424-96. Connection to Branch-Circuit Conductors.
(a) General. Heating panels or heating panel sets assembled together in
the field to form a heating installation in one room or area shall be connected in accordance with the manufacturer's instructions.
(b) Heating Panels. Heating panels shall be connected to branch-circuit
wiring by an approved wiring method.
(c) Heating Panel Sets.
(1) Heating panel sets shall be connected to branch-circuit wiring by a
method identified as being suitable for the purpose.
(2) A heating panel set provided with terminal junction assembly shall
be permitted to have the nonheating leads attached at the time of installation in accordance with the manufacturer's instructions.
424-97. Nonheating Leads. Excess nonheating leads of heating panels or
heating panel sets shall be permitted to be cut to the required length. They
shall meet the installation requirements of the wiring method employed in
accordance with Section 424-96. Nonheating leads shall be an integral part
of a heating panel and a heating panel set and shall not be subjected to the
ampacity requirements of Section 424-3(b) for branch circuits.
424-98. Installation in Concrete or Poured Masonry.
(a) Maximum Heated Area. Heating panels or heating panel sets shall
not exceed 33 watts per square foot (0.093 sq m) of heated area.
(b) Secured in Place and Identified as Suitable. Heating panels or heating panel sets shall be secured in place by means specified in the manufacturer's instructions and identified as suitable for the installation.