Regl. 5293, art. 310-10-426 dup2
FIXED OUTDOOR DEICING
Cite as Reglamento Núm. 5293, Art. 310-10-426 dup2
70-377
B. Installation
426-10. General. Equipment for outdoor electric deicing and snow melting shall be identified as being suitable for:
(1) The chemical, thermal, and physical environment, and
(2) Installation in accordance with the manufacturer's drawings and
instructions.
426-11. Use. Electrical heating equipment shall be installed in such a
manner as to be afforded protection from physical damage.
426-12. Thermal Protection. External surfaces of outdoor electric deicing
and snow-melting equipment that operate at temperatures exceeding 60°C
(140°F) shall be physically guarded, isolated, or thermally insulated to protect against contact by personnel in the area.
426-13. Identification. The presence of outdoor electric deicing and
snow-melting equipment shall be evident by the posting of appropriate
caution signs or markings where clearly visible.
426-14. Special Permission. Fixed outdoor deicing and snow-melting
equipment employing methods of construction or installation other than
covered by this article shall be permitted only by special permission.
C. Resistance Heating Elements
426-20. Embedded Deicing and Snow-Melting Equipment.
(a) Watt Density. Panels or units shall not exceed 120 watts per square
foot (0.093 sq m) of heated area.
(b) Spacing. The spacing between adjacent cable runs is dependent
upon the rating of the cable, and shall be not less than 1 inch (25.4 mm) on
centers.
(c) Cover. Units, panels, or cables shall be installed:
(1) On a substantial asphalt or masonry base at least 2 inches (50.8 mm)
thick and have at least 1½ inches (38 mm) of asphalt or masonry applied over
the units, panels, or cables; or
(2) They shall be permitted to be installed over other approved bases
and embedded within 3½ inches (89 mm) of masonry or asphalt but not
less than 1½ inches (38 mm) from the top surface; or
(3) Equipment that has been specially investigated for other forms of
installation shall be installed only in the manner for which it has been
investigated.
(d) Secured. Cables, units, and panels shall be secured in place by
frames or spreaders or other approved means while the masonry or asphalt
finish is applied.
(e) Expansion and Contraction. Cables, units, and panels shall not be
installed where they bridge expansion joints unless provision is made for
expansion and contraction.
70-378
NATIONAL ELECTRICAL CODE
426-21. Exposed Deicing and Snow-Melting Equipment.
(a) Secured. Heating element assemblies shall be secured to the surface
being heated by approved means.
(b) Overtemperature. Where the heating element is not in direct contact
with the surface being heated, the design of the heater assembly shall be
such that its temperature limitations shall not be exceeded.
(c) Expansion and Contraction. Heating elements and assemblies shall
not be installed where they bridge expansion joints unless provision is
made for expansion and contraction.
(d) Flexural Capability. Where installed on flexible structures, the heating elements and assemblies shall have a flexural capability compatible
with the structure.
426-22. Installation of Nonheating Leads for Embedded Equipment.
(a) Grounding Sheath or Braid. Nonheating leads having a grounding
sheath or braid shall be permitted to be embedded in the masonry or
asphalt in the same manner as the heating cable without additional physical protection.
(b) Raceways. All but 1 to 6 inches (25.4 to 152 mm) of nonheating
leads of Type TW and other approved types not having a grounding sheath
shall be enclosed in a rigid conduit, electrical metallic tubing, intermediate
metal conduit, or other raceways within asphalt or masonry; and the distance from the factory splice to raceway shall be not less than 1 inch
(25.4 mm) or more than 6 inches (152 mm).
(c) Bushings. Insulating bushings shall be used in the asphalt or
masonry where leads enter conduit or tubing.
(d) Expansion and Contraction. Leads shall be protected in expansion
joints and where they emerge from masonry or asphalt by rigid conduit,
electrical metallic tubing, intermediate metal conduit, other raceways, or
other approved means.
(e) Leads in Junction Boxes. Not less than 6 inches (152 mm) of free
nonheating lead shall be within the junction box.
426-23. Installation of Nonheating Leads for Exposed Equipment.
(a) Nonheating Leads. Power supply nonheating leads (cold leads) for
resistance elements shall be suitable for the temperature encountered. Preassembled nonheating leads on approved heaters shall be permitted to be
shortened if the markings specified in Section 426-25 are retained. Not less
than 6 inches (152 mm) of nonheating leads shall be provided within the
junction box.
(b) Protection. Nonheating power supply leads shall be enclosed in a
rigid conduit, intermediate metal conduit, electrical metallic tubing, or
other approved means.
426-24. Electrical Connection.
(a) Heating Element Connections. Electrical connections, other than
factory connections of heating elements to nonheating elements embedded