Regl. 5293, art. 300
3, are installed in a common raceway or cable, the derating
Cite as Reglamento Núm. 5293, Art. 300
factors shown above shall apply to the number of power and lighting (Articles 210, 215, 220, and 230) conductors only.
Exception No. 2: For conductors installed in cable trays, the provisions
of Section 318-11 shall apply.
Exception No. 3: Derating factors shall not apply to conductors in nipples having a length not exceeding 24 inches (610 mm).
Exception No. 4: Derating factors shall not apply to underground conductors entering or leaving an outdoor trench if those conductors have
physical protection in the form of rigid metal conduit, intermediate metal
conduit, or rigid nonmetallic conduit having a length not exceeding 10 feet
(3.05 m) above grade and the number of conductors does not exceed four.
Exception No. 5: For other loading conditions, adjustment factors and
ampacities shall be permitted to be calculated under Section 310-15(b).
(FPN): See Appendix B, Table B-310-11 for adjustment factors for more than
three current-carrying conductors in a raceway or cable with load diversity.
(b) More than One Conduit, Tube, or Raceway. Spacing between conduits, tubing, or raceways shall be maintained.
9. Overcurrent Protection. Where the standard ratings and settings of
overcurrent devices do not correspond with the ratings and settings
allowed for conductors, the next higher standard rating and setting shall be
permitted.
Exception: As limited in Section 240-3.
70-180
NATIONAL ELECTRICAL CODE
10. Neutral Conductor.
(a) A neutral conductor that carries only the unbalanced current from
other conductors of the same circuit need not be counted when applying
the provisions of Note 8.
(b) In a 3-wire circuit consisting of 2-phase wires and the neutral of a
4-wire, 3-phase wye-connected system, a common conductor carries
approximately the same current as the other conductors and shall be
counted when applying the provisions of Note 8.
(c) On a 4-wire, 3-phase wye circuit where the major portion of the
load consists of nonlinear loads such as electric-discharge lighting, electronic computer/data processing, or similar equipment, there are harmonic
currents present in the neutral conductor, and the neutral shall be considered to be a current-carrying conductor.
11. Grounding or Bonding Conductor. A grounding or bonding conductor shall not be counted when applying the provisions of Note 8.
Table 310-61. Conductor Application and Insulation
Maximum
Trade
Type
Operating
Application
Outer
Name
Letter
Temperature
Provision
Insulation
Covering
Medium
MV-75*
75° C
Dry or wet
Thermoplastic
Jacket,
voltage
MV-85*
85° C
locations
or
Sheath,
solid
MV-90*
90° C
rated 2001
Thermosetting
or Armor
dielectric
volts and
higher
*Insulation and outer coverings that meet the requirements as flame-retardant limitedsmoke and are so listed shall be permitted to be designated limited-smoke with the suffix LS
after the Code type designation.
Table 310-62. Thickness of Insulation for 601-2000-Volt
Nonshielded Types RHH and RHW, in Mils
Conductor Size
AWG-kcmil
A
B
14-10
80
60
8
80
70
6-2
95
70
1-2/0
110
90
3/0-4/0
110
90
213-500
125
105
501-1000
140
120
Note: Column A insulations are limited to natural, SBR, and butyl rubbers.
Note: Column B insulations are materials such as cross-linked polyethylene, ethylene
propylene rubber, and composites thereof.
Table 310-63. Thickness of Insulation and Jacket for Nonshielded Solid
Dielectric Insulated Conductors Rated 2001 to 8000 Volts, in Mils
5001-8000 Volts 100 Percent
Conductor-Size
Insulation Level Wet or Dry
AWG-kcmil
2001-5000 Volts
Locations
Multi-
Dry Locations Single Conductor
Wet or Dry Locations
Single Conductor
Conductor*
Without
Multi-
Jacket
With Jacket
Single Conductor
Conductor*
Insulation
Insulation
Jacket
Insulation
Jacket
Insulation
Insulation
Jacket
Insulation
8
110
90
30
125
80
90
180
80
180
6
110
90
30
125
80
90
180
80
180
4-2
110
90
45
125
80
90
180
95
180
1-2/0
110
90
45
125
80
90
180
95
180
3/0-4/0
110
90
65
125
95
90
180
110
180
ARTICLE 310 - CONDUCTORS FOR GENERAL WIRING
213-500
120
90
65
140
110
90
210
110
210
501-750
130
90
65
155
125
90
235
125
235
751-1000
130
90
65
155
125
90
250
140
250
*Note: Under a common overall covering such as a jacket, sheath, or armor.
70-181
70-182
NATIONAL ELECTRICAL CODE
Table 310-64. Thickness of Insulation for Shielded Solid Dielectric
Insulated Conductors Rated 2001 to 35,000 Volts, in Mils
Conductor
2001-
Size
5000
25,001-
28,001-
AWG-kcmil
Volts
5001-8000
8001-15,000
15,001-25,000
28,000
35,000
100
133
100
133
100
133
100
100
Per-
Per-
Per-
Per-
Per-
Per-
Per-
Percent
cent
cent
cent
cent
cent
cent
cent
insuinsu-
insuinsu-
insuinsu-
insuinsu-
lation
lation
lation
lation
lation
lation
lation
lation
level
level
level
level
level
level
level
level
8
90
-
-
-
-
-
-
-
-
6-4
90
115
140
-
-
-
-
-
-
2
90
115
140
175
215
-
-
-
-
1
90
115
140
175
215
260
345
280
-
1/0-1000
90
115
140
175
215
260
345
280
345
*Definitions:
100 Percent Insulation Level. Cables in this category shall be permitted
to be applied where the system is provided with relay protection such that
ground faults will be cleared as rapidly as possible but, in any case, within
1 minute. While these cables are applicable to the great majority of cable
installations that are on grounded systems, they shall be permitted to be
used also on other systems for which the application of cables is acceptable, provided the above clearing requirements are met in completely
deenergizing the faulted section.
133 Percent Insulation Level. This insulation level corresponds to that
formerly designated for ungrounded systems. Cables in this category shall
be permitted to be applied in situations where the clearing time requirements of the 100 percent level category cannot be met, and yet there is
adequate assurance that the faulted section will be deenergized in a time
not exceeding 1 hour. Also, they shall be permitted to be used where additional insulation strength over the 100 percent level category is desirable.
ARTICLE 310 - CONDUCTORS FOR GENERAL WIRING
70-183
Table 310-67. Ampacities of Insulated Single Copper Conductor Cables
Triplexed in Air Based on Conductor Temperature of 90°C (194°F)
and Ambient Air Temperature of 40°C (104°F)
Conductor Size
2001-5000 Volts
5001-35,000 Volts
AWG-kcmil
Ampacity
Ampacity
8
65
-
6
90
100
4
120
130
2
160
170
1
185
195
1/0
215
225
2/0
250
260
3/0
290
300
4/0
335
345
250
375
380
350
465
470
500
580
580
750
750
730
1000
880
850
Table 310-68. Ampacities of Insulated Single Aluminum Conductor Cables
Triplexed in Air Based on Conductor Temperature of 90°C (194°F)
and Ambient Air Temperature of 40°C (104°F)
Conductor Size
2001-5000 Volts
5001-35,000 Volts
AWG-kcmil
Ampacity
Ampacity
8
50
-
6
70
75
4
90
100
2
125
130
1
145
150
1/0
170
175
2/0
195
200
3/0
225
230
4/0
265
270
250
295
300
350
365
370
500
460
460
750
600
590
1000
715
700
70-184
NATIONAL ELECTRICAL CODE
Table 310-69. Ampacities of Insulated Single Copper Conductor Isolated
in Air Based on Conductor Temperature of 90°C (194°F)
and Ambient Air Temperature of 40°C (104°F)
Conductor Size
2001-5000 Volts
5001-15,000 Volts
15,001-35,000 Volts
AWG-kcmil
Ampacity
Ampacity
Ampacity
8
83
-
-
6
110
110
-
4
145
150
-
2
190
195
I
1
225
225
225
1/0
260
260
260
2/0
300
300
300
3/0
345
345
345
4/0
400
400
395
250
445
445
440
350
550
550
545
500
695
685
680
750
900
885
870
1000
1075
1060
1040
1250
1230
1210
1185
1500
1365
1345
1315
1750
1495
1470
1430
2000
1605
1575
1535
Table 310-70. Ampacities of Insulated Single Aluminum Conductor
Isolated in Air Based on Conductor Temperature of 90°C (194°F)
and Ambient Air Temperature of 40°C (104°F)
Conductor Size
2001-5000 Volts
5001-15,000 Volts
15,001-35,000 Volts
AWG-kcmil
Ampacity
Ampacity
Ampacity
8
64
-
-
6
85
87
-
4
115
115
-
2
150
150
-
1
175
175
175
1/0
200
200
200
2/0
230
235
230
3/0
270
270
270
4/0
310
310
310
250
345
345
345
350
430
430
430
500
545
535
530
750
710
700
685
1000
855
840
825
1250
980
970
950
1500
1105
1085
1060
1750
1215
1195
1165
2000
1320
1295
1265
ARTICLE 310 - CONDUCTORS FOR GENERAL WIRING
70-185
Table 310-71. Ampacities of an Insulated Three-Conductor Copper
Cable Isolated in Air Based on Conductor Temperature of 90°C (194°F)
and Ambient Air Temperature of 40°C (104°F)
Conductor Size
2001-5000 Volts
5001-35,000 Volts
AWG-kcmil
Ampacity
Ampacity
8
59
-
6
79
93
4
105
120
2
140
165
1
160
185
1/0
185
215
2/0
215
245
3/0
250
285
4/0
285
325
250
320
360
350
395
435
500
485
535
750
615
670
1000
705
770
Table 310-72. Ampacities of an Insulated Three-Conductor Aluminum
Cable Isolated in Air Based on Conductor Temperature of 90°C (194°F)
and Ambient Air Temperature of 40°C (104°F)
Conductor Size
2001-5000 Volts
5001-35,000 Volts
AWG-kcmil
Ampacity
Ampacity
8
46
-
6
61
72
4
81
95
2
110
125
1
125
145
1/0
145
170
2/0
170
190
3/0
195
220
4/0
225
255
250
250
280
350
310
345
500
385
425
750
495
540
1000
585
635
70-186
NATIONAL ELECTRICAL CODE
Table 310-73. Ampacities of an Insulated Triplexed or Three Single
Conductor Copper Cables in Isolated Conduit in Air
Based on Conductor Temperature of 90°C (194°F)
and Ambient Air Temperature of 40°C (104°F)
Conductor Size
2001-5000 Volts
5001-35,000 Volts
AWG-kcmil
Ampacity
Ampacity
8
55
-
6
75
83
4
97
110
2
130
150
1
155
170
1/0
180
195
2/0
205
225
3/0
240
260
4/0
280
295
250
315
330
350
385
395
500
475
480
750
600
585
1000
690
675
Table 310-74. Ampacities of Insulated Triplexed or Three Single
Conductor Aluminum Cables in Isolated Conduit in Air
Based on Conductor Temperature of 90°C (194°F)
and Ambient Air Temperature of 40°C (104°F)
Conductor Size
2001-5000 Volts
5001-35,000 Volts
AWG-kcmil
Ampacity
Ampacity
8
43
-
6
58
65
4
76
84
2
100
115
1
120
130
1/0
140
150
2/0
160
175
3/0
190
200
4/0
215
230
250
250
255
350
305
310
500
380
385
750
490
485
1000
580
565
ARTICLE 310 - CONDUCTORS FOR GENERAL WIRING
70-187
Table 310-75. Ampacities of an Insulated Three-Conductor
Copper Cable in Isolated Conduit in Air
Based on Conductor Temperature of 90°C (194°F)
and Ambient Air Temperature of 40°C (104°F)
Conductor Size
2001-5000 Volts
5001-35,000 Volts
AWG-kcmil
Ampacity
Ampacity
8
52
-
6
69
83
4
91
105
2
125
145
1
140
165
1/0
165
195
2/0
190
220
3/0
220
250
4/0
255
290
250
280
315
350
350
385
500
425
470
750
525
570
1000
590
650
Table 310-76. Ampacities of an Insulated Three-Conductor
Aluminum Cable in Isolated Conduit in Air
Based on Conductor Temperature of 90°C (194°F)
and Ambient Air Temperature of 40°C (104°F)
Conductor Size
2001-5000 Volts
5001-35,000 Volts
AWG-kcmil
Ampacity
Ampacity
8
41
-
6
53
64
4
71
84
2
96
115
1
110
130
1/0
130
150
2/0
150
170
3/0
170
195
4/0
200
225
250
220
250
350
275
305
500
340
380
750
430
470
1000
505
550
70-188
NATIONAL ELECTRICAL CODE
Table 310-77. Ampacities of Three Single Insulated Copper Conductors
in Underground Electrical Ducts (Three Conductors per Electrical Duct)
Based on Ambient Earth Temperature of 20°C (68°F), Electrical Duct
Arrangement per Figure 310-1, 100 percent Load Factor,
Thermal Resistance (RHO) of 90, Conductor Temperature 90°C (194°F)
One Circuit
(See Figure 310-1,
Detail 1)
Size
2001-5000 Volts
5001-35,000 Volts
AWG-kcmil
Ampacity
Ampacity
8
64
6
85
90
4
110
115
2
145
155
1
170
175
1/0
195
200
2/0
220
230
3/0
250
260
4/0
290
295
250
320
325
350
385
390
500
470
465
750
585
565
1000
670
640
Three Circuits
(See Figure 310-1,
Detail 2)
Size
8
56
6
73
77
4
95
99
2
125
130
1
140
145
1/0
160
165
2/0
185
185
3/0
210
210
4/0
235
240
250
260
260
350
315
310
500
375
370
750
460
440
1000
525
495
Six Circuits
(See Figure 310-1,
Detail 3)
Size
8
48
6
62
64
4
80
82
2
105
105
1
115
120
1/0
135
135
2/0
150
150
3/0
170
170
4/0
195
190
250
210
210
350
250
245
500
300
290
750
365
350
1000
410
390
ARTICLE 310 - CONDUCTORS FOR GENERAL WIRING
70-189
Table 310-78. Ampacities of Three Single Insulated Aluminum Conductors
in Underground Electrical Ducts (Three Conductors per Electrical Duct)
Based on Ambient Earth Temperature of 20°C (68°F), Electrical Duct
Arrangement per Figure 310-1, 100 percent Load Factor,
Thermal Resistance (RHO) of 90, Conductor Temperature of 90°C (194°F)
One Circuit
(See Figure 310-1,
Detail 1)
Size
2001-5000 Volts
5001-35,000 Volts
AWG-kcmil
Ampacity
Ampacity
8
50
-
6
66
70
4
86
91
2
115
120
1
130
135
1/0
150
155
2/0
170
175
3/0
195
200
4/0
225
230
250
250
250
350
305
305
500
370
370
750
470
455
1000
545
525
Three Circuits
(See Figure 310-1,
Detail 2)
Size
8
44
-
6
57
60
4
74
77
2
96
100
1
110
110
1/0
125
125
2/0
145
145
3/0
160
165
4/0
185
185
250
205
200
350
245
245
500
295
290
750
370
355
1000
425
405
Six Circuits
(See Figure 310-1,
Detail 3)
Size
8
38
-
6
48
50
4
62
64
2
80
80
1
91
90
1/0
105
105
2/0
115
115
3/0
135
130
4/0
150
150
250
165
165
350
195
195
500
240
230
750
290
280
1000
335
320
70-190
NATIONAL ELECTRICAL CODE
Table 310-79. Ampacities of Three Insulated Copper Conductors Cabled
within an Overall Covering (Three-Conductor Cable) in
Underground Electrical Ducts (One Cable per Electrical Duct)
Based on Ambient Earth Temperature of 20°C (68°F), Electrical Duct
Arrangement per Figure 310-1, 100 percent Load Factor,
Thermal Resistance (RHO) of 90, Conductor Temperature 90°C (194°F)
One Circuit
(See Figure 310-1,
Detail 1)
Size
2001-5000 Volts
5001-35,000 Volts
AWG-kcmil
Ampacity
Ampacity
8
59
-
6
78
88
4
100
115
2
135
150
1
155
170
1/0
175
195
2/0
200
220
3/0
230
250
4/0
265
285
250
290
310
350
355
375
500
430
450
750
530
545
1000
600
615
Three Circuits
(See Figure 310-1,
Detail 2)
Size
8
53
-
6
69
75
4
89
97
2
115
125
1
135
140
1/0
150
160
2/0
170
185
3/0
195
205
4/0
225
230
250
245
255
350
295
305
500
355
360
750
430
430
1000
485
485
Six Circuits
(See Figure 310-1,
Detail 3)
Size
8
46
-
6
60
63
4
77
81
2
98
105
1
110
115
1/0
125
130
2/0
145
150
3/0
165
170
4/0
185
190
250
200
205
350
240
245
500
290
290
750
350
340
1000
390
380
ARTICLE 310 - CONDUCTORS FOR GENERAL WIRING
70-191
Table 310-80. Ampacities of Three Insulated Aluminum Conductors
Cabled within an Overall Covering (Three-Conductor Cable) in
Underground Electrical Ducts (One Cable per Electrical Duct)
Based on Ambient Earth Temperature of 20°C (68°F), Electrical Duct
Arrangement per Figure 310-1, 100 percent Load Factor,
Thermal Resistance (RHO) of 90, Conductor Temperature 90°C (194°F)
One Circuit
(See Figure 310-1,
Detail 1)
Size
2001-5000 Volts
5001-35,000 Volts
AWG-kcmil
Ampacity
Ampacity
8
46
-
6
61
69
4
80
89
2
105
115
1
120
135
1/0
140
150
2/0
160
170
3/0
180
195
4/0
205
220
250
230
245
350
280
295
500
340
355
750
425
440
1000
495
510
Three Circuits
(See Figure 310-1,
Detail 2)
Size
8
41
6
54
59
4
70
75
2
90
100
1
105
110
1/0
120
125
2/0
135
140
3/0
155
160
4/0
175
180
250
190
200
350
230
240
500
280
285
750
345
350
1000
400
400
Six Circuits
(See Figure 310-1,
Detail 3)
Size
8
36
-
6
46
49
4
60
63
2
77
80
1
87
90
1/0
99
105
2/0
110
115
3/0
130
130
4/0
145
150
250
160
160
350
190
190
500
230
230
750
280
275
1000
320
315
70-192
NATIONAL ELECTRICAL CODE
Table 310-81. Ampacities of Single Insulated Copper Conductors
Directly Buried in Earth
Based on Ambient Earth Temperature of 20°C (68°F),
Arrangement per Figure 310-1, 100 percent Load Factor,
Thermal Resistance (RHO) of 90, Conductor Temperature 90°C (194°F)
Conductor Size
2001-5000 Volts
5001-35,000 Volts
AWG-kcmil
Ampacity
Ampacity
One Circuit-
3 Conductors
(See Figure 310-1,
Detail 9)
8
110
6
140
130
4
180
170
2
230
210
1
260
240
1/0
295
275
2/0
335
310
3/0
385
355
4/0
435
405
250
470
440
350
570
535
500
690
650
750
845
805
1000
980
930
Two Circuits-
6 Conductors
(See Figure 310-1,
Detail 10)
8
100
I
6
130
120
4
165
160
2
215
195
1
240
225
1/0
275
255
2/0
310
290
3/0
355
330
4/0
400
375
250
435
410
350
520
495
500
630
600
750
775
740
1000
890
855
For SI units: one inch = 25.4 millimeters.
ARTICLE 310 - CONDUCTORS FOR GENERAL WIRING
70-193
Table 310-82. Ampacities of Single Insulated Aluminum Conductors
Directly Buried in Earth
Based on Ambient Earth Temperature of 20°C (68°F),
Arrangement per Figure 310-1, 100 percent Load Factor,
Thermal Resistance (RHO) of 90, Conductor Temperature 90°C (194°F)
Conductor Size
2001-5000 Volts
5001-35,000 Volts
AWG-kcmil
Ampacity
Ampacity
One Circuit-
3 Conductors
(See Figure 310-1,
Detail 9)
8
85
-
6
110
100
4
140
130
2
180
165
1
205
185
1/0
230
215
2/0
265
245
3/0
300
275
4/0
340
315
250
370
345
350
445
415
500
540
510
750
665
635
1000
780
740
Two Circuits—
6 Conductors
(See Figure 310-1,
Detail 10)
8
80
6
100
95
4
130
125
2
165
155
1
190
175
1/0
215
200
2/0
245
225
3/0
275
255
4/0
310
290
250
340
320
350
410
385
500
495
470
750
610
580
1000
710
680
For SI units: one inch = 25.4 millimeters.
70-194
NATIONAL ELECTRICAL CODE
Table 310-83. Ampacities of Three Insulated Copper Conductors
Cabled within an Overall Covering (Three-Conductor Cable),
Directly Buried in Earth
Based on Ambient Earth Temperature of 20°C (68°F),
Arrangement per Figure 310-1, 100 percent Load Factor,
Thermal Resistance (RHO) of 90, Conductor Temperature 90°C (194°F)
Conductor Size
2001-5000 Volts
5001-35,000 Volts
AWG-kcmil
Ampacity
Ampacity
One Circuit
(See Figure 310-1,
Detail 5)
8
85
6
105
115
4
135
145
2
180
185
1
200
210
1/0
230
240
2/0
260
270
3/0
295
305
4/0
335
350
250
365
380
350
440
460
500
530
550
750
650
665
1000
730
750
Two Circuits
(See Figure 310-1,
Detail 10)
8
80
-
6
100
105
4
130
135
2
165
170
1
185
195
1/0
215
220
2/0
240
250
3/0
275
280
4/0
310
320
250
340
350
350
410
420
500
490
500
750
595
605
1000
665
675
For SI units: one inch = 25.4 millimeters.
ARTICLE 310 - CONDUCTORS FOR GENERAL WIRING
70-195
Table 310-84. Ampacities of Three Insulated Aluminum Conductors
Cabled within an Overall Covering (Three-Conductor Cable),
Directly Buried in Earth
Based on Ambient Earth Temperature of 20°C (68°F),
Arrangement per Figure 310-1, 100 percent Load Factor,
Thermal Resistance (RHO) of 90, Conductor Temperature 90°C (194°F)
Conductor Size
2001-5000 Volts
5001-35,000 Volts
AWG-kcmil
Ampacity
Ampacity
One Circuit
(See Figure 310-1,
Detail 5)
8
65
-
6
80
90
4
105
115
2
140
145
1
155
165
1/0
180
185
2/0
205
210
3/0
230
240
4/0
260
270
250
285
300
350
345
360
500
420
435
750
520
540
1000
600
620
Two Circuits
(See Figure 310-1,
Detail 6)
8
60
-
6
75
80
4
100
105
2
130
135
1
145
150
1/0
165
170
2/0
190
195
3/0
215
220
4/0
245
250
250
265
275
350
320
330
500
385
395
750
480
485
1000
550
560
For SI units: one inch = 25.4 millimeters.
70-196
NATIONAL ELECTRICAL CODE
Notes to Tables 310-69 through 310-84
(FPN): For ampacities calculated in accordance with the following Notes 1
and 2, reference IEEE/ICEA "Power Cable Ampacities," Vol. I and II (IPCEA
Pub. No. P-46-426) and the "References" therein for availability of all factors
and constants.
1. Ambients Not in Tables. Ampacities at ambient temperatures other
than those shown in the tables shall be determined by means of the following formula:
I₂ = I₁ TC - TA2 - DELTA TD
TC - TA₁ - DELTA TC
Where:
I₁ = Ampacity from tables at ambient TA₁.
I₂ = Ampacity at desired ambient TA2.
TC = Conductor temperature in degrees C.
TA₁ = Surrounding ambient from tables in degrees C.
TA2 = Desired ambient in degrees C.
DELTA TD = Dielectric loss temperature rise.
2. Grounded Shields. Ampacities shown in Tables 310-69, 310-70, 310-
81, and 310-82 are for cable with shields grounded at one point only. Where
shields are grounded at more than one point, ampacities shall be adjusted
to take into consideration the heating due to shield currents.
3. Electrical Duct Bank Configuration. Ampacities shown in Tables 310-
77, 310-78, 310-79, and 310-80 shall apply only where the cables are located
in the outer electrical ducts of the electrical duct bank. Ampacities for
cables located in the inner electrical ducts of the electrical duct bank shall
be determined by special calculations.
4. Burial Depth of Underground Circuits. For applications where burial
depths must be deeper than shown in the underground ampacity tables, the
following ampacity derating factor shall be permitted to be used: 6 percent per increased foot of depth for all values of Rho. No rating change is
required where the burial depth is decreased.
5. Thermal Resistivity. Thermal resistivity, as used in this Code, refers
to the heat transfer capability through a substance by conduction. It is the
reciprocal of thermal conductivity and is designated Rho and expressed in
the units °C-cm/watt.
6. Electrical Ducts Utilized in Figure 310-1. Spacings between electrical
ducts (raceways) as defined in Figure 310-1 shall be permitted to be less
than specified in Figure 310-1, where ducts (raceways) enter equipment
enclosures from underground, without reducing the ampacity of conductors contained within such ducts (raceways).
ARTICLE 310 - CONDUCTORS FOR GENERAL WIRING
70-197
4
7.5"
Detail 1
7.5" 7.5"
V
7.5" 7.5",7.5"
11.5"x11.5"
Electrical duct bank
7.5"
One electrical duct
D
Detail 2
7.5
7.51
7.5
19"x19"
Electrical duct bank
Detail 3
Detail 4
Three electrical ducts
19"x27"
27"x27"
Electrical duct bank
Electrical duct bank
Or
Six electrical ducts
Nine electrical ducts
Or
0
,
=
7.5'
7.5
7.5
.5
27"x11.5"
Electrical duct bank
Three electrical ducts
7.5
7.5
27"x19"
Electrical duct bank
Six electrical ducts
24"
24"
Detail 5
Detail 6
Detail 7
Detail 8
Buried 3
Buried 3
Buried triplexed
Buried triplexed cables
conductor
conductor
cables (1 circuit)
(2 circuits)
cable
cables
7.5"
7.5
7.5"
7.5
24"
7.5"
7.5"
Detail 9
Detail 10
Buried single conductor
Buried single conductor
cables (1 circuit)
cables (2 circuits)
Notes for all details:
Legend
1. Minimum burial depths to top electrical ducts or cables shall
be in accordance with Section 710-4(b). Maximum depth to the top
Backfill
of electrical duct banks shall be 30 inches and maximum depth to
(earth or concrete)
the top of direct buried cables shall be 36 inches.
Electrical duct
2. Burial depths shall be permitted to be increased in part(s) of
the duct run to avoid underground obstructions without
Cable or cables
decreasing the rated ampacity of the conductors. The total
length of parts of the duct run increased in depth to avoid
obstructions must be less than 25 percent of the total run
length, or else the ampacity reduction factor of Note 4 of Tables
310-69 through 310-84 shall be applied.
3. For SI units: one inch = 25.4 millimeters; one foot = 305 millimeters.
Figure 310-1. Cable Installation Dimensions for Use with Tables 310-77 through 310-84.
70-198
NATIONAL ELECTRICAL CODE