Regl. 5293, art. 310-10-427 dup2
FIXED ELECTRIC HEATING EQUIPMENT
Cite as Reglamento Núm. 5293, Art. 310-10-427 dup2
FOR PIPELINES AND VESSELS
A. General
427-1. Scope. The requirements of this article shall apply to electrically
energized heating systems and the installation of these systems used with
pipelines or vessels or both.
427-2. Definitions. For the purpose of this article:
Pipeline: A length of pipe including pumps, valves, flanges, control
devices, strainers and/or similar equipment for conveying fluids.
Vessel: A container such as a barrel, drum, or tank for holding fluids
or other material.
Integrated Heating System: A complete system consisting of components such as pipelines, vessels, heating elements, heat transfer medium,
70-382
NATIONAL ELECTRICAL CODE
thermal insulation, moisture barrier, nonheating leads, temperature controllers, safety signs, junction boxes, raceways, and fittings.
Resistance Heating Element: A specific separate element to generate
heat that is applied to the pipeline or vessel externally or internally.
(FPN): Tubular heaters, strip heaters, heating cable, heating tape, heating blankets, and immersion heaters are examples of resistance heaters.
Impedance Heating System: A system in which heat is generated in a
pipeline or vessel wall by causing current to flow through the pipeline or
vessel wall by direct connection to an ac voltage source from a dualwinding transformer.
Induction Heating System: A system in which heat is generated in a
pipeline or vessel wall by inducing current and hysteresis effect in the
pipeline or vessel wall from an external isolated ac field source.
Skin Effect Heating System: A system in which heat is generated on
the inner surface of a ferromagnetic envelope attached to a pipeline and/or
vessel.
(FPN): Typically, an electrically insulated conductor is routed through and connected to the envelope at the other end. The envelope and the electrically insulated
conductor are connected to an ac voltage source from a dual-winding transformer.
427-3. Application of Other Articles. All requirements of this Code shall
apply except as specifically amended in this article. Cord-connected pipe
heating assemblies intended for specific use and identified as suitable for
this use shall be installed according to Article 422. Fixed electric pipeline
and vessel heating equipment for use in hazardous (classified) locations
shall comply with Articles 500 through 516.
427-4. Branch-Circuit Sizing. The ampacity of branch-circuit conductors
and the rating or setting of overcurrent protective devices supplying fixed
electric heating equipment for pipelines and vessels shall be not less than
125 percent of the total load of the heaters. The rating or setting of overcurrent protective devices shall be permitted in accordance with Section
240-3(b).
B. Installation
427-10. General. Equipment for pipeline and vessel electrical heating
shall be identified as being suitable for (1) the chemical, thermal, and physical environment; and (2) installation in accordance with the manufacturer's drawings and instructions.
427-11. Use. Electrical heating equipment shall be installed in such a
manner as to be afforded protection from physical damage.
427-12. Thermal Protection. External surfaces of pipeline and vessel
heating equipment that operate at temperatures exceeding 60°C (140°F)
shall be physically guarded, isolated, or thermally insulated to protect
against contact by personnel in the area.
ARTICLE 427 - FIXED HEATING FOR PIPELINES
70-383
427-13. Identification. The presence of electrically heated pipelines or
vessels, or both, shall be evident by the posting of appropriate caution
signs or markings at frequent intervals along the pipeline or vessel.
C. Resistance Heating Elements
427-14. Secured. Heating element assemblies shall be secured to the surface being heated by means other than the thermal insulation.
427-15. Not in Direct Contact. Where the heating element is not in direct
contact with the pipeline or vessel being heated, means shall be provided
to prevent overtemperature of the heating element unless the design of the
heater assembly is such that its temperature limitations will not be
exceeded.
427-16. Expansion and Contraction. Heating elements and assemblies
shall not be installed where they bridge expansion joints unless provisions
are made for expansion and contraction.
427-17. Flexural Capability. Where installed on flexible pipelines, the
heating elements and assemblies shall have a flexural capability compatible
with the pipeline.
427-18. Power Supply Leads.
(a) Nonheating Leads. Power supply nonheating leads (cold leads) for
resistance elements shall be suitable for the temperature encountered. Preassembled nonheating leads on approved heaters shall be permitted to be
shortened if the markings specified in Section 427-20 are retained. Not less
than 6 inches (152 mm) of nonheating leads shall be provided within the
junction box.
(b) Power Supply Leads Protection. Nonheating power supply leads
shall be protected where they emerge from electrically heated pipeline or
vessel heating units by rigid metal conduit, intermediate metal conduit,
electrical metallic tubing, or other raceways identified as suitable for the
application.
(c) Interconnecting Leads. Interconnecting nonheating leads connecting portions of the heating system shall be permitted to be covered by
thermal insulation in the same manner as the heaters.
427-19. Electrical Connections.
(a) Nonheating Interconnections. Nonheating interconnections, where
required under thermal insulation, shall be made with insulated connectors
identified as suitable for this use.
(b) Circuit Connections. Splices and terminations outside the thermal
insulation shall be installed in a box or fitting in accordance with Sections
110-14 and 300-15.
70-384
NATIONAL ELECTRICAL CODE
427-20. Marking. Each factory-assembled heating unit shall be legibly
marked within 3 inches (76 mm) of each end of the nonheating leads with
the permanent identification symbol, catalog number, and ratings in volts
and watts, or in volts and amperes.
427-21. Grounding. Exposed noncurrent-carrying metal parts of electric
heating equipment that are likely to become energized shall be grounded as
required in Article 250.
427-22. Equipment Protection. Ground-fault protection of equipment
shall be provided for branch circuits supplying electric heating equipment
not having a metal covering.
427-23. Nonmetallic Pipelines. Heating assemblies intended for heating
covering. nonmetallic pipelines or vessels shall have an overall grounded metal
D. Impedance Heating
427-25. Personnel Protection. All accessible external surfaces of the
pipeline and/or vessel being heated shall be physically guarded, isolated, or
thermally insulated (with weatherproof jacket for outside installations) to
protect against contact by personnel in the area.
427-26. Voltage Limitations. The secondary winding of the isolation
transformer (Section 427-27) connected to the pipeline or vessel being
heated shall not have an output voltage greater than 30 volts ac.
Exception: The voltage shall be permitted to be greater than 30 volts
but not more than 80 volts if a ground-fault circuit-interrupter for personnel protection is provided.
427-27. Isolation Transformer. A dual-winding transformer with a
grounded shield between the primary and secondary windings shall be
used to isolate the distribution system from the heating system.
427-28. Induced Currents. All current-carrying components shall be
installed in accordance with Section 300-20.
427-29. Grounding. The pipeline or vessel, or both, being heated that is
operating at a voltage greater than 30 but not more than 80 shall be
grounded at designated points.
427-30. Secondary Conductor Sizing. The ampacity of the conductors
connected to the secondary of the transformer shall be at least 100 percent
of the total load of the heater.
E. Induction Heating
427-35. Scope. This part covers the installation of line frequency induction heating equipment and accessories for pipelines and vessels.
(FPN): See Article 665 for other applications.
ARTICLE 427 - FIXED HEATING FOR PIPELINES
70-385
427-36. Personnel Protection. Induction coils that operate or may operate at a voltage greater than 30 volts ac shall be enclosed in a nonmetallic
or split metallic enclosure, isolated or made inaccessible by location to
protect personnel in the area.
427-37. Induced Current. Induction coils shall be prevented from inducing circulating currents in surrounding metallic equipment, supports, or
structures by shielding, isolation, or insulation of the current paths. Stray
current paths shall be bonded to prevent arcing.
F. Skin Effect Heating
427-45. Conductor Ampacity. The ampacity of the electrically insulated
conductor inside the ferromagnetic envelope shall be permitted to exceed the
values given in Article 310, provided it is identified as suitable for this use.
427-46. Pull Boxes. Pull boxes for pulling the electrically insulated conductor in the ferromagnetic envelope shall be permitted to be buried under
the thermal insulation, provided their locations are indicated by permanent
markings on the insulation jacket surface and on drawings. For outdoor
installations, pull boxes shall be of watertight construction.
427-47. Single Conductor in Enclosure. The provisions of Section 300-20
shall not apply to the installation of a single conductor in a ferromagnetic
envelope (metal enclosure).
427-48. Grounding. The ferromagnetic envelope shall be grounded at
both ends and, in addition, it shall be permitted to be grounded at intermediate points as required by its design. The ferromagnetic envelope shall be
bonded at all joints to assure electrical continuity.
The provisions of Section 250-26 shall not apply to the installation of
skin effect heating systems.
(FPN): See Section 250-26(d) for grounding methods.
G. Control and Protection
427-55. Disconnecting Means.
(a) Switch or Circuit Breaker. Means shall be provided to disconnect all
fixed electric pipeline or vessel heating equipment from all ungrounded
conductors. The branch-circuit switch or circuit breaker, where readily
accessible to the user of the equipment, shall be permitted to serve as the
disconnecting means. The disconnecting means shall be of the indicating
type, and shall be provided with a positive lockout in the "off" position.
(b) Cord- and Plug-Connected Equipment. The factory-installed attachment plug of cord- and plug-connected equipment rated 20 amperes or less
and 150 volts or less to ground shall be permitted to be the disconnecting
means.
70-386
NATIONAL ELECTRICAL CODE
427-56. Controls.
(a) Temperature Control with "Off" Position. Temperature controlled
switching devices that indicate an "off" position and that interrupt line
current shall open all ungrounded conductors when the control device is in
this "off" position. These devices shall not be permitted to serve as the
disconnecting means unless provided with a positive lockout in the "off"
position.
(b) Temperature Control Without "Off" Position. Temperature controlled switching devices that do not have an "off" position shall not be
required to open all ungrounded conductors and shall not be permitted to
serve as the disconnecting means.
(c) Remote Temperature Controller. Remote controlled temperatureactuated devices shall not be required to meet the requirements of Sections
427-56(a) and (b). These devices shall not be permitted to serve as the disconnecting means.
(d) Combined Switching Devices. Switching devices consisting of combined temperature-actuated devices and manually controlled switches that
serve both as the controllers and the disconnecting means shall comply
with all the following conditions:
(1) Open all ungrounded conductors when manually placed in the
"off" position; and
(2) Be so designed that the circuit cannot be energized automatically if
the device has been manually placed in the "off" position; and
(3) Be provided with a positive lockout in the "off" position.
427-57. Overcurrent Protection. Heating equipment shall be considered
as protected against overcurrent where supplied by a branch circuit as
specified in Section 427-4.