Regl. 5293, art. 250-8 dup2
1; or
Cite as Reglamento Núm. 5293, Art. 250-8 dup2
(3) If the building or structure served has no grounding means, as
described in b(1) or b(2), to (1) an effectively grounded metal structure or
(2) to a ground rod or pipe not less than 5 feet (1.52 m) in length and ½ inch
(12.7 mm) in diameter, driven, where practicable, into permanently damp
earth and separated from lightning conductors as covered in Section 800-13
and at least 6 feet (1.83 m) from electrodes of other systems. Steam or hot
water pipes or lightning-rod conductors shall not be employed as electrodes for protectors.
(c) Electrode Connection. Connections to grounding electrodes shall
comply with Section 250-115. Connectors, clamps, fittings, or lugs used to
attach grounding conductors and bonding jumpers to grounding electrodes
or to each other that are to be concrete-encased or buried in the earth shall
be suitable for its application.
(d) Bonding of Electrodes. A bonding jumper not smaller than No. 6
copper or equivalent shall be connected between the communications
grounding electrode and power grounding electrode system at the building
or structure served where separate electrodes are used. Bonding together
of all separate electrodes shall be permitted.
Exception: At mobile homes as covered in Section 800-41.
(FPN No. 1): See Section 250-86 for use of lightning rods.
(FPN No. 2): Bonding together of all separate electrodes will limit potential differences between them and between their associated wiring systems.
70-798
NATIONAL ELECTRICAL CODE
800-41. Primary Protector Grounding and Bonding at Mobile Homes.
(a) Grounding. Where there is no mobile home service equipment
located in sight from and not more than 30 feet (9.14 m) from the exterior
wall of the mobile home it serves, or there is no mobile home disconnecting means grounded in accordance with Section 250-24 and located within
sight from and not more than 30 feet (9.14 m) from the exterior wall of the
mobile home it serves, the primary protector ground shall be in accordance
with Section 800-40(b)(2) and (3).
(b) Bonding. The primary protector grounding terminal or grounding
electrode shall be bonded to the metal frame or available grounding terminal of the mobile home with a copper grounding conductor not smaller than
No. 12 under any of the following conditions:
(1) Where there is no mobile home service equipment or disconnecting means as in (a) above or;
(2) The mobile home is supplied by cord and plug.
E. Conductors Within Buildings
800-49. Fire Resistance of Communications Wires and Cables. Communications wires and cables installed as wiring within a building shall be
listed as being resistant to the spread of fire in accordance with Sections
800-50 and 800-51.
800-50. Listing, Marking, and Installation of Communications Wires and
Cables. Communications wires and cables installed as wiring within
buildings shall be listed as being suitable for the purpose, marked in accordance with Table 800-50, and installed in accordance with Section 800-52.
The cable voltage rating shall not be marked on the cable.
(FPN): Voltage markings on cables may be misinterpreted to suggest that the
cables may be suitable for Class 1, electric light and power applications.
Exception No. 1: Voltage markings shall be permitted where the cable
has listings. multiple listings and voltage marking is required for one or more of the
Exception No. 2: Listing and marking shall not be required where the
cable enters the building from the outside and is continuously enclosed in
rigid metal conduit or intermediate metal conduit and such conduits are
grounded to an electrode in accordance with Section 800-40(b).
Exception No. 3: Listing and marking shall not be required where the
length of cable within the building does not exceed 50 feet (15.2 m) and the
cable enters the building from the outside and is terminated in an enclosure or on a listed primary protector.
(FPN No. 1): Splice cases or terminal boxes, both metallic and plastic types, are
typically used as enclosures for splicing or terminating telephone cables.
(FPN No. 2): This exception limits the length of unlisted outside plant cable to
50 feet (15.2 m), while Section 800-30(b) requires that the primary protector shall be
located as close as practicable to the point at which the cable enters the building.
Hence, in installations requiring a primary protector, the outside plant cable may not
be permitted to extend 50 feet (15.2 m) into the building if it is practicable to place
the primary protector closer than 50 feet (15.2 m) to the entrance point.
ARTICLE 800 - COMMUNICATIONS CIRCUITS
70-799
Exception No. 4: Multipurpose cables shall be considered as being suitable for the purpose and shall be permitted to substitute for communications cables as provided for in Section 800-53(f).
Table 800-50. Cable Markings
Cable
Marking
Type
Reference
MPP
Multipurpose plenum cable
Sections 800-51(g) and 800-53(a)
CMP
Communications plenum cable
Sections 800-51(a) and 800-53(a)
MPR
Multipurpose riser cable
Sections 800-51(g) and 800-53(b)
CMR
Communications riser cable
Sections 800-51(b) and 800-53(b)
MPG
Multipurpose general-
Sections 800-51(g) and 800-53(d)
purpose cable
CMG
Communications general-
Sections 800-51(c) and 800-53(d)
purpose cable
MP
Multipurpose general-
Sections 800-51(g) and 800-52(d)
purpose cable
CM
Communications general-
Sections 800-51(d) and 800-53(d)
purpose cable
CMX
Communications cable,
Sections 800-51(e) and 800-53(d),
limited use
Exception Nos. 1, 2, 3, and 4
CMUC
Undercarpet communications
Sections 800-51(f) and 800-53(d),
wire and cable
Exception No. 5
(FPN No. 1): Cable types are listed in descending order of fire resistance rating,
and multipurpose cables are listed above communications cables because multipurpose cables may substitute for communications cables.
(FPN No. 2): See the referenced sections for permitted uses.
800-51. Listing Requirements. Communications wires and cables shall
have a voltage rating of not less than 300 V and shall be listed in accordance with (a) through (i) below.
(FPN): See Section 800-4 for listing requirement for equipment.
(a) Type CMP. Type CMP communications plenum cable shall be listed
as being suitable for use in ducts, plenums, and other space used for environmental air and shall also be listed as having adequate fire-resistant and
low-smoke-producing characteristics.
(FPN): One method of defining low-smoke-producing cables is by establishing
an acceptable value of the smoke produced when tested in accordance with the Test
for Fire and Smoke Characteristics of Wires and Cables, NFPA 262-1990 (ANSI) to
a maximum peak optical density of 0.5 and a maximum average optical density of
0.15. Similarly, one method of defining fire-resistant cables is by establishing maximum allowable flame travel distance of 5 feet (1.52 m) when tested in accordance
with the same test.
(b) Type CMR. Type CMR communications riser cable shall be listed as
being suitable for use in a vertical run in a shaft and shall also be listed as
having fire-resistant characteristics capable of preventing the carrying of
fire from floor to floor.
70-800
NATIONAL ELECTRICAL CODE
(FPN): One method of defining fire-resistant characteristics capable of preventing the carrying of fire from floor to floor is that the cables pass the requirements of
the Standard Test for Flame Propagation Height of Electrical and Optical-Fiber
Cable Installed Vertically in Shafts, ANSI/UL 1666-1986.
(c) Type CMG. Type CMG general-purpose communications cable shall
be listed as being suitable for general-purpose communications use, with
the exception of risers and plenums, and shall also be listed as being resistant to the spread of fire.
(FPN): One method of defining resistant to the spread of fire is for the damage
(char length) not to exceed 4 feet 11 inches (1.5 m) when performing the "Vertical
Flame Test - - Cables in Cable Trays," as described in Test Methods for Electrical
Wires and Cables, CSA C22.2 No. 0.3-M 1985.
(d) Type CM. Type CM communications cable shall be listed as being
suitable for general purpose communications use, with the exception of
risers and plenums, and shall also be listed as being resistant to the spread
of fire.
(FPN): One method of defining resistant to the spread of fire is that the cables
do not spread fire to the top of the tray in the "Vertical-Tray Flame Test" in the
Reference 1581-1985. Standard for Electrical Wires, Cables and Flexible Cords, ANSI/UL
Another method of defining resistant to the spread of fire is for the damage (char
length) not to exceed 4 feet 11 inches (1.5 m) when performing the "Vertical Flame
Test-Cables in Cable Trays," as described in Test Methods for Electrical Wires
and Cables, CSA C22.2 No. 0.3-M-1985.
(e) Type CMX. Type CMX limited use communications cable shall be
listed as being suitable for use in dwellings and for use in raceway and shall
also be listed as being flame-retardant.
(FPN): One method of determining that cable is flame-retardant is by testing the
cable to the "VW-1 (Vertical-Wire) Flame Test" in the Reference Standard for
Electrical Wires, Cables and Flexible Cords, ANSI/UL 1581-1985.
(f) Type CMUC Undercarpet Wire and Cable. Type CMUC undercarpet
communications wire and cable shall be listed as being suitable for undercarpet use and shall also be listed as being flame-retardant.
(FPN): One method of determining that cable is flame-retardant is by testing the
cable to the "VW-1 (Vertical-Wire) Flame Test" in the Reference Standard for
Electrical Wires, Cables and Flexible Cords, ANSI/UL 1581-1985.
(g) Multipurpose (MP) Cables. Cables that meet the requirements for
Types CMP, CMR, CMG, and CM and also satisfy the requirements of
Sections 760-51(a) and (b) for multiconductor cables and Section 760-51(g)
for coaxial cables shall be permitted to be listed and marked as Types
MPP, MPR, MPG, and MP, respectively.
(h) Communications Wires. Communications wires, such as distributing frame wire and jumper wire, shall be listed as being resistant to the
spread of fire.
(FPN): One method of defining resistant to the spread of fire is that the cables
do not spread fire to the top of the tray in the "Vertical-Tray Flame Test" in the
Reference 1581-1985. Standard for Electrical Wires, Cables and Flexible Cords, ANSI/UL
ARTICLE 800 - COMMUNICATIONS CIRCUITS
70-801
Another method of defining resistant to the spread of fire is for the damage (char
length) not to exceed 4 feet 11 inches (1.5 m) when performing the "Vertical Flame
Test-Cables in Cable Trays," as described in Test Methods for Electrical Wires
and Cables, CSA C22.2 No. 0.3-M-1985.
(i) Hybrid Power and Communications Cable. Listed hybrid power and
communications cable shall be permitted where the power cable is a listed
Type NM conforming to the provisions of Article 336, and the communications cable is a listed Type CM, and the jackets on the listed NM and
listed CM cables are rated for 600 volts minimum, and the hybrid cable is
listed as being resistant to the spread of fire.
(FPN): One method of defining resistant to the spread of fire is that the cables
do not spread fire to the top of the tray in the "Vertical-Tray Flame Test" in the
Reference Standard for Electrical Wires, Cables and Flexible Cords, ANSI/UL
1581-1985.
Another method of defining resistant to the spread of fire is for the damage (char
length) not to exceed 4 feet 11 inches (1.5 m) when performing the "Vertical Flame
Test-Cables in Cable Trays," as described in Test Methods for Electrical Wires
and Cables, CSA C22.2 No. 0.3-M-1985.
800-52. Installation of Communications Wires, Cables, and Equipment.
Communications wires and cables from the protector to the equipment or,
where no protector is required, communications wires and cables attached
to the outside or inside of the building shall comply with (a) through (c)
below.
(a) Separation from Other Conductors.
(1) Open Conductors. Communications wires and cables shall be separated at least 2 inches (50.8 mm) from conductors of any electric light or
power circuits, Class 1, or nonpower-limited fire protective signaling circuits.
Exception No. 1: Where the electric light or power, Class 1, or
nonpower-limited fire protective signaling circuit conductors are in a raceway or in metal-sheathed, metal-clad, nonmetallic-sheathed, Type AC, or
Type UF cables.
Exception No. 2: Where the communications wires and cables are permanently separated from the conductors of the other circuit by a continuous and firmly fixed nonconductor, such as porcelain tubes or flexible
tubing, in addition to the insulation on the wire.
(2) In Raceways, Boxes, and Cables.
a. Other Power-Limited Circuits. Communications cables shall
be permitted in the same raceway or enclosure with cables of any of the
following:
1. Class 2 and Class 3 remote-control, signaling, and powerlimited circuits in compliance with Article 725.
2. Power-limited fire protective signaling systems in compliance
with Article 760.
3. Nonconductive and conductive optical fiber cables in compliance with Article 770.
4. Community antenna television and radio distribution systems
in compliance with Article 820.
70-802
NATIONAL ELECTRICAL CODE
b. Class 2 and Class 3 Circuits. Class 1 circuits shall not be run
in the same cable with communications circuits. Class 2 and Class 3 circuit conductors shall be permitted in the same cable with communications circuits, in which case the Class 2 and Class 3 circuits shall be
classified as communications circuits and shall meet the requirements of
this article. The cables shall be listed as communications cables or multipurpose cables.
Exception: Cables constructed of individually listed Class 2, Class 3, and
communications cables under a common jacket shall not be required to be
classified as communications cable. The fire resistance rating of the composite cable shall be determined by the performance of the composite cable.
c. Electric Light or Power Circuits.
1. Communications conductors shall not be placed in any raceway, compartment, outlet box, junction box, or similar fitting with conductors of electric light or power circuits or Class 1 circuits.
Exception No. 1: Where all of the conductors of electric light or power,
Class 1, or nonpower-limited fire protective signaling circuits are separated from all of the conductors of communications circuits by a barrier.
Exception No. 2: Electric light or power, Class 1, or nonpower-limited
fire protective signaling circuit conductors in outlet boxes, junction boxes,
or similar fittings or compartments where such conductors are introduced
solely for power supply to communications equipment or for connection to
remote-control equipment. The electric light or power, Class 1, or
nonpower-limited fire protective signaling circuit conductors shall be
routed within the enclosure to maintain a minimum of 0.25 inch (6.35 mm)
separation from the communications circuit conductors.
2. In shafts. Communications wires and cables run in the same
shaft with conductors of electric light or power, Class 1, or nonpowerlimited fire protective signaling circuits shall be separated from light or
power conductors, Class 1, or nonpower-limited fire protective signaling circuit conductors by not less than 2 inches (50.8 mm).
Exception No. 1: Where either (1) all of the conductors of the electric
light or power, Class 1 or nonpower-limited fire protective signaling circuits, or (2) all of the conductors of communications circuits are encased
in raceway.
Exception No. 2: Where the electric light or power, Class 1 or
nonpower-limited fire protective signaling conductors are in a raceway, or
in metal-sheathed, metal-clad, nonmetallic-sheathed, or Type UF cables.
ARTICLE 800 - COMMUNICATIONS CIRCUITS
70-803
(b) Spread of Fire or Products of Combustion. Installations in hollow
spaces, vertical shafts, and ventilation or air-handling ducts shall be so
made that the possible spread of fire or products of combustion will not be
substantially increased. Openings around penetrations through fire
resistance-rated walls, partitions, floors, or ceilings shall be firestopped
using approved methods.
(c) Equipment in Other Space Used for Environmental Air. Section
300-22(c) shall apply.
(d) Cable Trays. Types MPP, MPR, MPG, and MP multipurpose cables
and Types CMP, CMR, CMG, and CM communications cables shall be
permitted to be installed in cable trays.
(e) Support of Conductors. Raceways shall not be used as a means of
support for communications wires and cables.
800-53. Applications of Listed Communications Wires and Cables.
Communications wires and cables shall comply with (a) through (f) below.
(a) Plenum. Cables installed in ducts, plenums, and other spaces used
for environmental air shall be Type CMP.
Exception: Types CMP, CMR, CMG, CM, and CMX and communications wire installed in compliance with Section 300-22.
(b) Riser. Cables installed in vertical runs and penetrating more than
one floor, or cables installed in vertical runs in a shaft, shall be Type CMR.
Floor penetrations requiring Type CMR shall contain only cables suitable
for riser or plenum use.
(FPN): See Section 800-52(b) for firestop requirements for floor penetrations.
Exception No. 1: Where the listed cables are encased in metal raceway
or are located in a fireproof shaft having firestops at each floor.
Exception No. 2: Types CM and CMX cable in one- and two-family
dwellings.
(c) Distributing Frames and Cross-Connect Arrays. Communications
wires shall be used in distributing frames and cross-connect arrays.
Exception: Types CMP, CMR, CMG, and CM are permitted to be used.
(d) Other Wiring Within Buildings. Cables installed in building locations
other than the locations covered in (a), (b), and (c) above shall be Type
CMG or Type CM.
Exception No. 1: Where listed communications wires and cables are
enclosed in raceway.
Exception No. 2: Type CMX communications cable in nonconcealed
spaces where the exposed length of cable does not exceed 10 feet (3.05 m).
Exception No. 3: Type CMX communications cables that are less than
0.25 inch (6.35 mm) in diameter and installed in one- or two-family dwellings.
Exception No. 4: Type CMX communications wires and cables that are
less than 0.25 inch (6.35 mm) in diameter and installed in nonconcealed
spaces in multifamily dwellings.
Exception No. 5: Type CMUC undercarpet communications wires and
cables installed under carpet.
70-804
NATIONAL ELECTRICAL CODE
(e) Hybrid Power and Communications Cable. Hybrid power and communications cable listed in accordance with Section 800-51(i) shall be permitted to be installed in one-and two-family dwellings.
(f) Cable Substitutions. Substitutions for communications cables listed
in Table 800-53 and illustrated in Figure 800-53 shall be permitted.
Table 800-53. Cable Substitutions
Cable Type
Permitted Substitutions
MPP
None
CMP
MPP
MPR
MPP
CMR
MPP, CMP, MPR
MPG, MP
MPP, MPR
CMG, CM
MPP, CMP, MPR, CMR, MPG, MP
CMX
MPP, CMP, MPR, CMR, MPG,
MP, CMG, CM
(FPN): For the use of communications cable and multipurpose cable in place of
Class 2 or Class 3 cables, see Section 725-53(g), and, for the use of communications
cable and multipurpose cable in place of power-limited fire protective signaling
cables, see Section 760-53(d). The permitted cable substitutions are illustrated in
Figure 800-53.
MPP
CMP
CL3P
FPLP
CL2P
Plenum
MPR
CMR
CL3R
FPLR
CL2R
Riser
MPG
MP
CMG
PLTC
CM
CL3
FPL
General
Purpose
CL2
CMX
CL3X
A
B
Cable A
Dwellings
Shall be Permitted
to be Used in
CL2X
Place of Cable B
Type CM - Communications Wires and Cables
A
B
Types CL2 and CL3 - Class 2 and Class 3 Remote-Control,
Cable A
Shall be Permitted
Signaling, and Power-Limited Cables
to be Used in
Type FPL - Power-Limited Fire Protective Signaling Cables
Place of Cable B
Type MP - Multipurpose Cables
with Restrictions.
Type PLTC - - Power-Limited Tray Cable
See Sec. 760-51
(a), (b), and (g)
Figure 800-53. Cable Substitution Hierarchy