Regl. 5293, art. 250-8-810
RADIO AND TELEVISION EQUIPMENT
Cite as Reglamento Núm. 5293, Art. 250-8-810
70-805
ARTICLE 810 - RADIO AND TELEVISION EQUIPMENT
A. General
810-1. Scope. This article covers radio and television receiving equipment and amateur radio transmitting and receiving equipment, but not
equipment and antennas used for coupling carrier current to power line
conductors.
810-2. Other Articles. Wiring from the source of power to and between
devices connected to the interior wiring system shall comply with Chapters
1 through 4 other than as modified by Sections 640-3, 640-4, and 640-5.
Wiring for radio-frequency and audio-frequency equipment and loud
speakers shall comply with Article 640. Where optical fiber is used Article
770 shall apply. Coaxial cable wiring for television receiving shall comply
with Article 820.
810-3. Community Television Antenna. The antenna shall comply with
this article. The distribution system shall comply with Article 820.
810-4. Radio Noise Suppressors. Radio interference eliminators, interference capacitors, or noise suppressors connected to power-supply leads
shall be of a listed type. They shall not be exposed to physical damage.
810-5. Definitions. See Article 100.
B. Receiving Equipment - Antenna Systems
810-11. Material. Antennas and lead-in conductors shall be of harddrawn copper, bronze, aluminum alloy, copper-clad steel, or other highstrength, corrosion-resistant material.
Exception: Soft-drawn or medium-drawn copper shall be permitted for
lead-in conductors where the maximum span between points of support is
less than 35 feet (10.67 m).
810-12. Supports. Outdoor antennas and lead-in conductors shall be
securely supported. The antennas shall not be attached to the electric service mast. They shall not be attached to poles or similar structures carrying open electric light or power wires or trolley wires of over 250 volts
between conductors. Insulators supporting the antenna conductors shall
have sufficient mechanical strength to safely support the conductors.
Lead-in conductors shall be securely attached to the antennas.
810-13. Avoidance of Contacts with Conductors of Other Systems.
Outdoor antennas and lead-in conductors from an antenna to a building
shall not cross over open conductors of electric light or power circuits and
shall be kept well away from all such circuits so as to avoid the possibility
70-806
NATIONAL ELECTRICAL CODE
of accidental contact. Where proximity to open electric light or power service conductors of less than 250 volts between conductors cannot be
avoided, the installation shall be such as to provide a clearance of at least
2 feet (610 mm).
Where practicable, antenna conductors shall be so installed as not to
cross under open electric light or power conductors.
810-14. Splices. Splices and joints in antenna spans shall be made
mechanically secure with approved splicing devices or by such other
means as will not appreciably weaken the conductors.
810-15. Grounding. Masts and metal structures supporting antennas
shall be grounded in accordance with Section 810-21.
810-16. Size of Wire-Strung Antenna - Receiving Station.
(a) Size of Antenna Conductors. Outdoor antenna conductors for
receiving stations shall be of a size not less than given in Table 810-16(a).
Table 810-16(a).
Size of Receiving-Station Outdoor Antenna Conductors
Minimum Size of Conductors
When Maximum Open Span Length is
Material
Less than
35 feet to
Over
35 feet
150 feet
150 feet
Aluminum alloy, harddrawn copper
19
14
12
Copper-clad steel, bronze,
or other high-strength
material
20
17
14
For SI units: one foot = 0.3048 meter.
(b) Self-Supporting Antennas. Outdoor antennas, such as vertical rods,
dishes, or dipole structures, shall be of corrosion-resistant materials and of
strength suitable to withstand ice and wind loading conditions, and shall be
located well away from overhead conductors of electric light and power circuits of over 150 volts to ground, so as to avoid the possibility of the antenna
or structure falling into or making accidental contact with such circuits.
810-17. Size of Lead-in - Receiving Station. Lead-in conductors from
outside antennas for receiving stations shall, for various maximum open
span lengths, be of such size as to have a tensile strength at least as great
as that of the conductors for antennas as specified in Section 810-16.
Where the lead-in consists of two or more conductors that are twisted
together, are enclosed in the same covering, or are concentric, the conductor size shall, for various maximum open span lengths, be such that the
tensile strength of the combination will be at least as great as that of the
conductors for antennas as specified in Section 810-16.
ARTICLE 810 - RADIO AND TELEVISION EQUIPMENT
70-807
810-18. Clearances - Receiving Stations.
(a) Outside of Buildings. Lead-in conductors attached to buildings shall
be so installed that they cannot swing closer than 2 feet (610 mm) to the conductors of circuits of 250 volts or less between conductors, or 10 feet (3.05 m)
to the conductors of circuits of over 250 volts between conductors, except
that in the case of circuits not over 150 volts between conductors, where all
conductors involved are supported so as to ensure permanent separation, the
clearance shall be permitted to be reduced but shall not be less than 4 inches
(102 mm). The clearance between lead-in conductors and any conductor
forming a part of a lightning-rod system shall not be less than 6 feet (1.83 m)
unless the bonding referred to in Section 250-86 is accomplished. Underground conductors shall be separated at least 12 inches (305 mm) from conductors of any light or power circuits, or Class 1 circuits.
Exception: Where the electric light or power conductors, Class 1 conductors, or lead-in conductors are installed in raceways or metal cable armor.
(b) Antennas and Lead-ins - Indoors. Indoor antennas and indoor
lead-ins shall not be run nearer than 2 inches (50.8 mm) to conductors of
other wiring systems in the premises.
Exception No. 1: Where such other conductors are in metal raceways
or cable armor.
Exception No. 2: Where permanently separated from such other conductors by a continuous and firmly fixed nonconductor, such as porcelain
tubes or flexible tubing.
(c) In Boxes or Other Enclosures. Indoor antennas and indoor lead-ins
shall be permitted to occupy the same box or enclosure with conductors of
other wiring systems where separated from such other conductors by an
effective permanently installed barrier.
810-19. Electric Supply Circuits Used in Lieu of Antenna - Receiving
Stations. Where an electric supply circuit is used in lieu of an antenna,
the device by which the radio receiving set is connected to the supply circuit shall be listed.
810-20. Antenna Discharge Units - Receiving Stations.
(a) Where Required. Each conductor of a lead-in from an outdoor
antenna shall be provided with a listed antenna discharge unit.
Exception: Where the lead-in conductors are enclosed in a continuous
metallic shield that is either permanently and effectively grounded, or is
protected by an antenna discharge unit.
(b) Location. Antenna discharge units shall be located outside the building or inside the building between the point of entrance of the lead-in and
the radio set or transformers, and as near as practicable to the entrance of
the conductors to the building. The antenna discharge unit shall not be
located near combustible material nor in a hazardous (classified) location
as defined in Article 500.
(c) Grounding. The antenna discharge unit shall be grounded in accordance with Section 810-21.
70-808
NATIONAL ELECTRICAL CODE
810-21. Grounding Conductors - Receiving Stations. Grounding conductors shall comply with (a) through (j) below.
(a) Material. The grounding conductor shall be of copper, aluminum,
copper-clad steel, bronze, or similar corrosion-resistant material.
(b) Insulation. Insulation on grounding conductors shall not be
required.
(c) Supports. The grounding conductors shall be securely fastened in
place and shall be permitted to be directly attached to the surface wired
over without the use of insulating supports.
Exception: Where proper support cannot be provided, the size of the
grounding conductors shall be increased proportionately.
(d) Mechanical Protection. The grounding conductor shall be protected
where exposed to physical damage, or the size of the grounding conductors
shall be increased proportionately to compensate for the lack of protection.
(e) Run in Straight Line. The grounding conductor for an antenna mast
or antenna discharge unit shall be run in as straight a line as practicable
from the mast or discharge unit to the grounding electrode.
(f) Electrode. The grounding conductor shall be connected as follows:
(1) To the nearest accessible location on (1) the building or structure
grounding electrode system as covered in Section 250-81, (2) the grounded
interior metal water piping system as covered in Section 250-80(a), (3) the
power service accessible means external to enclosures as covered in Section 250-71(b), (4) the metallic power service raceway, (5) the service
equipment enclosure, or (6) the grounding electrode conductor or the
grounding electrode conductor metal enclosures; or
(2) If the building or structure served has no grounding means, as
described in (f)(1), to any one of the individual electrodes described in
Section 250-81; or
(3) If the building or structure served has no grounding means, as
described in (f)(1) or (f)(2), to (1) an effectively grounded metal structure or
(2) to any of the individual electrodes described in Section 250-83.
(g) Inside or Outside Building. The grounding conductor shall be permitted to be run either inside or outside the building.
(h) Size. The grounding conductor shall not be smaller than No. 10 cop-
I
per or No. 8 aluminum or No. 17 copper-clad steel or bronze.
(i) Common Ground. A single grounding conductor shall be permitted
for both protective and operating purposes.
(j) Bonding of Electrodes. A bonding jumper not smaller than No. 6
copper or equivalent shall be connected between the radio and television
equipment grounding electrode and the power grounding electrode system
at the building or structure served where separate electrodes are used.
C. Amateur Transmitting and Receiving Stations - Antenna Systems
810-51. Other Sections. In addition to complying with Part C, antenna
systems for amateur transmitting and receiving stations shall also comply
with Sections 810-11 through 810-15.
ARTICLE 810 - RADIO AND TELEVISION EQUIPMENT
70-809
810-52. Size of Antenna. Antenna conductors for transmitting and
receiving stations shall be of a size not less than given in Table 810-52.
Table 810-52.
Size of Amateur Station Outdoor Antenna Conductors
Minimum Size of Conductors
Where Maximum Open Span Length is
Material
Less than
Over
150 feet
150 feet
Hard-drawn copper
14
10
Copper-clad steel, bronze, or other
high-strength material
14
12
For SI units: one foot = 0.3048 meter.
810-53. Size of Lead-in Conductors. Lead-in conductors for transmitting
stations shall, for various maximum span lengths, be of a size at least as
great as that of conductors for antennas as specified in Section 810-52.
810-54. Clearance on Building. Antenna conductors for transmitting stations, attached to buildings, shall be firmly mounted at least 3 inches
(76 mm) clear of the surface of the building on nonabsorbent insulating
supports, such as treated pins or brackets equipped with insulators having
not less than 3-inch (76-mm) creepage and airgap distances. Lead-in conductors attached to buildings shall also comply with these requirements.
Exception: Where the lead-in conductors are enclosed in a continuous
metallic shield that is permanently and effectively grounded, they shall not
be required to comply with these requirements. Where grounded, the
metallic shield shall also be permitted to be used as a conductor.
810-55. Entrance to Building. Except where protected with a continuous
metallic shield that is permanently and effectively grounded, lead-in conductors for transmitting stations shall enter buildings by one of the following methods: (1) through a rigid, noncombustible, nonabsorbent insulating
tube or bushing; (2) through an opening provided for the purpose in which
the entrance conductors are firmly secured so as to provide a clearance of
at least 2 inches (50.8 mm); or (3) through a drilled window pane.
810-56. Protection Against Accidental Contact. Lead-in conductors to
radio transmitters shall be so located or installed as to make accidental
contact with them difficult.
810-57. Antenna Discharge Units - Transmitting Stations. Each conductor of a lead-in for outdoor antennas shall be provided with an antenna
discharge unit or other suitable means that will drain static charges from
the antenna system.
70-810
NATIONAL ELECTRICAL CODE
Exception No. 1: Where protected by a continuous metallic shield that
is permanently and effectively grounded.
grounded. Exception No. 2: Where the antenna is permanently and effectively
810-58. Grounding Conductors - Amateur Transmitting and Receiving
Stations. Grounding conductors shall comply with (a) through (c) below.
(a) Other Sections. All grounding conductors for amateur transmitting
and receiving stations shall comply with Sections 810-21(a) through (j).
(b) Size of Protective Grounding Conductor. The protective grounding
conductor for transmitting stations shall be as large as the lead-in, but not
smaller than No. 10 copper, bronze, or copper-clad steel.
(c) Size of Operating Grounding Conductor. The operating grounding
conductor for transmitting stations shall not be less than No. 14 copper or
its equivalent.
D. Interior Installation - Transmitting Stations
810-70. Clearance from Other Conductors. All conductors inside the
building shall be separated at least 4 inches (102 mm) from the conductors
of any electric light, power, or signaling circuit.
Exception No. 1: As provided in Article 640.
Exception No. 2: Where separated from other conductors by raceway or
some firmly fixed nonconductor, such as porcelain tubes or flexible tubing.
810-71. General. Transmitters shall comply with (a) through (c) below.
(a) Enclosing. The transmitter shall be enclosed in a metal frame or
grille, or separated from the operating space by a barrier or other equivalent means, all metallic parts of which are effectively connected to ground.
(b) Grounding of Controls. All external metal handles and controls
accessible to the operating personnel shall be effectively grounded.
(c) Interlocks on Doors. All access doors shall be provided with interlocks that will disconnect all voltages of over 350 volts between conductors
when any access door is opened.