Regl. 5293, art. 300-17-520 dup2
THEATERS AND SIMILAR LOCATIONS
Cite as Reglamento Núm. 5293, Art. 300-17-520 dup2
70-565
wireway, the sum of the cross-sectional areas of all contained conductors at any cross section shall not exceed 20 percent of the interior
cross-sectional area of the auxiliary gutter or wireway. The thirtyconductor limitation of Sections 362-5 and 374-5 shall not apply.
520-6. Enclosing and Guarding Live Parts. Live parts shall be enclosed
or guarded to prevent accidental contact by persons and objects. All
switches shall be of the externally operable type. Dimmers, including rheostats, shall be placed in cases or cabinets that enclose all live parts.
520-7. Emergency Systems. Control of emergency systems shall comply
with Article 700, Emergency Systems.
520-8. Branch Circuits. A branch circuit of any size supplying one or
more receptacles shall be permitted to supply stage set lighting. The voltage rating of the receptacles shall not be less than the circuit voltage.
Receptacle ampere ratings and branch-circuit conductor ampacity shall not
be less than the branch-circuit overcurrent device ampere rating. Table
210-21(b)(2) shall not apply.
B. Fixed Stage Switchboard
520-21. Dead Front. Stage switchboards shall be of the dead-front type
and shall comply with Part C of Article 384 unless approved based on suitability as a stage switchboard as determined by a qualified testing laboratory and recognized test standards and principles.
520-22. Guarding Back of Switchboard. Stage switchboards having
exposed live parts on the back of such boards shall be enclosed by the
building walls, wire mesh grills, or by other approved methods. The
entrance to this enclosure shall be by means of a self-closing door.
520-23. Control and Overcurrent Protection of Receptacle Circuits.
Means shall be provided at a stage lighting switchboard to which load circuits are connected for overcurrent protection of stage lighting branch circuits, including branch circuits supplying stage and auditorium receptacles
used for cord- and plug-connected stage equipment. Where the stage
switchboard contains dimmers to control nonstage lighting, the locating of
the overcurrent protective devices for these branch circuits at the stage
switchboard shall be permitted.
520-24. Metal Hood. A stage switchboard that is not completely enclosed
dead-front and dead-rear or recessed into a wall shall be provided with a
metal hood extending the full length of the board to protect all equipment
on the board from falling objects.
520-25. Dimmers. Dimmers shall comply with (a) through (d) below.
(a) Disconnection and Overcurrent Protection. Where dimmers are
installed in ungrounded conductors, each dimmer shall have overcurrent
protection not greater than 125 percent of the dimmer rating, and shall be
70-566
NATIONAL ELECTRICAL CODE
disconnected from all ungrounded conductors when the master or individual switch or circuit breaker supplying such dimmer is in the open position.
(b) Resistance- or Reactor-type Dimmers. Resistance- or series reactortype dimmers shall be permitted to be placed in either the grounded or the
ungrounded conductor of the circuit. Where designed to open either the
supply circuit to the dimmer or the circuit controlled by it, the dimmer
shall then comply with Section 380-1. Resistance- or reactor-type dimmers
placed in the grounded neutral conductor of the circuit shall not open the
circuit.
(c) Autotransformer-type Dimmers. The circuit supplying an
autotransformer-type dimmer shall not exceed 150 volts between conductors. The grounded conductor shall be common to the input and output
circuits.
(d) Solid-State-type Dimmers. The circuit supplying a solid-state dimmer shall not exceed 150 volts between conductors unless the dimmer is
specifically approved for higher voltage operation. Where a grounded conductor supplies a dimmer, it shall be common to the input and output circuits. Dimmer chassis shall be connected to the equipment grounding
conductor.
(FPN): See Section 210-9 for circuits derived from autotransformers.
520-26. Type of Switchboard. Stage switchboard shall be either one or a
combination of the following types:
(a) Manual. Dimmers and switches are operated by handles mechanically linked to the control devices.
(b) Remotely Controlled. Devices are operated electrically from a pilottype control console or panel. Pilot control panels shall either be part of the
switchboard or shall be permitted to be at another location.
(c) Intermediate. A stage switchboard with circuit interconnections is a
secondary switchboard (patch panel) or panelboard remote to the primary
stage switchboard. It shall contain overcurrent protection. Where the
required branch circuit overcurrent protection is provided in the dimmer
panel, it shall be permitted to be omitted from the intermediate switchboard.
520-27. Stage Switchboard Feeders. Feeders supplying stage switchboards shall be one of the following:
(a) Single Feeder. A single feeder disconnected by a single disconnect
device. The neutral of feeders supplying solid-state, 3-phase, 4-wire dimming systems shall be considered a current-carrying conductor.
(b) Multiple Feeders to Intermediate Stage Switchboard (Patch Panel).
Multiple feeders of unlimited quantity shall be permitted, provided that all
multiple feeders are part of a single system. Where combined, neutral conductors in a given raceway shall be of sufficient ampacity to carry the
maximum unbalanced current supplied by multiple feeder conductors in
the same raceway, but need not be greater than the ampacity of the neutral supplying the primary stage switchboard. Parallel neutral conductors
shall comply with Section 310-4. The neutral of feeders supplying solidstate, 3-phase, 4-wire dimming systems shall be considered a currentcarrying conductor.
ARTICLE 520 - THEATERS AND SIMILAR LOCATIONS
70-567
(c) Separate Feeders to Single Primary Stage Switchboard (Dimmer
Bank). Installations with separate feeders to a single primary stage switchboard shall have a disconnecting means for each feeder. The primary stage
switchboard shall have a permanent and obvious label stating the number
and location of disconnecting means. If the disconnecting means are
located in more than one distribution switchboard, the primary stage
switchboard shall be provided with barriers to correspond with these multiple locations. The neutral of feeders supplying solid-state, 3-phase, 4-wire
dimming systems shall be considered a current-carrying conductor.
For purposes of computing supply capacity to switchboards, it shall be
permissible to consider the maximum load that the switchboard is intended
to control in a given installation, provided that all feeders supplying the
switchboard shall be protected by an overcurrent device with a rating not
greater than the ampacity of the feeder, and that the opening of the overcurrent device does not have any effect on the egress or emergency lighting systems.
(FPN): For computation of stage switchboard feeder loads, see Section 220-10.
C. Stage Equipment-Fixed
520-41. Circuit Loads. Footlights, border lights, and proscenium side
lights shall be so arranged that no branch circuit supplying such equipment
will carry a load exceeding 20 amperes.
Exception: Where heavy-duty lampholders only are used, such circuits
shall be permitted to comply with Article 210 for circuits supplying heavyduty lampholders.
520-42. Conductor Insulation. Foot, border, proscenium, or portable
strip light fixtures and connector strips shall be wired with conductors having insulation suitable for the temperature at which the conductors will be
operated, but not less than 125°C (257°F). The ampacity of the 125°C
(257°F) conductors shall be that of 60°C (140°F) conductors. All drops from
connector strips shall be 90°C (194°F) wire with no more than 6 inches (152
mm) of conductor extending into the connector strip. Article 310, Note
8(a), Notes to Ampacity Tables of 0 to 2000 Volts, shall not apply.
(FPN): See Table 310-13 for conductor types.
520-43. Footlights.
(a) Metal Trough Construction. Where metal trough construction is
employed for footlights, the trough containing the circuit conductors shall
be made of sheet metal not lighter than No. 20 MSG treated to prevent
oxidation. Lampholder terminals shall be kept at least ½ inch (12.7 mm)
from the metal of the trough. The circuit conductors shall be soldered to
the lampholder terminals.
(b) Other-than-Metal-Trough Construction. Where the metal trough
construction specified in Section 520-43(a) is not used, footlights shall consist of individual outlets with lampholders wired with rigid metal conduit,
intermediate metal conduit, or flexible metal conduit, Type MC cable, or
mineral-insulated, metal-sheathed cable. The circuit conductors shall be
soldered to the lampholder terminals.
70-568
NATIONAL ELECTRICAL CODE
(c) Disappearing Footlights. Disappearing footlights shall be so
arranged that the current supply will be automatically disconnected when
the footlights are replaced in the storage recesses designed for them.
520-44. Borders and Proscenium Sidelights.
(a) General. Borders and proscenium sidelights shall be (1) constructed
as specified in Section 520-43; (2) suitably stayed and supported; and (3) so
designed that the flanges of the reflectors or other adequate guards will
protect the lamps from mechanical damage and from accidental contact
with scenery or other combustible material.
(b) Cables for Border Lights. Cables for supply to border lights shall be
listed for extra-hard usage. The cables shall be suitably supported. Such
cables shall be employed only where flexible conductors are necessary.
Ampacity of the conductors shall be as provided in Section 400-5.
Exception: Listed multiconductor extra-hard usage type cords not in
direct contact with equipment containing heat-producing elements shall be
permitted to have their ampacity determined by Table 520-44. Maximum
load current in any conductor shall not exceed the values in Table 520-44.
Table 520-44. Allowable Ampacity of Listed Extra-Hard Usage Cords with
Temperature Ratings of 75°C (167°F) and 90°C (194°F)*
[Based on Ambient Temperature of 30°C (86°F)]
Size
Temperature Rating of Cord
Maximum
Rating of Over-
AWG
75° (167°F)
90°C (194°F)
current Device
14
24
28
15
12
32
35
20
10
41
47
25
8
57
65
35
6
77
87
45
4
101
114
60
2
133
152
80
*Ampacity shown is the allowable ampacity for multiconductor cords where only three
copper conductors are current-carrying. If the number of current-carrying conductors in a
cord exceeds three and the load diversity factor is a minimum of 50 percent, the allowable
ampacity of each conductor shall be reduced as shown in the following table.
Percent of
Number of
Allowable
Conductors
Ampacity
4 thru 6
80
7 thru 24
70
25 thru 42
60
43 and above
50
Note: Ultimate Insulation Temperature. In no case shall conductors be associated
together in such a way with respect to the kind of circuit, the wiring method used, or the
number of conductors such that the temperature limit of the conductors will be exceeded.
ARTICLE 520 - THEATERS AND SIMILAR LOCATIONS
70-569
520-45. Receptacles. Receptacles for electrical equipment or fixtures on
stages shall be rated in amperes.
Conductors supplying receptacles shall be in accordance with Articles
310 and 400.
520-46. Connector Strips, Drop Boxes, and Stage Pockets. Receptacles
for the connection of portable stage lighting equipment shall be pendant or
mounted in suitable pockets or enclosures and comply with Section 520-45.
Supply cables for connector strips and drop boxes shall be as specified in