conductor
Conductor
Size
AWG
Diam.
Area
Diam.
Area
Diam.
Area
kcmil
Inches
Sq. In.
Inches
Sq. In.
Inches
Sq. In.
14
.28
.062
.28 X .47
.115
.59
.273
12
.29
.066
.31 X .54
.146
.62
.301
10
.35
.096
.35 X .59
.180
.68
.363
8
sol.
.41
.132
.41 X .71
.255
.82
.528
8
str.
.43
.145
.43 X .75
.282
.86
.581
6
.49
.188
.49 X .86
.369
.97
.738
4
.55
.237
.54 X .96
.457
1.08
.916
2
.60
.283
.61 X 1.08
.578
1.21
1.146
1
.67
.352
.70 X 1.23
.756
1.38
1.49
1/0
.71
.396
.74 X 1.32
.859
1.47
1.70
2/0
.76
.454
.79 X 1.41
.980
1.57
1.94
3/0
.81
.515
.84 X 1.52
1.123
1.69
2.24
4/0
.87
.593
.90 X 1.64
1.302
1.85
2.68
250
.98
.754
2.02
3.20
300
1.04
.85
2.15
3.62
350
1.10
.95
2.26
4.02
400
1.14
1.02
2.40
4.52
500
1.23
1.18
2.59
5.28
The above cables are limited to straight runs or with nominal offsets equivalent to not
more than two quarter bends.
Note: No. 14 through No. 10, solid conductors; No. 8, solid or stranded conductors; Nos.
6 and larger, stranded conductors.
70-830
NATIONAL ELECTRICAL CODE
Table 8. Conductor Properties
Conductors
DC Resistance at 75°C (167°F)
Stranding
Overall
Size
Area
Copper
Aluminum
AWG/
Cir.
Quan-
Diam.
Diam.
Area
Uncoated
Coated
ohm/
kcmil
Mills
tity
In.
In.
In.
ohm/kFT
ohm/kFT
kFT
18
1620
1
-
0.040
0.001
7.77
8.08
12.8
18
1620
7
0.015
0.046
0.002
7.95
8.45
13.1
16
2580
1
-
0.051
0.002
4.89
5.08
8.05
16
2580
7
0.019
0.058
0.003
4.99
5.29
8.21
14
4110
1
-
0.064
0.003
3.07
3.19
5.06
14
4110
7
0.024
0.073
0.004
3.14
3.26
5.17
12
6530
1
-
0.081
0.005
1.93
2.01
3.18
12
6530
7
0.030
0.092
0.006
1.98
2.05
3.25
10
10380
1
|
0.102
0.008
1.21
1.26
2.00
10
10380
7
0.038
0.116
0.011
1.24
1.29
2.04
8
16510
1
-
0.128
0.013
0.764
0.786
1.26
8
16510
7
0.049
0.146
0.017
0.778
0.809
1.28
6
26240
7
0.061
0.184
0.027
0.491
0.510
0.808
4
41740
7
0.077
0.232
0.042
0.308
0.321
0.508
3
52620
7
0.087
0.260
0.053
0.245
0.254
0.403
2
66360
7
0.097
0.292
0.067
0.194
0.201
0.319
1
83690
19
0.066
0.332
0.087
0.154
0.160
0.253
1/0
105600
19
0.074
0.373
0.109
0.122
0.127
0.201
2/0
133100
19
0.084
0.419
0.138
0.0967
0.101
0.159
3/0
167800
19
0.094
0.470
0.173
0.0766
0.0797
0.126
4/0
211600
19
0.106
0.528
0.219
0.0608
0.0626
0.100
250
-
37
0.082
0.575
0.260
0.0515
0.0535
0.0847
300
-
37
0.090
0.630
0.312
0.0429
0.0446
0.0707
350
-
37
0.097
0.681
0.364
0.0367
0.0382
0.0605
400
-
37
0.104
0.728
0.416
0.0321
0.0331
0.0529
500
-
37
0.116
0.813
0.519
0.0258
0.0265
0.0424
600
-
61
0.099
0.893
0.626
0.0214
0.0223
0.0353
700
-
61
0.107
0.964
0.730
0.0184
0.0189
0.0303
750
-
61
0.111
0.998
0.782
0.0171
0.0176
0.0282
800
-
61
0.114
1.03
0.834
0.0161
0.0166
0.0265
900
-
61
0.122
1.09
0.940
0.0143
0.0147
0.0235
1000
-
61
0.128
1.15
1.04
0.0129
0.0132
0.0212
1250
I
91
0.117
1.29
1.30
0.0103
0.0106
0.0169
1500
-
91
0.128
1.41
1.57
0.00858
0.00883
0.0141
-1750
-
127
0.117
1.52
1.83
0.00735
0.00756
0.0121
2000
-
127
0.126
1.63
2.09
0.00643
0.00662
0.0106
These resistance values are valid ONLY for the parameters as given. Using conductors having coated strands, different stranding type, and, especially, other temperatures changes the
resistance.
Formula for temperature change: R₂ = R₁ [1 + α(T₂ - 75)] where: αcu = 0.00323, αL =
0.00330.
Conductors with compact and compressed stranding have about 9 percent and 3 percent,
respectively, smaller bare conductor diameters than those shown. See Table 5A for actual
compact cable dimensions.
The IACS conductivities used: bare copper = 100%, aluminum = 61%.
Class B stranding is listed as well as solid for some sizes. Its overall diameter and area is
that of its circumscribing circle.
(FPN): The construction information is per NEMA WC8-1976 (Rev 5=1980). The resistance is
calculated per National Bureau of Standards Handbook 100, dated 1966, and Handbook 109, dated
1972.
Table 9. AC Resistance and Reactance for 600 V Cables, 3-Phase 60, Hz, 75°C (167°F) -
Three Single Conductors in Conduit
Ohms to Neutral per 1000 feet
XL (Reactance)
AC Resistance for
AC Resistance for
Effective N at .85 PF for
Effective Z at .85 PF for
for All Wires
Uncoated Copper Wires
Aluminum Wires
Uncoated Copper Wires
Aluminum Wires
Size
Size
AWG/
PVC, AI.
Steel
PVC
AI.
Steel
PVC
AI.
Steel
PVC
AI.
Steel
PVC
AI.
Steel
AWG/
kcmil
Conduits
Condult
Conduit
Conduit
Conduit
Conduit
Conduit
Conduit
Conduit
Conduit
Condult
Conduit
Condult
Conduit
kcmil
14
.058
.073
3.1
3.1
3.1
-
-
-
2.7
2.7
2.7
14
12
.054
.068
2.0
2.0
2.0
3.2
3.2
3.2
1.7
1.7
1.7
2.8
2.8
2.8
12
10
.050
.063
1.2
1.2
1.2
2.0
2.0
2.0
1.1
1.1
1.1
1.8
1.8
1.8
10
8
.052
.065
0.78
0.78
0.78
1.3
1.3
1.3
0.69
0.69
0.70
1.1
1.1
1.1
8
6
.051
.064
0.49
0.49
0.49
0.81
0.81
0.81
0.44
0.45
0.45
0.71
0.72
0.72
6
4
.048
.060
0.31
0.31
0.31
0.51
0.51
0.51
0.29
0.29
0.30
0.46
0.46
0.46
4
3
.047
.059
0.25
0.25
0.25
0.40
0.41
0.40
0.23
0.24
0.24
0.37
0.37
0.37
3
2
.045
.057
0.19
0.20
0.20
0.32
0.32
0.32
0.19
0.19
0.20
0.30
0.30
0.30
2
1
.046
.057
0.15
0.16
0.16
0.25
0.26
0.25
0.16
0.16
0.16
0.24
0.24
0.25
1
1/0
.044
.055
0.12
0.13
0.12
0.20
0.21
0.20
0.13
0.13
0.13
0.19
0.20
0.20
1/0
2/0
.043
.054
0.10
0.10
0.10
0.16
0.16
0.16
0.11
0.11
0.11
0.16
0.16
0.16
2/0
3/0
.042
.052
0.077
0.082
0.079
0.13
0.13
0.13
0.088
0.092
0.094
0.13
0.13
0.14
3/0
4/0
.041
.051
0.062
0.067
0.063
0.10
0.11
0.10
0.074
0.078
0.080
0.11
0.11
0.11
4/0
250
.041
.052
0.052
0.057
0.054
0.085
0.090
0.086
0.066
0.070
0.073
0.094
0.098
0.10
250
300
.041
.051
0.044
0.049
0.045
0.071
0.076
0.072
0.059
0.063
0.065
0.082
0.086
0.088
300
CHAPTER 9 AND EXAMPLES
350
.040
.050
0.038
0.043
0.039
0.061
0.066
0.063
0.053
0.058
0.060
0.073
0.077
0.080
350
400
.040
.049
0.033
0.038
0.035
0.054
0.059
0.055
0.049
0.053
0.056
0.066
0.071
0.073
400
500
.039
.048
0.027
0.032
0.029
0.043
0.048
0.045
0.043
0.048
0.050
0.057
0.061
0.064
500
600
.039
.048
0.023
0.028
0.025
0.036
0.041
0.038
0.040
0.044
0.047
0.051
0.055
0.058
600
750
.038
.048
0.019
0.024
0.021
0.029
0.034
0.031
0.036
0.040
0.043
0.045
0.049
0.052
750
1000
.037
.046
0.015
0.019
0.018
0.023
0.027
0.025
0.032
0.036
0.040
0.039
0.042
0.046
1000
Notes:
1. These values are based on the following constants: UL-type RHH wires with Class B stranding, in cradled configuration. Wire conductivitites are 100% IACS
copper and 61% IACS aluminum, and aluminum conduit is 45% IACS. Capacitive reactance is ignored, since it is negligible at these voltages.
These resistance values are valid only at 75°C (167°F) and for the parameters as given, but are representative for 600-volt wire types operating at 60 Hz.
2. "Effective Z" is defined as R cos(theta) + X sin(theta), where "theta" is the power factor angle of the circuit. Multiplying current by effective impedance
gives a good approximation for line-to-neutral voltage drop. Effective impedance values shown in this table are valid only at .85 power factor.
For another circuit power factor (PF), effective impedance (Zc) can be calculated from R and XL values given in this table as follows:
70-831
Zc = R X PF + XL sin[arccos(PF)].
Table 10. Expansion Characteristics of PVC Rigid Nonmetallic Conduit
Coefficient of Thermal Expansion = 3.38 x 10⁻⁵ in./in./°F
70-832
Length Change
Length Change
Length Change
Length Change
Temperature
in Inches per
Temperature
in Inches per
Temperature
in Inches per
Temperature
in Inches per
Change in
100 ft. of
Change In
100 ft. of
Change in
100 ft. of
Change in
100 ft. of
Degrees F
PVC Conduit
Degrees F
PVC Conduit
Degrees F
PVC Conduit
Degrees F
PVC Conduit
5
0.2
55
2.2
105
4.2
155
6.3
10
0.4
60
2.4
110
4.5
160
6.5
15
0.6
65
2.6
115
4.7
165
6.7
20
0.8
70
2.8
120
4.9
170
6.9
25
1.0
75
3.0
125
5.1
175
7.1
30
1.2
80
3.2
130
5.3
180
7.3
35
1.4
85
3.4
135
5.5
185
7.5
40
1.6
90
3.6
140
5.7
190
7.7
45
1.8
95
3.8
145
5.9
195
7.9
50
2.0
100
4.1
150
6.1
200
8.1
NATIONAL ELECTRICAL CODE
CHAPTER 9 - TABLES AND EXAMPLES
70-833
B. Examples
Selection of Conductors. In the following examples, the results are generally expressed in amperes. To select conductor sizes, refer to the 0 to 2000
volt ampacity tables of Article 310 and the Notes that pertain to such
tables.
Voltage. For uniform application of Articles 210, 215, and 220, a nominal voltage of 120, 120/240, 240, and 208Y/120 volts shall be used in computing the ampere load on the conductor.
Fractions of an Ampere. Except where the computations result in a major
fraction of an ampere (0.5 or larger), such fractions shall be permitted to be
I
dropped.
Ranges. For the computation of the range loads in these examples,
Column A of Table 220-19 has been used. For optional methods, see
Columns B and C of Table 220-19. Except where the computations result
in a major fraction of a kilowatt (0.5 or larger), such fractions shall be permitted to be dropped.
SI Units: For SI units: one square foot = 0.093 square meter; one foot =
0.3048 meter.
Example No. 1(a). One-Family Dwelling
The dwelling has a floor area of 1500 sq. ft., exclusive of unoccupied
cellar, unfinished attic, and open porches. Appliances are a 12-kW range
and a 5.5 kW, 240-volt dryer. Assume range and dryer kW ratings equivalent to kVA ratings in accordance with Sections 220-18 and 220-19.
Computed Load [see Section 220-10(a)]:
General Lighting Load:
1500 sq. ft. at 3 volt-amperes per sq. ft = 4500 volt-amperes.
Minimum Number of Branch Circuits Required [see Section 220-4(b)]:
General Lighting Load:
4500 volt-amperes ÷ 120 volts = 37.5 A: This requires three 15 A 2-wire or two
20 A 2-wire circuits
Small Appliance Load: Two 2-wire 20 A circuits [see Section 220-3(b)]
Laundry Load: One 2-wire 20 A circuit [see Section 220-4(c)]
Minimum Size Feeder Required [see Section 220-10(a)]:
General Lighting
4500 volt-amperes
Small Appliance Load
3000 volt-amperes
Laundry
1500 volt-amperes
Total General Light and Small Appliance
9000 volt-amperes
3000 volt-amperes at 100%
3000 volt-amperes
9000 - 3000 = 6000 volt-amperes at 35%
2100 volt-amperes
Net General Lighting and Small Appliance Load
5100 volt-amperes
Range Load (see Table 220-19)
8000 volt-amperes
Dryer Load (see Table 220-18)
5500 volt-amperes
Total Load
18,600 volt-amperes
For 120/240-volt 3-wire single-phase service or feeder,
18,600 volt-amperes ÷ 240 volts = 77.5 A.
Net computed load exceeds 10kVA. Service conductors shall be 100 amperes [see