Regl. 5293, art. 250-8-820
COMMUNITY ANTENNA TELEVISION
Cite as Reglamento Núm. 5293, Art. 250-8-820
AND RADIO DISTRIBUTION SYSTEMS
A. General
820-1. Scope. This article covers coaxial cable distribution of radio frequency signals typically employed in community antenna television
(CATV) systems.
(FPN): Where the installation is other than coaxial, see Articles 770 and 800 as
applicable.
ARTICLE 820 - COMMUNITY ANTENNA TELEVISION
70-811
820-2. Energy Limitations. The coaxial cable shall be permitted to
deliver low-energy power to equipment directly associated with the radio
frequency distribution system if the voltage is not over 60 volts and if the
current supply is from a transformer or other device having energy-limiting
characteristics.
820-3. Definitions. See Article 100. For the purposes of this Article, the
following additional definition applies:
Point of Entrance. The point of entrance within a building is the point
at which the cable emerges from an external wall, from a concrete floor
slab, or from a rigid metal conduit or an intermediate metal conduit
grounded to an electrode in accordance with Section 820-40(b).
820-5. Access to Electrical Equipment Behind Panels Designed to Allow
Access. Access to equipment shall not be denied by an accumulation of
wires and cables that prevents removal of panels, including suspended
ceiling panels.
820-6. Mechanical Execution of Work. Community antenna television
and radio distribution systems shall be installed in a neat and workmanlike
manner.
B. Cables Outside and Entering Buildings
820-10. Outside Cables. Coaxial cables, prior to the point of grounding,
as defined in Section 820-33, shall comply with (a) through (e) below.
(a) On Poles. Where practicable, conductors on poles shall be located
below the electric light or power conductors and shall not be attached to a
cross-arm that carries electric light or power conductors.
(b) Lead-in Clearance. Lead-in or aerial-drop cables from a pole or
other support, including the point of initial attachment to a building or
structure, shall be kept away from electric light or power circuits so as to
avoid the possibility of accidental contact.
Exception: Where proximity to electric light or power service conductors cannot be avoided, the installation shall be such as to provide clearances of not less than 12 inches (305 mm) from light or power service
drops.
(c) Above Roofs. Cables shall have a vertical clearance of not less than
8 feet (2.44 m) from all points of roofs above which they pass.
Exception No. 1: Auxiliary buildings such as garages and the like.
Exception No. 2: A reduction in clearance above only the overhanging
portion of the roof to not less than 18 inches (457 mm) shall be permitted
if (1) not more than 4 feet (1.22 m) of communication service drop conductors pass above the roof overhang, and (2) they are terminated at a
through-the-roof raceway or support.
Exception No. 3: Where the roof has a slope not less than 4 inches
(102 mm) in 12 inches (305 mm), a reduction in clearance to not less
than 3 feet (914 mm) shall be permitted.
70-812
NATIONAL ELECTRICAL CODE
(d) Between Buildings. Cables extending between buildings and also
the supports or attachment fixtures shall be acceptable for the purpose and
shall have sufficient strength to withstand the loads to which they may be
subjected.
Exception: Where a cable does not have sufficient strength to be selfsupporting, it shall be attached to a supporting messenger cable that,
together with the attachment fixtures or supports, shall be acceptable for
the purpose and shall have sufficient strength to withstand the loads to
which they may be subjected.
(e) On Buildings. Where attached to buildings, cables shall be securely
fastened in such a manner that they will be separated from other conductors as follows:
(1) Electric Light or Power. The coaxial cable shall have a separation
of at least 4 inches (102 mm) from electric light or power conductors not in
raceway or cable, or be permanently separated from conductors of the
other system by a continuous and firmly fixed nonconductor in addition to
the insulation on the wires.
(2) Other Communications Systems. Coaxial cable shall be installed
so that there will be no unnecessary interference in the maintenance of the
separate systems. In no case shall the conductors, cables, messenger
strand, or equipment of one system cause abrasion to the conductors,
cable, messenger strand, or equipment of any other system.
(3) Lightning Conductors. Where practicable, a separation of at least
conductors. 6 feet (1.83 m) shall be maintained between any coaxial cable and lightning
820-11. Entering Buildings.
(a) Underground Systems. Underground coaxial cables in a duct, pedestal, handhole, or manhole containing electric light or power conductors
or Class 1 circuits shall be in a section permanently separated from such
conductors by means of a suitable barrier.
(b) Direct Buried Cables and Raceways. Direct buried coaxial cable
shall be separated at least 12 inches (305 mm) from conductors of any light
or power or Class 1 circuit.
Exception No. 1: Where electric service conductors or coaxial cables
are installed in raceways or have metal cable armor.
Exception No. 2: Where electric light or power branch-circuit or feeder
conductors or Class 1 circuit conductors are installed in a raceway or in
metal-sheathed, metal-clad, or Type UF or Type USE cables; or the coaxial cables have metal cable armor or are installed in a raceway.
C. Protection
820-33. Grounding of Outer Conductive Shield of a Coaxial Cable.
Where coaxial cable is exposed to lightning or to accidental contact with
lightning arrester conductors or power conductors operating at a voltage of
over 300 volts to ground, the outer conductive shield of the coaxial cable
shall be grounded at the building premises as close to the point of cable
entry as practicable. For purposes of this section, the point at which the
ARTICLE 820 - COMMUNITY ANTENNA TELEVISION
70-813
exposed cable enters shall be considered to be the point of emergence
through an exterior wall, a concrete floor slab, or from a rigid or intermediate metal conduit grounded to an electrode in accordance with Section
820-40(b).
For purposes of this section, grounding located at mobile home service
equipment located in sight from and no more than 30 feet (9.14 m) from the
exterior wall of the mobile home it serves, or at a mobile home disconnecting means grounded in accordance with Section 250-24 and located in sight
from and not more than 30 feet (9.14 m) from the exterior wall of the
mobile home it serves, shall be considered to meet the requirements of this
section.
(FPN): Selecting a grounding location to achieve the shortest practicable
grounding conductor will help limit potential differences between CATV and other
metallic systems.
(a) Shield Grounding. Where the outer conductive shield of a coaxial
cable is grounded, no other protective devices shall be required.
(b) Shield Protection Devices. Grounding of a coaxial drop cable shield
by means of a protective device that does not interrupt the grounding system within the premises shall be permitted.
D. Grounding Methods
820-40. Cable Grounding. Where required by Section 820-33, the shield
of the coaxial cable shall be grounded as specified in (a) through (d) below.
(a) Grounding Conductor.
(1) Insulation. The grounding conductor shall be insulated and shall be
listed as suitable for the purpose.
(2) Material. The grounding conductor shall be copper or other
corrosion-resistant conductive material, stranded or solid.
(3) Size. The grounding conductor shall not be smaller than No. 14; it
shall have a current-carrying capacity approximately equal to that of the
outer conductor of the coaxial cable.
(4) Run in Straight Line. The grounding conductor shall be run to the
grounding electrode in as straight a line as practicable.
(5) Physical Protection. Where subject to physical damage, the
grounding conductor shall be adequately protected. Where the grounding
conductor is run in a metal raceway, both ends of the raceway shall be
bonded to the grounding conductor or the same terminal or electrode to
which the grounding conductor is connected.
(b) Electrode. The grounding conductor shall be connected as follows:
(1) To the nearest accessible location on (1) the building or structure
grounding electrode system as covered in Section 250-81, (2) the grounded
interior metal water piping system as covered in Section 250-80(a), (3) the
power service accessible means external to enclosures as covered in Section 250-71(b), (4) the metallic power service raceway, (5) the service
equipment enclosure, (6) the grounding electrode conductor or the grounding electrode conductor metal enclosure, or (7) to the grounding conductor
or to the grounding electrode of a building or structure disconnecting
means that is grounded to an electrode as covered in Section 250-24; or
70-814
NATIONAL ELECTRICAL CODE
(2) If the building or structure served has no grounding means as
described in (b)(1), to any one of the individual electrodes described in
Section 250-81; or
(3) If the building or structure served has no grounding means as
described in (b)(1) or (b)(2), to (1) an effectively grounded metal structure
or (2) to any one of the individual electrodes described in Section 250-83.
(c) Electrode Connection. Connections to grounding electrodes shall
comply with Section 250-115.
(d) Bonding of Electrodes. A bonding jumper not smaller than No. 6
copper or equivalent shall be connected between the antenna systems
grounding electrode and the power grounding electrode system at the
building or structure served where separate electrodes are used.
Exception: At mobile homes as covered in Section 820-42.
(FPN No. 1): See Section 250-86 for use of lightning rods.
(FPN No. 2): Bonding together of all separate electrodes will limit potential differences between them and between their associated wiring systems.
820-41. Equipment Grounding. Unpowered equipment and enclosures
or equipment powered by the coaxial cable shall be considered grounded
where connected to the metallic cable shield.
820-42. Bonding and Grounding at Mobile Homes.
(a) Grounding. Where there is no mobile home service equipment
located in sight from and not more than 30 feet (9.14 m) from the exterior
wall of the mobile home it serves, or there is no mobile home disconnecting means grounded in accordance with Section 250-24 and located within
sight from and not more than 30 feet (9.14 m) from the exterior wall of the
mobile home it serves, the coaxial cable shield ground, or surge arrester
ground, shall be in accordance with Sections 820-40(b) (2) and (3).
(b) Bonding. The coaxial cable shield grounding terminal, surge
arrester grounding terminal, or grounding electrode shall be bonded to the
metal frame or available grounding terminal of the mobile home with a
copper grounding conductor not smaller than No. 12 under any of the following conditions:
(1) Where there is no mobile home service equipment or disconnecting means as in (a) above, or
(2) Where the mobile home is supplied by cord and plug.
E. Cables Within Buildings
820-49. Fire Resistance of CATV Cables. Coaxial cables installed as wiring within buildings shall be listed as being resistant to the spread of fire in
accordance with Sections 820-50 and 820-51.
820-50. Listing, Marking, and Installation of Coaxial Cables. Coaxial
cables in a building shall be listed as being suitable for the purpose, and
cables shall be marked in accordance with Table 820-50. The cable voltage
rating shall not be marked on the cable.
ARTICLE 820 - COMMUNITY ANTENNA TELEVISION
70-815
(FPN): Voltage markings on cables may be misinterpreted to suggest that the
cables may be suitable for Class 1, electric light and power applications.
Exception No. 1: Voltage markings shall be permitted where the cable
has multiple listings and voltage marking is required for one or more of the
listings.
Exception No. 2: Listing and marking shall not be required where the
cable enters the building from the outside and is run in rigid metal conduit
or intermediate metal conduit, and such conduits are grounded to an electrode in accordance with Section 820-40(b).
Exception No. 3: Listing and marking shall not be required where the
length of cable within the building does not exceed 50 feet (15.2 m) and the
cable enters the building from the outside and is terminated at a grounding
block.
Table 820-50. Cable Markings
Cable
Marking
Type
Reference
CATVP
CATV plenum cable
Sections 820-51(a) and 820-53(a)
CATVR
CATV riser cable
Sections 820-51(b) and 820-53(b)
CATV
CATV cable
Sections 820-51(c) and 820-53(c)
CATVX
CATV cable, limited use
Sections 820-51(d) and 820-53(c),
Exception Nos. 1, 2, and 3
(FPN No. 1): Cable types are listed in descending order of fire-resistance rating.
(FPN No. 2): See the referenced sections for listing requirements and permitted
uses.
820-51. Additional Listing Requirements. Cables shall be listed in accordance with (a) through (d) below.
(a) Type CATVP. Type CATVP community antenna television plenum
cable shall be listed as being suitable for use in ducts, plenums, and other
space used for environmental air and shall also be listed as having adequate
fire-resistant and low-smoke-producing characteristics.
(FPN): One method of defining low-smoke-producing cables is by establishing
an acceptable value of the smoke produced when tested in accordance with the Test
for Fire and Smoke Characteristics of Wires and Cables, NFPA 262-1990 (ANSI), I
to a maximum peak optical density of 0.5 and a maximum average optical density of
0.15. Similarly, one method of defining fire-resistant cables is by establishing maximum allowable flame travel distance of 5 feet (1.52 m) when tested in accordance
with the same test.
(b) Type CATVR. Type CATVR community antenna television riser
cable shall be listed as being suitable for use in a vertical run in a shaft or
from floor to floor and shall also be listed as having fire-resistant characteristics capable of preventing the carrying of fire from floor to floor.
70-816
NATIONAL ELECTRICAL CODE
(FPN): One method of defining fire-resistant characteristics capable of preventing the carrying of fire from floor to floor is that the cables pass the requirements of
the Standard Test for Flame Propagation Height of Electrical and Optical-Fiber
Cable Installed Vertically in Shafts, ANSI/UL 1666-1986.
(c) Type CATV. Type CATV community antenna television cable shall
be listed as being suitable for general purpose CATV use, with the exception of risers and plenums, and shall also be listed as being resistant to the
spread of fire.
(FPN): One method of defining resistant to the spread of fire is that the cables
do not spread fire to the top of the tray in the "Vertical-Tray Flame Test" in the
Reference 1581-1985. Standard for Electrical Wires, Cables and Flexible Cords, ANSI/UL
Another method of defining resistant to the spread of fire is for the damage (char
length) not to exceed 4 feet 11 inches (1.5 m) when performing the "Vertical Flame
Test-Cables in Cable Trays," as described in Test Methods for Electrical Wires
and Cables, CSA C22.2 No. 0.3-M-1985.
(d) Type CATVX. Type CATVX limited-use community antenna television cable shall be listed as being suitable for use in dwellings and for use
in raceway and shall also be listed as being flame-retardant.
(FPN): One method of determining that cable is flame-retardant is by testing the
cable to the "VW-1 (Vertical-Wire) Flame Test" in the Reference Standard for
Electrical Wires, Cables and Flexible Cords, ANSI/UL 1581-1985.
820-52. Installation of Cables and Equipment. Beyond the point of
grounding, as defined in Section 820-33, the cable installation shall comply
I
with (a) through (e) below.
(a) Separation from Other Conductors.
(1) Open Conductors. Coaxial cable shall be separated at least
2 inches (50.8 mm) from conductors of any electric light or power circuits
or Class 1 circuits.
Exception No. 1: Where the electric light or power or Class 1 or coaxial cable circuit conductors are in a raceway, or in metal-sheathed, metalclad, nonmetallic-sheathed, or Type UF cables.
Exception No. 2: Where the conductors are permanently separated
from the conductors of the other circuits by a continuous and firmly fixed
nonconductor, such as porcelain tubes or flexible tubing, in addition to the
insulation on the wire.
(2) In Enclosures and Raceways.
a. Other Power-Limited Circuits. Coaxial cables shall be permitfollowing: ted in the same raceway or enclosure with jacketed cables of any of the
1. Class 2 and Class 3 remote-control, signaling, and powerlimited circuits in compliance with Article 725.
2. Power-limited fire protective signaling systems in compliance
with Article 760.
3. Communications circuits in compliance with Article 800.
4. Optical fiber cables in compliance with Article 770.
ARTICLE 820 - COMMUNITY ANTENNA TELEVISION
70-817
b. Electric Light or Power Circuits. Coaxial cable shall not be
placed in any raceway, compartment, outlet box, junction box, or other
enclosures with conductors of electric light or power or Class 1 circuits.
Exception No. 1: Where the conductors of the different systems are
separated by a permanent barrier.
Exception No. 2: Conductors in outlet boxes, junction boxes, or similar
fittings or compartments where such conductors are introduced solely for
power supply to the coaxial cable system distribution equipment or for
power connection to remote-control equipment.
The electric light, power, and Class 1 circuit conductors and nonpowerlimited fire protective signaling circuit conductors shall be routed within
the enclosure to maintain a minimum 0.25-inch (6.35-mm) separation from
the coaxial cable.
(3) In Shafts. Coaxial cables run in the same shaft with conductors of
electric light or power shall be separated from electric light or power conductors by not less than 2 inches (50.8 mm).
Exception No. 1: Where the conductors of either system are encased in
metal raceway.
Exception No. 2: Where the electric light or power conductors are in
raceway, or in metal-sheathed, metal-clad, nonmetallic-sheathed, or Type
UF cables.
(b) Spread of Fire or Products of Combustion. Installations in hollow
spaces, vertical shafts, and ventilation or air-handling ducts shall be so
made that the possible spread of fire or products of combustion will not be
substantially increased. Openings around penetrations through fireresistance-rated walls, partitions, floors, or ceilings shall be firestopped
using approved methods.
(c) Equipment in Other Space Used for Environmental Air. Section
300-22(c) shall apply.
(d) Hybrid Power and Coaxial Cabling. The provisions of Section 780-6
shall apply for listed hybrid power and coaxial cabling in closed-loop and
programmed power distribution.
(e) Support of Conductors. Raceways shall not be used as a means of
support for coaxial cables.
820-53. Applications of Listed CATV Cables. CATV cables shall comply
with (a) through (d) below.
(a) Plenum. Cables installed in ducts, plenums, and other spaces used
for environmental air shall be Type CATVP.
Exception: Types CATVP, CATVR, CATV, and CATVX cables
installed in compliance with Section 300-22.
(b) Riser. Cables installed in vertical runs and penetrating more than
one floor, or cables installed in vertical runs in a shaft, shall be Type
CATVR. Floor penetrations requiring Type CATVR shall contain only
cables suitable for riser or plenum use.
Exception No. 1: Types CATV and CATVX cables encased in metal
raceway or located in a fireproof shaft having firestops at each floor.
70-818
NATIONAL ELECTRICAL CODE
Exception No. 2: Types CATV and CATVX cables in one- and twofamily dwellings.
(FPN): See Section 820-52(b) for the firestop requirements for floor penetrations.
(c) Other Wiring Within Buildings. Cables installed in building locations
other than the locations covered in (a) and (b) above shall be Type CATV.
Exception No. 1: Type CATVX cable enclosed in raceway.
Exception No. 2: Type CATVX cable in nonconcealed spaces where the
exposed length of cable does not exceed 10 feet (3.05 m).
Exception No. 3: Type CATVX cables that are less than .375 inch
(9.52 mm) in diameter and installed in one- or two-family dwellings.
Exception No. 4: Type CATVX cables that are less than .375 inch
(9.52 mm) in diameter and installed in nonconcealed spaces in multifamily dwellings.
(d) Cable Substitutions. The substitutions for community antenna television cables listed in Table 820-53 shall be permitted.
Table 820-53. Coaxial Cable Substitutions
Cable Type
Permitted Substitutions
CATVP
MPP, CMP
CATVR
CATVP, MPP, CMP, MPR, CMR
CATV
CATVP, MPP, CMP, CATVR, MPR, CMR,
MPG, MP, CMG, CM
CATVX
CATVP, MPP, CMP, CATVR, MPR, CMR,
CATV, MPG, MP, CMG, CM
70-819
Chapter
9
Tables and Examples
A. Tables
Notes to Tables
1. Tables 3A, 3B, and 3C apply only to complete conduit or tubing systems and are not intended to apply to sections of conduit or tubing used to
protect exposed wiring from physical damage.
2. Equipment grounding or bonding conductors, where installed, shall be
included when calculating conduit or tubing fill. The actual dimensions of the
equipment grounding or bonding conductor (insulated or bare) shall be used
in the calculation.
3. Where conduit or tubing nipples having a maximum length not to
exceed 24 inches (610 mm) are installed between boxes, cabinets, and similar enclosures, the nipple shall be permitted to be filled to 60 percent of its
total cross-sectional area, and Article 310, Note 8(a) of Notes to Ampacity
Tables of 0 to 2000 Volts need not apply to this condition.
4. For conductors not included in Chapter 9, such as multiconductor
cables, the actual dimensions shall be used.
5. See Table 1 for allowable percentage of conduit or tubing fill.
(FPN): Table 1 is based on common conditions of proper cabling and alignment
of conductors where the length of the pull and the number of bends are within reasonable limits. It should be recognized that for certain conditions a larger size conduit or a lesser conduit fill should be considered.
Table 1. Percent of Cross Section of
Conduit and Tubing for Conductors
(See Table 2 for Fixture Wires)
Number of Conductors
1
2
3
4
Over 4
All conductor types
53
31
40
40
40
except lead-covered
Lead-covered conductors
55
30
40
38
35
Note 1. See Tables 3A, 3B, and 3C for number of conductors all of the same size in trade
sizes of conduit or tubing ½ inch through 6 inch.
Note 2: See Table 5B for number of compact conductors all of the same size in trade sizes
of conduit or tubing ½ inch through 4 inch.
Note 3. For conductors larger than 750 kcmil or for combinations of conductors of different sizes, use Tables 4 through 8, Chapter 9, for dimensions of conductors, conduit, and
tubing.
Note 4. Where the calculated conductors, all of the same size (total cross-sectional area
including insulation), include a decimal fraction, the next higher whole number shall be used
where this decimal is 0.8 or larger.
Note 5. Where bare conductors are permitted by other sections of this Code, the dimensions for bare conductors in Table 8 of Chapter 9 shall be permitted.
Note 6. A multiconductor cable of two or more conductors shall be treated as a single
conductor cable for calculating percentage conduit fill area. For cables that have elliptical cross
section, the cross-sectional area calculation shall be based on using the major diameter of the ellipse
as a circle diameter.
Table 2. Maximum Number of Fixture Wires in Trade Sizes of Conduit or Tubing
(40 Percent Fill Based on Individual Diameters)
Conduit
70-820
Trade Size
(Inches)
1/2
3/4
1
1½
1½
2
Wire Types
18
16
14
12
10
18
16
14
12
10
18
16
14
12
10
18
16
14
12
10
18
16
14
12
10
18
16
14
12
10
PTF, PTFF,
PGFF, PGF,
PFF, PF, PAF,
PAFF, ZF, ZFF
23
18
14
40
31
24
65
50
39
115
90
70
157
122
95
257
200
156
TFFN, TFN
19
15
34
26
55
43
97
76
132
104
216
169
SF-1
16
29
47
83
114
186
SFF-1
15
26
43
76
104
169
TF
11
10
20
18
32
30
57
53
79
72
129
118
RFH-1
11
20
32
57
79
129
TFF
11
10
20
17
32
27
56
49
77
66
126
109
NATIONAL ELECTRICAL CODE
AF
11
9
7
4
3
19
16
12
7
5
31
26
20
11
8
55
46
36
19
15
75
63
49
27
20
123
104
81
44
34
SFF-2
9
7
6
16
12
10
27
20
17
47
36
30
65
49
42
106
81
68
SF-2
9
8
6
16
14
11
27
23
18
47
40
32
65
55
43
106
90
71
FFH-2
9
7
15
12
25
19
44
34
60
46
99
75
RFH-2
7
5
12
10
20
16
36
28
49
38
80
62
KF-1, KFF-1,
KF-2, KFF-2
36
32
22
14
9
64
55
39
25
17
103
89
63
41
28
182
158
111
73
49
248
216
152
100
67
406
353
248
163
110
Table 3A. Maximum Number of Conductors in Trade Sizes of Conduit or Tubing
(Based on Table 1, Chapter 9)
Conduit or Tubing Trade Size
(Inches)
½
3/4
1
1½
1½
2
2½
3
3½
4
5
6
Conductor
Size
Type Letters
AWG/kcmil
TW, XHHW
14
9
15
25
44
60
99
142
(14 through 18)
12
7
12
19
35
47
78
111
171
RH (14 + 12)
10
5
9
15
26
36
60
85
131
176
8
2
4
7
12
17
28
40
62
84
108
RHW and RHH
14
6
10
16
29
40
65
93
143
192
(without outer
12
4
8
13
24
32
53
76
117
157
covering),
10
4
6
11
19
26
43
61
95
127
163
RH (10 + 8)
8
1
3
5
10
13
22
32
49
66
85
133
THW, THHW
TW,
6
1
2
4
7
10
16
23
36
48
62
97
141
4
1
1
3
5
7
12
17
27
36
47
73
106
THW,
3
1
1
2
4
6
10
15
23
31
40
63
91
2
1
1
2
4
5
9
13
20
27
34
54
78
CHAPTER 9 - TABLES AND EXAMPLES
1
1
1
3
4
6
9
14
19
25
39
57
FEPB (6 through 2),
1/0
1
1
2
3
5
8
12
16
21
33
49
RHW and RHH (with-
2/0
1
1
1
3
5
7
10
14
18
29
41
out outer
3/0
1
1
1
2
4
6
9
12
15
24
35
covering)
4/0
1
1
1
3
5
7
10
13
20
29
250
1
1
1
2
4
6
8
10
16
23
300
1
1
1
2
3
5
7
9
14
20
350
1
1
1
3
4
6
8
12
18
400
1
1
1
2
4
5
7
11
16
RH, THHW
500
1
1
1
1
3
4
6
9
14
600
1
1
1
3
4
5
7
11
700
1
1
1
2
3
4
7
10
750
1
1
1
2
3
4
6
9
70-821
Note 1. This table is for concentric stranded conductors only. For cables with compact conductors, the dimensions in Table 5A shall be used.
Note 2. Conduit fill for conductors with a -2 suffix is the same as for those types without the suffix.
Table 3B. Maximum Number of Conductors in Trade Sizes of Conduit or Tubing
(Based on Table 1, Chapter 9)
70-822
Conduit or Tubing Trade Size
(Inches)
1/2
3/4
1
1½
1½
2
2½
3
3½
4
5
6
Conductor
Size
Type Letters
AWG/kcmil
14
13
24
39
69
94
154
12
10
THWN,
18
29
51
70
114
164
10
6
11
18
32
44
73
104
160
8
3
5
9
16
22
36
51
79
106
136
THHN,
6
1
4
6
11
15
26
37
57
76
98
154
FEP (14 through 2),
4
1
2
4
7
9
16
22
35
47
60
94
137
FEPB (14 through 8),
3
1
1
3
6
8
13
19
29
39
51
80
116
PFA (14 through 4/0)
2
1
1
3
5
7
11
16
25
33
43
67
97
PFAH (14 through 4/0)
1
1
1
3
5
8
12
18
25
32
50
72
Z (14 through 4/0)
1/0
1
1
3
4
7
10
15
21
27
XHHW (4 through
42
61
2/0
1
1
2
3
6
8
13
17
22
500 kcmil)
35
51
3/0
1
1
1
3
5
7
11
14
18
29
42
4/0
1
1
1
2
4
6
9
12
15
NATIONAL ELECTRICAL CODE
24
35
250
1
1
1
3
4
7
10
12
20
28
300
1
1
1
3
4
6
8
11
17
24
350
1
1
1
2
3
5
7
9
15
21
400
1
1
1
3
5
6
8
13
19
500
1
1
1
2
4
5
7
11
16
600
1
1
1
1
3
4
5
9
13
700
1
1
1
3
4
5
8
11
750
1
1
1
2
3
4
7
11
XHHW
6
1
3
5
9
13
21
30
47
63
81
128
185
600
1
1
1
1
3
4
5
9
13
700
1
1
1
3
4
5
7
11
750
1
1
1
2
3
4
7
10
Note 1. This table is for concentric stranded conductors only. For cables with compact conductors, the dimensions in Table 5A shall be used.
I
Note 2. Conduit fill for conductors with a -2 suffix is the same as for those types without the suffix.
Table 3C. Maximum Number of Conductors in Trade Sizes of Conduit or Tubing
(Based on Table 1, Chapter 9)
Conduit or Tubing Trade Size
(Inches)
1/2
3/4
1
11/4
1½
2
2½
3
3½
4
5
6
Conductor
Size
Type Letters
AWG/kcmil
14
3
6
10
18
25
41
58
90
121
155
12
3
5
9
15
21
35
50
77
103
132
RHW,
10
2
4
7
13
18
29
41
64
86
110
8
1
2
4
7
9
16
22
35
47
60
94
137
RHH
6
1
1
2
5
6
11
15
24
32
41
64
93
4
1
1
1
3
5
8
12
18
24
31
50
72
(with
3
1
1
1
3
4
7
10
16
22
28
44
63
outer
2
1
1
3
4
6
9
14
19
24
38
56
covering)
1
1
1
1
3
5
7
11
14
18
29
42
1/0
1
1
1
2
4
6
9
12
16
25
37
2/0
1
1
1
3
5
8
11
14
22
32
3/0
1
1
1
3
4
7
9
12
19
28
CHAPTER 9 - TABLES AND EXAMPLES
4/0
1
1
1
2
4
6
8
10
16
24
250
1
1
1
3
5
6
8
13
19
300
1
1
1
3
4
5
7
11
17
350
1
1
1
2
4
5
6
10
15
400
1
1
1
1
3
4
6
9
14
500
1
1
1
1
3
4
5
8
11
600
1
1
1
2
3
4
6
9
700
1
1
1
1
3
3
6
8
750
1
1
1
3
3
5
8
Note 1. This table is for concentric stranded conductors only. For cables with compact conductors, the dimensions in Table 5A shall be used.
Note 2. Conduit fill for conductors with a -2 suffix is the same as for those types without the suffix.
70-823
Tables 4 through 8, Chapter 9. Tables 4 through 8 give the nominal size of conductors and conduit or tubing for use in computing
size of conduit or tubing for various combinations of conductors. The dimensions represent average conditions only, and variations will
be found in dimensions of conductors and conduits of different manufacture.
70-824
Table 4. Dimensions and Percent Area of Conduit and of Tubing
Areas of Conduit or Tubing for the Combinations of Wires Permitted in Table 1, Chapter 9.
Area - Square Inches
Not Lead-Covered
Lead-Covered
Internal
Over 2
Over 4
Trade
Diameter
Total
2 Cond.
Cond.
1 Cond.
1 Cond.
2 Cond.
3 Cond.
4 Cond.
Cond.
Size
Inches
100%
31%
40%
53%
55%
30%
40%
38%
35%
½
.622
.30
.09
.12
.16
.17
.09
.12
.11
.11
3/4
.824
.53
.16
.21
.28
.29
.16
.21
.20
.19
1
1.049
.86
.27
.34
.46
.47
.26
.34
.33
.30
1½
1.380
1.50
.47
.60
.80
.83
.45
.60
.57
.53
1½
1.610
2.04
.63
.82
1.08
1.12
.61
.82
.78
.71
2
2.067
3.36
1.04
1.34
1.78
1.85
1.01
1.34
1.28
1.18
2½
2.469
4.79
1.48
1.92
2.54
2.63
1.44
1.92
1.82
1.68
3
3.068
7.38
2.26
2.95
3.91
4.06
2.21
2.95
2.80