Regl. 5293, art. 310-10-426 dup3
FIXED OUTDOOR DEICING
Cite as Reglamento Núm. 5293, Art. 310-10-426 dup3
70-379
in masonry or asphalt or on exposed surfaces, shall be made with insulated
connectors identified for the use.
(b) Circuit Connections. Splices and terminations at the end of the nonheating leads, other than the heating element end, shall be installed in a
box or fitting in accordance with Sections 110-14 and 300-15.
426-25. Marking. Each factory-assembled heating unit shall be legibly
marked within 3 inches (76 mm) of each end of the nonheating leads with
the permanent identification symbol, catalog number, and ratings in volts
and watts, or in volts and amperes.
426-26. Corrosion Protection. Ferrous and nonferrous metal raceways,
cable armor, cable sheaths, boxes, fittings, supports, and support hardware
shall be permitted to be installed in concrete or in direct contact with the
earth, or in areas subject to severe corrosive influences, where made of
material suitable for the condition, or where provided with corrosion protection identified as suitable for the condition.
426-27. Grounding.
(a) Metal Parts. Exposed noncurrent-carrying metal parts of equipment
likely to become energized shall be bonded together and grounded in a
manner specified in Article 250.
(b) Grounding Braid or Sheath. Grounding means, such as copper
braid, metal sheath, or other approved means, shall be provided as part of
the heated section of the cable, panel, or unit.
D. Impedance Heating
426-30. Personnel Protection. Exposed elements of impedance heating
systems shall be physically guarded, isolated, or thermally insulated with
weatherproof jacket to protect against contact by personnel in the area.
vs426-31. Voltage Limitations. The impedance heating elements shall not
operate at a voltage greater than 30 volts ac.
Exception: The voltage shall be permitted to be greater than 30 volts,
but not more than 80 volts, if a ground-fault circuit-interrupter for personnel protection is provided.
426-32. Isolation Transformer. A dual-winding transformer with a
grounded shield between the primary and secondary windings shall be
used to isolate the distribution system from the heating system.
426-33. Induced Currents. All current-carrying components shall be
installed in accordance with Section 300-20.
426-34. Grounding. An impedance heating system that is operating at a
voltage greater than 30, but not more than 80, shall be grounded at designated point(s).
70-380
NATIONAL ELECTRICAL CODE
E. Skin Effect Heating
426-40. Conductor Ampacity. The current through the electrically insulated conductor inside the ferromagnetic envelope shall be permitted to
exceed the ampacity values shown in Article 310, provided it is identified
as suitable for this use.
426-41. Pull Boxes. Where pull boxes are used, they shall be accessible
without excavation by location in suitable vaults or above grade. Outdoor
pull boxes shall be of watertight construction.
426-42. Single Conductor in Enclosure. The provisions of Section 300-20
shall not apply to the installation of a single conductor in a ferromagnetic
envelope (metal enclosure).
426-43. Corrosion Protection. Ferromagnetic envelopes, ferrous or nonferrous metal raceways, boxes, fittings, supports, and support hardware
shall be permitted to be installed in concrete or in direct contact with the
earth, or in areas subjected to severe corrosive influences, where made of
material suitable for the condition, or where provided with corrosion protection identified as suitable for the condition. Corrosion protection shall
maintain the original wall thickness of the ferromagnetic envelope.
426-44. Grounding. The ferromagnetic envelope shall be grounded at
both ends; and, in addition, it shall be permitted to be grounded at intermediate points as required by its design.
The provisions of Section 250-26 shall not apply to the installation of
skin effect heating systems.
(FPN): For grounding methods, see Section 250-26(d).
F. Control and Protection
426-50. Disconnecting Means.
(a) Disconnection. All fixed outdoor deicing and snow-melting equipment shall be provided with a means for disconnection from all
ungrounded conductors. Where readily accessible to the user of the equipment, the branch-circuit switch or circuit breaker shall be permitted to
serve as the disconnecting means. Switches used as the disconnecting
means shall be of the indicating type.
(b) Cord- and Plug-Connected Equipment. The factory-installed attachment plug of cord- and plug-connected equipment rated 20 amperes or less
and 150 volts or less to ground shall be permitted to be the disconnecting
means.
426-51. Controllers.
(a) Temperature Controller with "Off" Position. Temperature controlled
switching devices that indicate an "off" position and that interrupt line
current shall open all ungrounded conductors when the control device is in
the "off" position. These devices shall not be permitted to serve as the
disconnecting means unless provided with a positive lockout in the "off"
position.