Regl. 5293, art. 300-17 dup3
The derating factors given in Article 310, Note 8(a) of
Cite as Reglamento Núm. 5293, Art. 300-17 dup3
Notes to Ampacity Tables of 0 to 2000 Volts shall apply as follows:
(1) To all conductors where the fire protective signaling circuit conductors carry continuous loads in excess of 10 percent of the ampacity of each
conductor and where the total number of conductors is more than three.
(2) To the power-supply conductors only, where the fire protective
signaling circuit conductors do not carry continuous loads in excess of 10
percent of the ampacity of each conductor and where the number of
power-supply conductors is more than three.
(c) Cable Trays. Where fire protective signaling circuit conductors
are installed in cable trays, they shall comply with Sections 318-9
through 318-11.
C. Power-Limited Fire Protective Signaling Circuits
760-21. Power Limitations. As specified in Table 760-21(a) for ac circuits
and Table 760-21(b) for dc circuits, the power for power-limited fire protective signaling circuits shall be either inherently limited requiring no overcurrent protection or limited by a combination of a power source and
overcurrent protection.
760-22. Circuit Marking. The equipment shall be durably marked where
plainly visible to indicate each circuit that is a power-limited fire protective
signaling circuit.
(FPN): See Section 760-28(a), Exception No. 3 where a power-limited circuit is
to be reclassified as a nonpower-limited circuit.
760-23. Overcurrent Protection. Where overcurrent protection is
required, the overcurrent protective devices shall not be interchangeable
with devices of higher ratings. The overcurrent device shall be permitted
as an integral part of the power supply.
760-24. Location of Overcurrent Device. Overcurrent device, where
required, shall be located at the point where the conductor to be protected
receives its supply.
Table 760-21(a). Power Source Limitations for Alternating-Current Fire Protective Signaling Circuits
70-774
Inherently Limited Power Source
Not Inherently Limited Power Source
(Overcurrent protection not required)
(Overcurrent protection required)
Circuit Voltage
Over 20 and
Over 30 and
Over 20 and
Over 100 and
Vₘₐₓ (Volts) (Note 1)
0 through 20
through 30
through 100
0 through 20
through 100
through 150
Power Limitations
250
(VA) max (Volt-Amps)
-
-
-
250
N.A.
(Note 1)
(Note 2)
Current Limitations
max (Amps)
8.0
8.0
150/V max
1000/V
1000/V
1.0
max
max
(Note 1)
Maximum Overcurrent Protection
-
-
-
5.0
100/V max
1.0
(Amps)
VA
5.0 X V.
100
100
5.0 X V
100
100
Power Source
Maximum Namemax
plate Ratings
(Volt-Amps)
max
NATIONAL ELECTRICAL CODE
Current
5.0
(Amps)
100/V max
100/V max
5.0
100/V max
100/V max
Supply Conductors
and Cables
See Section 760-25
Circuit Conductors
and Cables
See Sections 760-49 through 760-53
Table 760-21(b). Power Source Limitations for Direct-Current Fire Protective Signaling Circuits
Inherently Limited Power Source
Not Inherently Limited Power Source
(Overcurrent protection not required)
(Overcurrent protection required)
Circuit Voltage
Over 20 and
Over 30 and
Over 100 and
Over 20 and
Over 100 and
Vₘₐₓ (Volts) (Note 1)
0 through 20
through 30
through 100
through 250
0 through 20
through 100
through 150
Power Limitations
250
(VA) max (Volt-Amps)
-
-
-
-
250
N.A.
(Note 2)
(Note 1)
Current Limitations
max (Amps)
8.0
8.0
150/V max
0.030
1000/V.
1000/V
1.0
max
max
(Note 1)
Maximum Overcurrent Protection
-
-
-
5.0
100/V max
1.0
(Amps)
VA
5.0 X Vₘₐₓ
100
100
0.030 X V. max
5.0 X max
100
100
Power Source
Maximum Nameplate Ratings
(Volt-Amps)
Current
5.0
100/V max
100/V max
0.030
5.0
100/V max
100/V. max
(Amps)
Supply Conductors
See Section 760-25
and Cables
ARTICLE 760 - FIRE PROTECTIVE SIGNALING SYSTEMS
Circuit Conductors
and Cables
See Sections 760-49 through 760-53
Notes for Tables 760-21(a) and (b)
Note 1. Vₘₐₓ: Maximum output voltage regardless of load with rated input applied.
Iₘₐₓ: Maximum output current under any noncapacitive load, including short circuit, and with overcurrent protection bypassed if used.
When a transformer limits the output current, Iₘₐₓ limits apply after one minute of operation. Where a current-limiting impedance, listed for the purpose, is used in combination with a nonpower-limited transformer or a stored energy source, e.g., storage battery, to limit the output current, Iₘₐₓ
limits apply after 5 seconds.
VAₘₐₓ: Maximum volt-ampere output after one minute of operation regardless of load and overcurrent protection bypassed if used. Current-
70-775
limiting impedance shall not be bypassed when determining Iₘₐₓ and VAₘₐₓ·
Note 2. If the power source is a transformer, (VA)ₘₐ is 350 or less when Vₘₐₓ is 15 or less.
70-776
NATIONAL ELECTRICAL CODE
760-25. Wiring Methods on Supply Side. Conductors and equipment on
the supply side of overcurrent protection, transformers, or current-limiting
devices shall be installed in accordance with the appropriate requirements
of Part B and Chapter 3. Transformers or other devices supplied from
power-supply conductors shall be protected by an overcurrent device rated
not over 20 amperes.
Exception: The input leads of a transformer or other power source supplying power-limited fire protective signaling circuits shall be permitted to
be smaller than No. 14, but not smaller than No. 18, if they are not over
12 inches (305 mm) long and if they have insulation that complies with